Situation
Check Items
Solution
The UPS switches into battery mode
and then back into utility mode when
a connected device is turned on,
or the UPS switches back and forth
between battery and utility modes.
A power strip is connected to the
UPS.
See if there is any damage to the
utility wall receptacle or if the cord
plug is faulty.
Do not use the power strip.
Replace the wall receptacle/cord
plug.
Strange noise or smell
Shut down the whole system
immediately. Disconnect the power
from the UPS and contact your local
dealer.
UPS is unable to provide backup
power.
Check that the battery connectors
are fully engaged. Allow the batteries
to recharge if they are weak. If the
problem persists after recharging the
batteries, consult your local dealer for
assistance.
Checking error code on LCD panel:
If UPS is in abnormal condition common alarm sign
will light up and come with audible alarm. The
LCD screen will shows information of alternate normal and error code. You can follow section 5 and 0 up
for troubleshooting.
Code
Meaning
Er05
Battery weak or faulty
Er06
Output short-circuited
Er07
EPO mode
Er11
UPS over-temperature
Er12
Inverter overload
Er14
Fan errors
Er39
When UPS start process, Utility Voltage less than 90V and Battery no connection.
Er28
Bypass overload
Maintenance
1. Clean the dust from the ventilation openings and intakes on the rear panel.
2. Turn off the UPS and wipe the casing with a damp cloth. Be careful to avoid getting water in the UPS.
3. Periodically unplug the power cord of the UPS from the wall receptacle to test the condition of the
batteries. Be sure you have saved your data in any open computer applications before you proceed
with this battery test.
ARES UPS User Manual
19
EN
Summary of Contents for ARES
Page 128: ...Ablerex Ablerex Ablerex www ablerex eu Pb...
Page 130: ...UPS UPS UPS UPS UPS 30 cm UPS AC UPS ARES UPS 130 EL...
Page 131: ...a b c d ARES UPS 131 EL...
Page 133: ...LCD LCD UPS UPS UPS UPS 3 ARES UPS 133 EL...
Page 144: ...UPS LED LED Er05 Er39 8 UPS DC UPS Er11 UPS L N AC Er14 UPS 8 ARES UPS 144 EL...