background image

page 12

Fig. 4

1.11  EXPLODED VIEW - WD version with ducts for ceiling installation

page 25

mm and which has an adequate capacity, to
be used as a general switch to turn off the
units.

Insert the power supply cable through its bushing,
making sure to cut the wires so that the yellow/
green ground cable is longer than the other two.
In case of accidental disconnection this
precaution allows the ground cable to be
disconnected last.

Connect the power supply cable to the phase
connectors (L), to the neutral wire (N) of the
mains filter (FR), and to the air heater’s ground
terminal (see the wiring diagram). Use the
supplied 6.3 x 0.8 mm faston type terminals to
connect the phase and neutral wires.

Observe phase/neutral polarity, otherwise
the control equipment will generate a safety
shutdown. Verify that the system has been
grounded in compliance with the electrical
standards.

4.4.6 Remote-control panel (only for the WR

and WD versions to be ceiling installed)

The remote-control panel is equipped with a
probe for measuring the room temperature. Its
position must be chosen not only for ease of use,
but also so as to avoid air currents, heat sources,
and sources of excessive humidity which could
alter the temperature measurement.

Also avoid installing it in recesses. Do not obstruct
the openings in the panel for the same reasons
as in the last paragraph. However, it is advisable
to install it at a height of approximately 1.5
meters from the ground.

To install it on the wall, use the two screw
anchors supplied with a diameter of 4 mm.
Unhook the rear part of the panel by using the
proper tools to release the four snap fasteners.

Make two holes in the wall with a center distance
of 120 mm. Insert the screw anchors and attach
the rear part of the panel to the wall. Put the front
part of the panel back by snapping it in place.

If you should need to insert the panel’s connection
cable inside trunking, you must disconnect the
cable from the terminal board on the panel.
When you have put the cable in place, re-
establish the electrical connection by putting the
cable in its proper position on the terminal board
(see the wiring diagram).

If you need to insert it in trunking underneath, the
cable could exit from the wall in correspondence
to the hole in the rear part of the panel, so as not
to leave the cable in view. The original hole

which the cable should have passed through must
be closed with the plastic cap provided. If the
panel is attached to a metal structure or wall, this
structure or wall must be grounded.

4.4.7 Using a programmable timer

If you would like to have the air heater function
automatically at preset times, it is possible to
install a programmable timer.

A jumper for auxiliary connections (OP - see the
wiring diagram
) is provided on the unit’s electrical
board between the J14 and J15 faston connectors
(4.8 x 0.8 mm type) of the terminal board on the
printed circuit. Remove the jumper and connect
the above connectors to the timer’s switch. Use
the bushing (fig. 1) for the connection cable’s
exit.

4.4.8 Connecting more than one unit with a

single external programmable timer

To operate several units with just one
programmable timer follow the diagram in figure
21
 and use the same J14 and J15 connectors
listed in the previous point. You have to use a
normally-open contact relay with an adequate
rating to make this special connection.

Fig. 21

J14
J15

n

2

1

n

2

1

J14
J15

J14
J15

2

nd

air heater

1

st

air heater

n

th

air heater

Timer

switch

Relay with
n contacts

Neutral wire

Phase wire

Summary of Contents for W

Page 1: ...A2B srl Via d Ancona 37 60027 Osimo An Tel 071 723991 Fax 071 7133153 Web Site www accorroni it E mail a2b a 2 b it Technical information W WR WD Gas fired convection heaters with fan W WR WD...

Page 2: ......

Page 3: ...al data table 7 1 10 Dimensions WR and WD versions 8 page 36 Gas fired convection heaters with fan W WR WD series Models 8 10 Technical Information Code 25259501 GB Rev 3 10 05 05 WARNING Whentheburne...

Page 4: ...open and the electric power supply is on 10 3 2 The instructions to the control panel functions which follow refer to fig 35 a Turn the room thermostat knob E clockwise to the maximum value b Turn swi...

Page 5: ...e user to carry out the operations indicated in point 11 1 of this manual at least once every two months 9 2 YEARLY INSPECTION 9 2 1 Control and safety devices WARNING Specific technical skills are re...

Page 6: ...this solution would present technical or functional advantages For ceiling installation WR version in rooms where there is not enough free space on the walls For ceiling installation with duct con nec...

Page 7: ...d a combustion chamber which houses an atmospheric burner which generates an axial flame The combustion products are exhausted outdoors by a centrifugal fan The ventilation unit which is made up of tw...

Page 8: ...e the remodelingofbuildingunitsasresidences offices stores orworkshopsiscomplicatedbyaseriesof technical and structural problems that make it difficult to install a traditional heating system These sy...

Page 9: ...first checking the on off valves on the delivery line Completely bleed off any residual air and restart the unit b Thegassolenoidvalvesdonotopenbecause the coils are malfunctioning or their electrica...

Page 10: ...tch does not reset the contacts to the proper position see point 8 4 d The flue gas expeller fan s motor has failed and the differential pressure switch will not allow startup to proceed Change the fa...

Page 11: ...y plastic caps and then using the point of a screwdriverasalevertoreleasethefastening springs in the rear d Remove the 2 screws which attach the gas supply pipe connector to the combustion chamber fig...

Page 12: ...ses and about the importance of periodic tests which must be performed at least once every year by skilled personnel 6 GAS TYPE CHANGE 6 1 SWITCHING FROM GAS IN THE SECOND GROUP NATURAL GAS TO GAS IN...

Page 13: ...ressure of 20 mbar Instead if gas from the third group is used LPG first carry out the operations described in point 6 1 5 1 4 Check that the gas on off valves on the meter and on the air heater are o...

Page 14: ...the wall with a center distance of 120 mm Insert the screw anchors and attach the rear part of the panel to the wall Put the front part of the panel back by snapping it in place Ifyoushouldneedtoinse...

Page 15: ...R and WD WARNING For your safety due to the weight of the unit and the possible difficulties of installingit itisadvisabletouseamechanical hoisting device for positioning the air heater For these same...

Page 16: ...ts must be made on the free ends opposite the wind protection terminals Make sure that they are cut squarely and trim off any burrs NOTE The exhaust flue is the longer of the two c Insert the ducts in...

Page 17: ...R and WD Once the unit s position has been determined bend the supplied paper template on the dashed line and apply it to the ceiling with adhesive tape fig 17 a Indicate the position of the four hole...

Page 18: ...from ACCORRONI S r l In any case any increases to the length of the ducts must respect the limits specified in the next point 4 2 2 Duct length limits If the duct passes directly through an outside w...

Page 19: ...between the rear part of the unit and the wall so as to permit correct air intake and to allow the filter to easily be removed for cleaning fig 13 For the WD version make sure that the air intake sys...

Page 20: ...k making sure to observe the instructions reported on the box indicated by the special graphic symbols When delivered check that no visible damage on the packing and or on the appliance has occurred d...

Reviews: