background image

page 8

Fig. 1

219

1.220

613

32

212

151

930

38

171

160

69

40

136

190

910

219

212

150

657

1.10 DIMENSIONS - WR and WD versions for ceiling installation

Bottom view of
the WR version

Front view of the WR version

Front view of the WD version

Side view of the WR version

Side view of the WD version

Rear view of the WR version

Rear view of the WD version

 ISO 228/1 G1/2”A gas connection

Air intake, Ø 60

190

108

Flue gas discharge, Ø 60

Air filter

Optional timer cable outlet

Electric power supply cable inlet

Control panel cable outlet

page 29

7.   OPERATING DEFECTS

7.1 PRELIMINARY TESTS

Before performing specific tests, make sure that:

a) The electric power supply is properly connected

(pay particular attention to the phase-neutral
polarity and ground connector) and that any
external adjustment components (for example,
the programmable timer) function correctly.

b) The gas supply is correct, the gas on-off valve

is open, and the pressure to the burner
corresponds to what is indicated in the
technical data table.

c) The external terminals of the combustion air

intake duct and the combustion product
exhaust flue are not obstructed and that the
material they are made of has not deteriorated.

d) The control panel functions correctly.

7.2 POSSIBLE DEFECTS

The following is a list of possible defects along
with their probable causes. The information
indicated in italics refers to repair operations or
corrections which are the responsibility of the
authorised Technical Service Centre.

7.2.1 The appliance does not start even if the

conditions described in the previous
points are correct.

a) the flame detection circuit of the control

equipment is malfunctioning and the initial self-
check does not allow the cycle to continue.

-

Replace the control equipment (see point
8.1).

b) The flame detection electrode has an earth

leakage.

-

Check the correct position of the electrode.
The ceramic insulation material may be
cracked and this is difficult to determine
visually. In case of doubt, replace the electrode
(see point 8.7).

c) The differential pressure switch’s contacts

are frozen in the position they assume when
the draft is correct.

-

Change the pressure switch if its microswitch
does not reset the contacts to the proper
position (see point 8.4).

d) The flue gas expeller fan’s motor has failed

and the differential pressure switch will not
allow startup to proceed.

-

Change the fan. Be careful to reassemble the
unit as shown in figure 31 (see point 8.8).

7.2.2 The control equipment does not shut

down, but the cycle remains in a
continuous preventilation phase

a) The differential pressure switch will not allow

startup to proceed because the flue gas
exhaust flue or the air supply duct is
obstructed.

-

First eliminate any obstructions from the
terminals. In any case check the entire path of
the ducts for damage or alterations.

b) The differential pressure switch will allow

startup to proceed because the flue gas
expeller fan does not function correctly and
does not develop enough suction.

-

Check to see if there are any problems of
wear with the rotation of the fan motor. Make
sure that the fan is positioned correctly, that
there is nothing that interferes with the rotation,
and that there are not any deformations. If
necessary, change the fan. Be careful to
reassemble the unit as shown in figure 31
(see point 8.8).

c) The differential pressure switch will not allow

startup to proceed because it is broken or its
electrical connection has been interrupted.

-

Check that the connection cable and the
corresponding terminals are in good condition.
Do not attempt to adjust the pressure switch
by removing the seal; instead, change it.

d) The differential pressure switch will not allow

startup to proceed because the pressure inlet
tube is obstructed or the silicone connection
tube is disconnected or broken.

-

Make sure that the silicone tube is connected
correctly and that it does not have any holes
or cuts in it. If it is not damaged, check the
steel pressure inlet tube and remove any
obstructions or deposits from it. It will be
necessary to access the inside of the
exchanger’s flue gas collector to completely
carry out this operation.

7.2.3 At the end of the preventilation phase,

the ignition electrodes do not discharge
and the control equipment shuts down
within the safety time

a) The ignition transformer is malfunctioning.

