Maintenance

Should a condition occur that results in premature failure of  
the SPD, the integral SPD suppression thermal fusing will safely 
interrupt current flow through the SPD without disrupting power 
to the protected equipment. This will remove the SPD from the 
power system, and the load equipment will remain unprotected 
from subsequent surge activity until the SPD is replaced.

If a change in operational status/alarm indication occurs, a 
qualified (licensed) electrician should inspect the electrical 
system to verify electrical system integrity. If the SPD remains  
in alarm after inspection/corrections have been made, the SPD 
should be replaced.

Servicing/troubleshooting

ABB does not provide a specific schedule for preventative 
maintenance as conditions will vary based on location and  
the environmental factors presented at each installation site. 
However, periodic inspections should be scheduled to verify  
that the SPD does not indicate a failure mode. Inspections  
should also be made to check the integrity of the electrical  
supply connections to the SPD to ensure continued reliable 
performance.

The unit’s heavy-duty construction is designed to provide  
years of uninterrupted service. 

The unit contains no serviceable parts.

L

unité ne contient aucune pièce réparable.

NOTICE

In the event of an SPD alarm condition, do not attempt to  
dis-assemble the SPD to replace fusing or other components.  
The SPD contains thermally protected MOVs that will only open 
when the SPD has failed in a non-serviceable condition. The  
entire SPD must be replaced.

En cas de condition d’alarme du SPD, n’essayez pas de démonter 
le SPD pour remplacer les fusibles ou d’autres composants. Le 
SPD contient des MOV protégés thermiquement qui ne s’ouvrent 
que lorsque le SPD tombe en panne et ne fonctionne plus. 
L’ensemble du SPD doit être remplacé.

4. Test / enable / disable switch (cont.) 

 - Test position — The test switch provides a quick diagnostic 

status of the audible alarm, alarm status indicator and remote 
alarm contacts. When pressed, the audible alarm will sound, 
the alarm lamp will illuminate, and the remote contacts will 
change state. The “test” position is momentary. Once pressed, 
the switch will automatically reset to the enable position  
upon release.

5.  Surge counter LCD 

The surge counter will sense and record transient surge events 
that have been mitigated by the SPD. The counter has been 
designed to detect transients that exceed the peak sine wave 
by more than 70%. If desired, the surge counter display can be 
reset to zero at any time by pressing the reset button located 
on the LCD display.

Operation

20

20

0

13

6

0

1-

7.

20

20

We reserve the right to make technical 
changes or modify the contents of this 
document without prior notice. With regard 
to purchase orders, the agreed particulars 
shall prevail. ABB Inc. does not accept any 
 responsibility whatsoever for potential 
errors or possible lack of information in  
this document.

We reserve all rights in this document  
and in the subject matter and illustrations 
contained therein. Any reproduction or 
utilization of its contents – in whole or in 
parts – is forbidden without prior written 
consent of ABB Inc.  Copyright© 2020 ABB.
All rights reserved.

ABB Inc.
305 Gregson Drive
Cary, NC 27511

electrification.us.abb.com/ 
products/surge-protective-devices

Summary of Contents for TPME Series

Page 1: ...umber suffixes of NSBX and NSWM Example TPHE277Y20NSBX Model types are also available with a UL Type 1 rating These models will be labeled with the part number suffix of T1 INSTALLATION OPER ATION AND MAINTENANCE MANUAL TPME and TPHE NSBX and NSWM series Integral SPDs for OEM factory installation ...

Page 2: ...igueur dans le pays lieu où l appareil est utilisé WARNING Do not HIPOT the SPD unit or the electrical system to which the SPD unit is connected without disconnecting the SPD unit s conductors including phases neutral and ground Ne procédez PAS à des ESSAIS DE RIGIDITÉ DIÉLECTRIQUE sur le SPD ou le système électrique auquel il est connecté sans déconnecter les conducteurs des SPD y compris les pha...

Page 3: ... diagram EXAMPLE OF AN NEC COMPLIANT GROUNDING ARRANGEMENT FOR A SEPERATELY DERIVED SYSTEM for an example of an installation that complies with these NEC recommendations Verify that there have not been multiple instances of neutral to ground bonds on the electrical system These bonds while either intentional or accidental result in ground currents that can create differential voltage potentials be...

Page 4: ...se 3 wire ground TPME TPHE120Y TPME TPHE220Y TPME TPHE240Y TPME TPHE277Y TPME TPHE347Y 120 208 V 220 380 V 240 415 V 277 480 V 347 600 V 150 V L N L G 320 V L N L G 320 V L N L G 320 V L N L G 420 V L N L G Three phase WYE 4 wire ground TPME TPHE 240D TPME TPHE 480D 240 V 480 V 270 V L G 550 V L G Three phase Delta 3 wire Three phase WYE 3 wire TPME TPHE 240H 120 240 V 150 V L N L G Phase A C 270 ...

Page 5: ...raîner des blessures graves la mort et ou des dégâts matériels The SPDs described in this manual are intended to arrive at the job site as factory mounted and wired into OEM electrical panels or gear When receiving the SPD on site as OEM factory preinstalled please begin at step number 5 below Installation steps 1 4 shown below appended with OEM are intended to provide guidance to OEMs for factory...

Page 6: ...ts will switch to normal status The contacts will only change back to alarm status if there is a failure within the SPD suppression circuitry or if power has been disconnected from the SPD Allowing the remote alarm contacts remain unconnected will not affect the performance or integrity of the SPD 6 SPD disconnect switch Not provided on NSBX or NSWM models 7 Pre energization check Once all of the ...

Page 7: ...cators will be illuminated green There is one green indicator per each protected phase 2 Alarm status indicator LEDs When illuminated the red alarm status indicator LED will provide notification of an SPD failure condition Verify the alarm status indicator is not illuminated upon startup 3 Remote alarm contacts Remote alarm contacts are available to remotely monitor the health status of the SPD An...

Page 8: ...ust be replaced En cas de condition d alarme du SPD n essayez pas de démonter le SPD pour remplacer les fusibles ou d autres composants Le SPD contient des MOV protégés thermiquement qui ne s ouvrent que lorsque le SPD tombe en panne et ne fonctionne plus L ensemble du SPD doit être remplacé 4 Test enable disable switch cont Test position The test switch provides a quick diagnostic status of the a...

Reviews: