background image

Videographic Recorder

SM1000

Appendix D – Default Settings

IM/SM1000

Issue 11

123

D.2.8 QSDAIRY

As D.2.5 QSRTD_C except:

Recording

Primary sample rate

1 min

Chart View

Screen interval

2 days/screen

Bargraph View

Bargraph view enable

Off

Archiving

Archive file enables

Alarm event log file

True

Audit log file

True

New file interval

Daily

Recording Channel Setup

Source indentifiers

Channel 1.1

Analog input A1

Channel 1.2

Analog input A2

All other channels

None

Analog Input A1

Engineering range

Low

–10.0

High

90.0

Units

°C

Short tag

Tank

Long tag

Tank Temperature

Broken sensor direction

Upscale

Analog Input A2

Engineering range

Low

–10.0

High

90.0

Units

°C

Short tag

Return

Long tag

Return Temperature

Broken sensor direction

Upscale

•1 Applicable only if the Totalizer option is enabled

Ch1.1 Alarm A

Alarm type

Delayed high process

Trip

10.0 °C

Hysteresis/Delay time

Hysteresis

0.5 °C

Delay time

7200 Secs

Enable source

Digital I/P C1

Log enable

On

Ch1.1 Alarm B

Alarm type

Delayed high process

Trip

12.0 °C

Hysteresis/Delay time

Hysteresis

0.5 °C

Delay time

1200 Secs

Enable source

Digital I/P C2

Log enable

On

Relay modules

Source

Relay C1

Logic equation 1

Relay C2

None

Relay C3

None

Polarity

+ve

Summary of Contents for SM1000

Page 1: ...User Guide IM SM1000 Issue 11 Videographic Recorder SM1000 ...

Page 2: ...ovative design and development to incorporate the latest technology The UKAS Calibration Laboratory No 0255 is just one of the ten flow calibration plants operated by the Company and is indicative of our dedication to quality and accuracy Information in this manual is intended only to assist our customers in the efficient operation of our equipment Use of this manual for any other purpose is speci...

Page 3: ...es 41 3 7 5 Binary Format Data Verification and Integrity 41 3 8 Archiving Online Offline 44 3 9 Backing up Archived Data 44 3 10 Archive Wrap 44 4 Configuration 45 4 1 Introduction 45 4 1 1 Configuration Level Security 45 4 1 2 Configuration Level Access 45 4 2 Overview of Configuration 48 4 2 1 Adjusting Screen Contrast 48 4 3 Making Changes to Parameters 49 4 4 Common Configuration 52 4 4 1 Set...

Page 4: ...duction 106 B 2 Setting Up 106 B 3 Modbus Commands Supported 106 B 4 Modbus Exception Responses 106 B 5 Operating Mode Modbus Coils 106 B 6 Operating Mode Modbus Registers 112 B 7 Comms Analog and Digital Inputs 114 Appendix C Storage Capacity 116 C 1 Internal Storage Capacity 116 C 2 Archive Storage Capacity 117 Appendix D Default Settings 119 D 1 Company Standard 119 D 1 1 Common Configuration 1...

Page 5: ... sources can be displayed in Vertical or Horizontal Chart view format Vertical or Horizontal Bargraph view format Digital Indicator view format Process view format Three instrument logs record alarm events totalizer values if totalizer option is enabled and system configuration changes Screen Capture facility saves an image of any of the operator views to external archive media provided external a...

Page 6: ...alarm transitions and all operator messages Totalizer Log Records all totalizer activity Audit Log Records all system acfivity Alarm Event Log Section 2 7 Totalizer Log Section 2 8 Audit Log Section 2 9 Views provide a window on the stored data Archive Data Recording Channels 1 1 to 1 6 Process Group 1 Recording Channels 2 1 to 2 6 Process Group 2 Instrument Logs Configuration Data Files stored in...

Page 7: ...eviously recorded data View Key Selects a different process view or log Process Group 1 Process Group 2 Instrument Status Logs Chart View see Section 2 3 Bargraph Views see Section 2 4 Digital Indicator View see Section 2 5 Process View see Section 2 6 Also cancels the menu without making a change or returns to the previous menu level Door Lock Media Door Current Date and Time Programming Socket I...

Page 8: ... groups and views that have been enabled are displayed see Section 4 5 page 61 Vertical Bargraph Horizontal Bargraph Digital Indicator Process View Process Group 2 Recording Channels 2 1 to 2 6 Process Group 1 Recording Channels 1 1 to 1 6 Chart View Vertical Bargraph Horizontal Bargraph Digital Indicator Process View ...

Page 9: ...ital On Off Tag Channel Not Used Operator Message appears for 1 second Selects the next enabled view in the group Bar Digital or Process Selects next Process Group if enabled or Status View Opens the Operator Menu for the current view Global Alarm Status Icon see Note 1 on Page 8 Current Value see Note 1 on Page 8 Operator Message Annotation see Note 3 on Page 8 Alarm Event Annotation see Note 3 o...

Page 10: ...ashing border 3 Alarm Event and Operator Message Annotations Alarm Event and Operator Message annotations are not shown on the chart unless enabled see Chart Annotation on page 11 and see Section 4 5 2 page 63 If Alarm event annotation is enabled and an alarm becomes active a red alarm event icon surrounded by a channel colored box is displayed at the point at which the alarm occurred together wit...

Page 11: ...d see Section 4 4 4 page 56 Sign the chart electronically see Section 2 3 1 page 14 Select Historical Review to view previously recorded data stored in the instrument s onboard memory Note Use the and keys to move backwards and forwards through the recorded data Values displayed indicate the process status at the cursor position Cursor Historical Review Active Invalid data e g recording disabled D...

Page 12: ...y buffer during this time is archived on exiting Historical Review mode Select Goto to move to data stored in the instrument s onboard memory that was recorded at a specific date and time Note If daylight saving is enabled see Section 4 4 3 page 54 and the selected Goto target date time is within the daylight saving period Daylight Saving is displayed on the dialog box Once internal memory becomes...

Page 13: ...erated are added at the current time not the time indicated by the cursor If an alarm or operator message is obscuring part of a chart trace use the Chart Annotation option to hide or display alarms and messages on the screen Select the annotation required indicates the annotations selected The possible combinations are No annotation Alarms and Operator Messages both disabled Alarm annotation only...

Page 14: ... appears in the status bar while the instrument retrieves data from storage Selecting a different screen interval does not affect the rate at which data is sampled When in historical review mode changing the screen interval causes the time at the cursor position to change Maximum Screen Interval Sample Rate Setting Vertical Chart View horizontal Chart View 1 second Up to 9 minutes screen Up to 13 ...

Page 15: ...e current process group are identified by a flashing red Alarm Event icon in the bottom left hand corner of the associated channel indicator Active acknowledged alarms are identified by a continuous red Alarm Event icon in the bottom left hand corner of the indicator see Fig 2 3 page 7 To acknowledge all active alarms in the current process group simultaneously select All and press the key Note If...

Page 16: ...n be stored in the instrument s memory If 7 signatures exist and a new one is created the oldest is overwritten Valid Password Entered Create a new signature or Select one of 7 previously defined signatures see Note below Create new signature or edit an existing one Invalid Password Entered see Note in Fig 3 2 page 30 Enter Password see Section 3 3 page 31 Electronic signature is entered into alar...

Page 17: ...e engineering limit Selects the next Process Group if enabled or Status View Selects the next enabled view in the group Digital Indicator Process or Chart Opens the Operator Menu for the current view B Horizontal Bargraph View Alarm Trip Level not shown for slow and fast rate alarms Global Alarm Status Icon Maximum Value solid color Short Channel Tag Minimum Value white fill Alarm Event Icon Insta...

Page 18: ...ar alarm use the and keys to highlight it in the menu and press the key Note Active unacknowledged alarms in the current process group are identified by a flashing red Alarm Event icon in the bottom left hand corner of the associated indicator Active acknowledged alarms are identified by a continuous red Alarm Event icon in the bottom left hand corner of the indicator see Fig 2 5 page 15 To acknow...

Page 19: ...is not running i e Stop is selected the corresponding totalizer value is shown in red Channel Units Totalizer Value Totalizer Units Engineering Units Global Alarm Status Icon Selects the next Process Group if enabled or the Status View Selects the next enabled view in the group Process Chart or Bargraph Opens the Operator Menu for the current view Status Icons Short Channel Tag Current Value Alarm...

