Commissioning of the KNX function via ABB DCA SmartTouch 10 (from
ETS5)
Product manual 2CKA001473B5343
│
78
Time and date
■
Time format
Options: 12
h
24 h
The parameter is used to specify the time format in which the time is to be displayed.
■
Date format
Options: DD-MM-YY
MM/DD/YY
DD-MM-YY
YY-MM-DD
YY.MM.DD
The parameter is used to specify the date format in which the date is to be displayed.
■
Sending/receiving time and date
Options:
No sending and no receiving
Only sending
Only
receiving
The device has an internal date and time module. The parameter is used to set how the device
uses the date and time.
■
No sending and no receiving
: The device uses date and time only internal.
■
Only sending
: The device synchronizes additional KNX components in the system.
■
Only receiving
: The device receives date and time from a separate KNX timer.
Notice
Normally the panel synchronizes time and date via the NTP server. The device
accepts the received value only when it is not connected to the Internet.
If you select "Only sending" or "Only receiving", the time and date can be synchronized via a
communication object. The synchronization is carried out by sending a group address to or from
the device.
Link the communication objects "Time output" and "Date output" with a corresponding group
address.
■
Automatic summer/winter time changeover
Options: Activated
Deactivated
The parameter is used to specify whether the changeover between summer and winter time is
is to be made.