background image

B1 copy starts here

B2 copy starts here

B3 copy starts here

Headline starts here

3

Prior to energization of the SPD, it is critical that the 
following items have been addressed. Do not attempt  
to energize the SPD or continue with the installation  
if all these conditions have not been met, or are unknown.

1.  System configuration and voltage

CAUTION

Prior to installation, ensure the system configuration  
and voltage is equivalent to the SPD unit being installed.

Avant l’installation, assurez-vous que la configuration et 
la tension du système sont équivalentes à celles du SPD 
en cours d’installation. 

The SPD model number can be found on the UL label 
affixed to the SPD enclosure. The SPD selection can be 
verified by comparing the model number to the correct 
electrical system described in the “VOLTAGE RATINGS  
AND POWER SOURCE CONFIGURATIONS” chart.

2.  System grounding and bonding 

Verify that an NEC (National Electrical Code) compliant  
X0 bond has been made at the upstream transformer  
or other separately derived system that feeds the SPD. 
Per NEC Article 250.30, this bond must be in place on  
all 3-Phase WYE, 3-Phase Hi-Leg Delta and Single-Phase 
Split-Systems. Refer to diagram "EXAMPLE OF AN NEC 
COMPLIANT GROUNDING ARRANGEMENT FOR A 
SEPERATELY DERIVED SYSTEM" for an example  
of an installation that complies with these NEC 
recommendations.  
 
Verify that there have not been multiple instances  
of neutral-to-ground bonds on the electrical system.  
These bonds, while either intentional or accidental, 
result in ground currents that can create differential 
voltage potentials between neutral and ground.  
Redundant neutral-to-ground connections can result  
in damage to the SPD and are in violation of the NEC. 

Pre-installation requirements

3.  SPD installation on ungrounded power systems  

Ungrounded power systems are inherently unstable  
and can produce excessively high line-to-ground voltages 
during certain fault conditions. During these fault 
conditions, any electrical equipment, including an SPD,  
may be subjected  to voltages that exceed their designed 
ratings. This information is being provided to the user so 
that an informed decision can be made before installing  
any electrical equipment on an ungrounded power system.

4.  SPD location / primary overcurrent protection 

Per the National Electrical Code (NEC Article 285), Type 2 
SPDs are allowed to be placed on the load side of the main 
service breaker/fuse.

G U I D E TO I N S TA L L AT I O N A N D A SS I S TA N C E , P R E- I N S TA L L AT I O N C H EC K L I S T

Summary of Contents for TPME Series

Page 1: ...umber suffixes of NSBX and NSWM Example TPHE277Y20NSBX Model types are also available with a UL Type 1 rating These models will be labeled with the part number suffix of T1 INSTALLATION OPER ATION AND MAINTENANCE MANUAL TPME and TPHE NSBX and NSWM series Integral SPDs for OEM factory installation ...

Page 2: ...igueur dans le pays lieu où l appareil est utilisé WARNING Do not HIPOT the SPD unit or the electrical system to which the SPD unit is connected without disconnecting the SPD unit s conductors including phases neutral and ground Ne procédez PAS à des ESSAIS DE RIGIDITÉ DIÉLECTRIQUE sur le SPD ou le système électrique auquel il est connecté sans déconnecter les conducteurs des SPD y compris les pha...

Page 3: ... diagram EXAMPLE OF AN NEC COMPLIANT GROUNDING ARRANGEMENT FOR A SEPERATELY DERIVED SYSTEM for an example of an installation that complies with these NEC recommendations Verify that there have not been multiple instances of neutral to ground bonds on the electrical system These bonds while either intentional or accidental result in ground currents that can create differential voltage potentials be...

Page 4: ...se 3 wire ground TPME TPHE120Y TPME TPHE220Y TPME TPHE240Y TPME TPHE277Y TPME TPHE347Y 120 208 V 220 380 V 240 415 V 277 480 V 347 600 V 150 V L N L G 320 V L N L G 320 V L N L G 320 V L N L G 420 V L N L G Three phase WYE 4 wire ground TPME TPHE 240D TPME TPHE 480D 240 V 480 V 270 V L G 550 V L G Three phase Delta 3 wire Three phase WYE 3 wire TPME TPHE 240H 120 240 V 150 V L N L G Phase A C 270 ...

Page 5: ...raîner des blessures graves la mort et ou des dégâts matériels The SPDs described in this manual are intended to arrive at the job site as factory mounted and wired into OEM electrical panels or gear When receiving the SPD on site as OEM factory preinstalled please begin at step number 5 below Installation steps 1 4 shown below appended with OEM are intended to provide guidance to OEMs for factory...

Page 6: ...ts will switch to normal status The contacts will only change back to alarm status if there is a failure within the SPD suppression circuitry or if power has been disconnected from the SPD Allowing the remote alarm contacts remain unconnected will not affect the performance or integrity of the SPD 6 SPD disconnect switch Not provided on NSBX or NSWM models 7 Pre energization check Once all of the ...

Page 7: ...cators will be illuminated green There is one green indicator per each protected phase 2 Alarm status indicator LEDs When illuminated the red alarm status indicator LED will provide notification of an SPD failure condition Verify the alarm status indicator is not illuminated upon startup 3 Remote alarm contacts Remote alarm contacts are available to remotely monitor the health status of the SPD An...

Page 8: ...ust be replaced En cas de condition d alarme du SPD n essayez pas de démonter le SPD pour remplacer les fusibles ou d autres composants Le SPD contient des MOV protégés thermiquement qui ne s ouvrent que lorsque le SPD tombe en panne et ne fonctionne plus L ensemble du SPD doit être remplacé 4 Test enable disable switch cont Test position The test switch provides a quick diagnostic status of the a...

Reviews: