COMMUNICATION SOFTWARE
Hardware Setup
Connect to either RS-232 communication or USB communication.
Connect a male RS-232 connector or a USB cable* to the UPS communication port. Connect the female
RS-232 connector or the other end of the USB cable to the computer.
*Note: RS-232 cable is optional.
Software Installation
Please refer to the PowerMaster user’s manual.
TECHNICAL SPECIFICATION
Model
230V – 1K
230V – 2K
230V – 3K
Capacity
VA
1000 VA
2000 VA
3000 VA
W
900W
1800W
2700W
Input
Voltage Rating
110/150/180~300 VAC (Based on load percentage0 ~ 60% / 0 ~ 75% / 0 ~ 100%)
Frequency Rating
44-66 Hz
50Hz fin> 44Hz and fin < 56Hz
60Hz fin> 54Hz and fin < 66Hz
Phase
Single phase with ground
Power Factor
≧
0.99 at full linear load
Current harmonic distortion (THDi)
<7% at full load and nominal voltage
Generator Input
Supported
Output
Voltage
230 V, adjustable to 200/208/220/230/240
Voltage Regulation
Static: within ±1% until low-battery warning
Frequency(Synchronized Range)
3 Hz or 1 Hz (selectable)
Frequency (Battery Mode)
50/60 Hz ±0.2% unless synchronized to line
Current Crest Ratio
3:1
Voltage Harmonic Distortion(THDv)
< 3% at full linear load
< 6% at full non-linear load
Output Waveform
Pure sine wave
ARES UPS User Manual
20
EN
Summary of Contents for ARES
Page 128: ...Ablerex Ablerex Ablerex www ablerex eu Pb...
Page 130: ...UPS UPS UPS UPS UPS 30 cm UPS AC UPS ARES UPS 130 EL...
Page 131: ...a b c d ARES UPS 131 EL...
Page 133: ...LCD LCD UPS UPS UPS UPS 3 ARES UPS 133 EL...
Page 144: ...UPS LED LED Er05 Er39 8 UPS DC UPS Er11 UPS L N AC Er14 UPS 8 ARES UPS 144 EL...