Page 20: ...ntry keyboard appears to enable the message to be entered see Fig 4 6 page 50 The selected or user defined message is displayed briefly on screen Hide or display individual channel indicators for the group currently displayed Note The digital indicators displayed are sized equally depending on the number of channels selected This has no effect on the recording of the channel Channels that have not...

Page 21: ...ing red Alarm Event icon in the bottom left hand corner of the associated indicator Active acknowledged alarms are identified by a continuous red Alarm Event icon in the bottom left hand corner of the indicator see Fig 2 6 page 17 To acknowledge all active alarms in the current process group simultaneously select All and press the key Note If an alarm in the other process group is active the Globa...

Page 22: ...ation level Alarm Tag Alarm Trip Level Alarm Acknowledged A Process View Alarms Values since last totalizer reset or totalizer wrap Calculated only while the totalizer is enabled Updated only while the totalizer is running Channel Source Long Tag Average Max Short Channel Tag Alarm Status Instantaneous Value Global Alarm Status Icon Selects the next Process Group if enabled or the Status View Sele...

Page 23: ...the long tag for that channel is displayed Add one of 24 predefined Operator Messages see Section 4 4 7 page 60 or one User Defined Message to the alarm event log If user defined is selected a data entry keyboard appears to enable the message to be entered see Fig 4 6 page 50 The selected or user defined message is displayed briefly on screen Stop and start individual totalizers Channel totalizers...

Page 24: ...the bottom left hand corner of the indicator see Fig 2 6 page 17 To acknowledge all active alarms in the current process group simultaneously select All and press the key Note If an alarm in the other process group is active the Global Alarm status icon continues to be displayed in the status bar If an active alarm in the other process group is unacknowledged the icon is surrounded by a red flashi...

Page 25: ... 6 page 60 the oldest data is overwritten by the newest Entries are renumbered so that the number of the oldest entry is always 00 Newest Data View previous page of data Oldest Data View next page of data Selects Process Group 1 Selects the Totalizer Log Opens the Operator Menu for the current view Alarm becomes active Active transition Alarm Acknowledged Alarm becomes inactive Inactive transition...

Page 26: ... Transitions Only displays entries for alarms when made active and hides all acknowledged inactive transitions The Alarm Event log is not group specific To acknowledge a particular alarm use the and keys to first select the relevant process group followed by the alarm to be acknowledged To acknowledge all active alarms in the selected process group simultaneously select All and press the key Note ...

Page 27: ... is always 00 The logging of totalizer values can be triggered at pre determined intervals and or by digital signal see Log update on page 85 Fig 2 9 Totalizer Log Note Maximum Minimum and Average statistics are not shown unless enabled in the Filter menu see overleaf View next page of data Newest Data View previous page of data Oldest Data Selects Process Group 1 Selects the Audit Log Opens the O...

Page 28: ...layed in the log Indicates entries currently displayed This does not affect which events are recorded in the log Statistics displays the maximum minimum and average values of the analog value being totalized together with the dates and times at which all maximum and minimum values occurred These values are reset when the totalizer is reset and are updated only when the totalizer is running ...

Page 29: ...overwritten by the newest Entries are renumbered so that the number of the oldest entry is always 00 Fig 2 10 Audit Log Select the Configuration Level see Section 4 page 45 Select the Setup Level see Section 3 page 29 Newest Data View previous page of data Oldest Data View next page of data Audit Log Icon Selects Process Group 1 Selects the Status View Opens the Operator Menu for the current log F...

Page 30: ...s e g 10 hours 1 Hour Minutes e g 25 minutes Selects Process Group 1 Selects the Alarm Event Log Opens the Operator Menu for the current view Instrument Software Version Operating System Version Cold junction temperatures for Modules A B measured by the built in cold junction circuitry Not Used is displayed if none of the inputs on the module are thermocouples Amount of memory used on the archive ...

Page 31: ...rs Refer to Fig 3 2 to access the Setup Level If Security System is set to Advanced and Setup Level Security is set to On access to the Setup Level is protected by a unique password for each authorized user Refer to Fig 3 3 to access the Setup Level Note Users with Setup access can Start Stop recording Switch between primary and secondary recording rates Set archiving on line and off line View int...

