KNX communication objects
Application "Internal RTC"
Product manual 2CKA001473B5343
│
297
(slave)
Heating/Co
oling
Request fan speed level
manually (slave)
Output 1
bit
[1.001]
Switching
K - - U -
Request fan speed level
(slave)
Output 1
byte
[6.010]
Counting
pulses
(-128 - 127)
K - - U -
Confirm fan speed level
(slave)
Input/
Output
1 byte
[6.010]
Counting
pulses
(-128 - 127)
K - S U A
Name Object
function
Lengt
h
Data type
Flags
K
L
S
U
A
Block Input
1
bit
[1.002]
Boolean
K - S - A
Fan switch
Step output
Input/
Output
1 byte
[5.100}
Fan speed
level
(0 - 255)
K - S U A
Status output steps
Input
1 byte
[5.100}
Fan speed
level
(0 - 255)
K - S - A
Output 1
Input/
Output
1 bit
[1.002]
Boolean
K - S U A
Output 2
Input/
Output
1 bit
[1.002]
Boolean
K - S U A
Output 3
Input/
Output
1 bit
[1.002]
Boolean
K - S U A
Output 4
Input/
Output
1 bit
[1.002]
Boolean
K - S U A
Output 5
Input/
Output
1 bit
[1.002]
Boolean
K - S U A
Output 6
Input/
Output
1 bit
[1.002]
Boolean
K - S U A
Output 7
Input/
Output
1 bit
[1.002]
Boolean
K - S U A
Output 8
Input/
Output
1 bit
[1.002]
Boolean
K - S U A
Block
Input
1 bit
[1.002]
Boolean
K - S - A
Split Unit Control
Control On/Off
Input/
Output
1 bit
[1.001]
Switching
K - S U A
Setpoint temp
Input/
Output
2
bytes
[9.001]
Temperatur
e
(°C)
K - - U -
Actual temperature
Input
2
bytes
[9.001]
Temperatur
e
K - S U A