Operation of measurements display
UPS measurements can be checked after UPS started by pressing select key
. The display sequence
are as below figure-F~M.
figure_F (AC input voltage)
figure_G (AC input frequency)
figure_H (UPS output voltage)
figure_I (UPS output frequency)
figure-J (UPS loading percentage)
figure-K (UPS output current)
figure-L (Battery voltage)
figure-M (UPS inner temperature)
UPS Locked up
UPS UPS will locked up when encountering abnormal or failure condition. Refer to the LCD display as
shown below figure-N.
1. The procedures to release UPS from locked up status as below:
2. Check and record the error code.
3. Check user’s manual to understand possible cause, solve the problem or call service provider.
4. Press OFF key
and hold for 5 seconds until twice beep heard.
5. Unplug AC input power cord or turn off power source switch.
6. After UPS completely shut off, UPS is unlocked.
ARES UPS User Manual
13
EN