-

Replace the controller which contains the
transformer. Because these are electronic
components, it is advisable not to attempt to
replace just the transformer, especially if you
do not use the proper tools.

Summary of Contents for W

Page 1: ...A2B srl Via d Ancona 37 60027 Osimo An Tel 071 723991 Fax 071 7133153 Web Site www accorroni it E mail a2b a 2 b it Technical information W WR WD Gas fired convection heaters with fan W WR WD...

Page 2: ......

Page 3: ...al data table 7 1 10 Dimensions WR and WD versions 8 page 36 Gas fired convection heaters with fan W WR WD series Models 8 10 Technical Information Code 25259501 GB Rev 3 10 05 05 WARNING Whentheburne...

Page 4: ...open and the electric power supply is on 10 3 2 The instructions to the control panel functions which follow refer to fig 35 a Turn the room thermostat knob E clockwise to the maximum value b Turn swi...

Page 5: ...e user to carry out the operations indicated in point 11 1 of this manual at least once every two months 9 2 YEARLY INSPECTION 9 2 1 Control and safety devices WARNING Specific technical skills are re...

Page 6: ...this solution would present technical or functional advantages For ceiling installation WR version in rooms where there is not enough free space on the walls For ceiling installation with duct con nec...

Page 7: ...d a combustion chamber which houses an atmospheric burner which generates an axial flame The combustion products are exhausted outdoors by a centrifugal fan The ventilation unit which is made up of tw...

Page 8: ...e the remodelingofbuildingunitsasresidences offices stores orworkshopsiscomplicatedbyaseriesof technical and structural problems that make it difficult to install a traditional heating system These sy...

Page 9: ...first checking the on off valves on the delivery line Completely bleed off any residual air and restart the unit b Thegassolenoidvalvesdonotopenbecause the coils are malfunctioning or their electrica...

Page 10: ...tch does not reset the contacts to the proper position see point 8 4 d The flue gas expeller fan s motor has failed and the differential pressure switch will not allow startup to proceed Change the fa...

Page 11: ...y plastic caps and then using the point of a screwdriverasalevertoreleasethefastening springs in the rear d Remove the 2 screws which attach the gas supply pipe connector to the combustion chamber fig...

Page 12: ...ses and about the importance of periodic tests which must be performed at least once every year by skilled personnel 6 GAS TYPE CHANGE 6 1 SWITCHING FROM GAS IN THE SECOND GROUP NATURAL GAS TO GAS IN...

Page 13: ...ressure of 20 mbar Instead if gas from the third group is used LPG first carry out the operations described in point 6 1 5 1 4 Check that the gas on off valves on the meter and on the air heater are o...

Page 14: ...the wall with a center distance of 120 mm Insert the screw anchors and attach the rear part of the panel to the wall Put the front part of the panel back by snapping it in place Ifyoushouldneedtoinse...

Page 15: ...R and WD WARNING For your safety due to the weight of the unit and the possible difficulties of installingit itisadvisabletouseamechanical hoisting device for positioning the air heater For these same...

Page 16: ...ts must be made on the free ends opposite the wind protection terminals Make sure that they are cut squarely and trim off any burrs NOTE The exhaust flue is the longer of the two c Insert the ducts in...

Page 17: ...R and WD Once the unit s position has been determined bend the supplied paper template on the dashed line and apply it to the ceiling with adhesive tape fig 17 a Indicate the position of the four hole...

Page 18: ...from ACCORRONI S r l In any case any increases to the length of the ducts must respect the limits specified in the next point 4 2 2 Duct length limits If the duct passes directly through an outside w...

Page 19: ...between the rear part of the unit and the wall so as to permit correct air intake and to allow the filter to easily be removed for cleaning fig 13 For the WD version make sure that the air intake sys...

Page 20: ...k making sure to observe the instructions reported on the box indicated by the special graphic symbols When delivered check that no visible damage on the packing and or on the appliance has occurred d...

Reviews: