Charger
Charge Current (Max.) Standard
2.1A
1.5A
1.5A
Supplementary Charger (Max.)
5A x 1
4A x 2
4A x 2
Recharge time (to 90%)
4hr
4hr
6hr
Floating Mode Charging Voltage
40.9V±1%
81.9V±1%
81.9V±1%
Bulk Mode Charging Voltage
42.3V±1%
84.6V±1%
84.6V±1%
Transfer time
AC to DC
0 ms
Inverter to Bypass
4ms(Typical)
Programmable outlet
Programmable relay
support 2 output groups
Protection
Short Circuit
Bypass mode : Breaker
Normal Mode : Output Breaker/Electronic Circuit
Battery Mode : Output Breaker/Electronic Circuit
Battery
ABDM
EPO
UPS shuts down immediately.
Over Temperature
Normal Mode: Transfer to Bypass Mode
Battery Mode: UPS shuts down immediately
Physical
Dimensions
W x H x D
2U
model
(mm)
(inches)
440x88x405
17.3x3.5x15.9
440x88x600
17.3x3.5x23.6
440x88x600
17.3x3.5x23.6
Tower
model
(mm)
(inches)
154x214x388
6.0x8.8x15.3
192x250x475
7.5x9.8x18.6
192x320x451
7.5x12.6x17.7
Net Weight
2U
model
(kg)
(lbs)
11.7 kg
25.8 lbs
21.8 kg
48 lbs
24.6 kg
54.2 lbs
Tower
model
(kg)
(lbs)
11.6 kg / 25.6 lbs
22.2 kg / 48.9 lbs
29.8 kg / 65.7 lbs
Interface
Compatible Platforms
Microsoft Windows series, Linux, Mac, etc.
Environmental
Operating Temperature
Operating : 0ºC ~ 40ºC (32ºF to 104ºF)
Storage : -10ºC ~ 50ºC (14ºF to 122ºF)
Noise Level
≦
50dB
Relative Humidity
0-90% (without condensation)
Standards and Certifications
Safety
IEC/EN 62040-1
EMC
EN62040-2, EN61000-3-2, EN61000-3-3
Markings
CE, UKCA
ARES UPS User Manual
22
EN
Summary of Contents for ARES
Page 128: ...Ablerex Ablerex Ablerex www ablerex eu Pb...
Page 130: ...UPS UPS UPS UPS UPS 30 cm UPS AC UPS ARES UPS 130 EL...
Page 131: ...a b c d ARES UPS 131 EL...
Page 133: ...LCD LCD UPS UPS UPS UPS 3 ARES UPS 133 EL...
Page 144: ...UPS LED LED Er05 Er39 8 UPS DC UPS Er11 UPS L N AC Er14 UPS 8 ARES UPS 144 EL...