Page 32: ...sage is displayed If this occurs access privileges can be reinstated only by the system administrator User 1 If the system administrator s access privileges have been removed the security system must be disabled using the configuration security switch Yellow switch to gain access to the configuration see Section 4 1 2 page 45 Invalid Password Entered see Note Below Valid Password Entered Setup Sec...

Page 33: ...d keys and press to display the character entry box 2 Enter the old password using the and keys Highlight the OK button and press 3 Enter the new password using the same procedure as for the old password 4 Enter the new password again to confirm it 5 Highlight the OK button and press Password change successful Note If the key is pressed at any stage or OK is selected before the new password is con...

Page 34: ...terval in the Chart view When the channels are set to Stop the instantaneous values in the associated indicators are displayed in red and after the end of the next sample period no further samples are plotted on the associated traces Digital recording channels can only be set to Stop or Go Recording control can also be implemented using digital sources see Sections 4 5 1 page 61 and 4 6 1 page 72 ...

Page 35: ...ay Binary format of data in internal memory the Select data to be archived dialog box previous page is displayed Select data to be archived and press Once selected all data within the selected time frame is archived Older unarchived data remains in the internal memory buffer until overwritten by newer data but is not available for archiving unless Reset archiving is selected Places the archive med...

Page 36: ... Icons Note Do not remove media while either of the media update in progress status icons or are displayed Amount of memory used on the external archive media currently installed Approximate time left before the current external archive media is full assuming the amount of data recorded remains the same Time Left Display Format 1 Day Days e g 5 Days 1 Hour 1 Day Hours e g 10 hours 1 Hour Minutes e...

Page 37: ...door with the key supplied and press the release catch to open the door Withdraw the media 1 2 3 4 4 Compact Flash Media SmartMedia Set the archive media off line see Section 3 4 page 33 Note When inserting the media into the instrument Ensure the media is the correct type for the instrument If SmartMedia option is fitted ensure only 3 3V SmartMedia cards used Do not use excessive force ...

Page 38: ...istorical entries from the audit log Note The content of this file is the same for all groups Digital signature files S Digital signature file for the corresponding channel data file Batch data files V Analog or digital recording channels in the current process group when the batch function is active Batch log files X Historical record of the batches recorded Table 3 1 Text Format File Types and E...

Page 39: ...y file is started at 00 00 00 on 30th March 2003 filename 30Mar03ProcessGroup1 D00 Summertime starts at 2 00am on 30th March 2003 The clock changes automatically to 3 00am The existing file is closed and a new file is created filename 30Mar03ProcessGroup1 DS D00 The file 30Mar03ProcessGroup1 D00 contains data generated from 00 00 00 to 01 59 59 before summertime starts The file 30Mar03ProcessGroup...

Page 40: ...d into individual files The filenames are formatted as shown in Table 3 4 with the date and the time indicating the first entry in the file If one of the archive log files becomes full 64000 entries a new file is created with an extension incremented by 1 e g a01 e01 etc New text format log data files are also created when the daylight saving period starts or ends Files containing log data generat...

Page 41: ...pany s DataManager data analysis software package 3 6 5 Text Format Data File Digital Signatures Fig 3 5 A digital signature file is created for each channel data file using the same filename but with a S extension The file contains a unique fingerprint of the contents of the data file that can be used to prove if the data has been tampered with or corrupted Data validation can be carried out on a...

Page 42: ...Videographic Recorder SM1000 3 Setup 40 IM SM1000 Issue 11 Fig 3 6 Alarm Event Log Sample Text Format Fig 3 7 Totalizer Log Sample Text Format Fig 3 8 Audit Log Sample Text Format ...

Page 43: ...s When an existing valid binary log file does not exist on the media card When the maximum size 64000 entries is exceeded When the daylight saving period starts or ends Files containing log data generated during the daylight saving period summertime have DS appended to the filename 3 7 4 Binary Format Data File Examples Figs 3 9 to 3 12 Binary format archived data is stored in a secure binary enco...

Page 44: ...Videographic Recorder SM1000 3 Setup 42 IM SM1000 Issue 11 Fig 3 9 Channel Data File Sample Binary Format Fig 3 10 Alarm Event Log Sample Binary Format ...

Page 45: ...Videographic Recorder SM1000 3 Setup IM SM1000 Issue 11 43 Fig 3 11 Totalizer Log Sample Binary Format Fig 3 12 Audit Log Sample Binary Format ...

Page 46: ...grade and either of the Warning Too Many Files icons or are displayed Change the media as soon as possible When external archive media contains approximately 300 files its read write performance becomes too slow Archiving is stopped automatically and the Too Many Files Archiving Stopped icons alternating with are displayed Change the media immediately to prevent loss of data 3 9 Backing up Archive...

Page 47: ...rity Up to 12 users Each user is assigned a unique password of up to 20 characters Each user is assigned configuration setup and or electronic signature access privileges Each user is assigned one of 3 levels of configuration level access privileges Configurable password expiry times password failure limits and minimum password length Inactive user disabling 4 1 2 Configuration Level Access Figs 4...

Page 48: ...onfigured when a configuration is opened from file or when a new configuration is loaded Check Load security configuration from file to overwrite the current security configuration with data from the file to be loaded see Note 2 below Valid Password Entered Invalid Password Entered Press to accept the selection Press to toggle between internal and external storage Press to cancel Use and to highli...

Page 49: ...etting the Security Switch Note The red switch is for factory use only Ensure it remains in the position closest to the rear of the instrument Withdraw the instrument from the case Remove tamper evident seal if fitted Switch off the power to the instrument and unscrew the jacking screw securing the instrument to the case Set the yellow Security switch to the Configuration Level Not Protected posit...

Page 50: ... Configuration menu See Note below 1 Select the required parameter using the and keys Press the key to edit selected parameter Use the and keys to select the next required tab 4 2 3 When all configuration changes are complete select Exit to save or cancel changes Press the key to display the menu Select the next item required and activate using the key 5 6 Adjust the contrast to the required level...

Page 51: ... displayed automatically see Fig 4 6 Use the key to open the Configuration menu in order to select a different channel see Fig 4 11 page 72 Parameter Value Sub menu Edit Button Configuration Tab Selection List Higher level windows remain visible to identify location within the configuration structure Parameter Use the and keys to highlight a selection Press the key to accept the selection ...

Page 52: ...letters or fewer characters Cursor Parameter Limits Highlight text box and use and keys to position cursor to edit text as required Spacebar Note Values outside the preset parameter limits or with too many decimal places are highlighted when the OK button is selected Use and keys to highlight an item and press to select it Note Items not selected are indicated by an X in the parameter value window...

Page 53: ...le memory only when one of the save options above has been selected Any powerdown before this results in lost configuration changes Selecting Cancel discards unsaved changes and returns the instrument to the Operating level New internal data files for enabled recording channels are created if any of the following configuration parameters are changed Recording channel source Primary secondary sampl...

Page 54: ...mpts and menu items Select a signal source used to acknowledge all active alarms in both Process Groups simultaneously Refer to Appendix A page 104 for a description of the available sources Note This signal is edge triggered A rising edge inactive to active or falling edge active to inactive triggers global alarm acknowledgement Enter the tag to be used to identify the instrument on configuration...

Page 55: ...ave an image of any Operator screen to external archive media by pressing the key when an Operator Menu is not open Note All images are saved to a folder on the archive media named BMP The images are saved even if archiving is set to Offline If external archive media is not inserted or is full the screen capture facility is disabled automatically Adjust screen contrast refer to Section 4 2 1 page ...

Page 56: ...upon exiting Configuration Mode see Fig 4 7 page 51 does not reset the clock to its previous setting Select Cancel in the dialog box above to exit date and time setup without saving changes Setting an earlier date or time results in the loss of all data currently in the internal buffer memory past that date Data archived to external media is unaffected If an earlier time must be set change the Ins...

Page 57: ...he start and end of the daylight saving period in Central Europe is calculated automatically The clock is incremented automatically by 1 hour at 2 00am on the last Sunday in March and decremented automatically by 1 hour at 2 00am on the last Sunday in October Auto Custom The start and end of the daylight saving period can be configured manually for regions that do not follow either the USA or Euro...

Page 58: ...tion level for all users is prohibited once the changes have been saved and made active Access to the Configuration level is then achieved only by setting the internal security switch to the Configuration Level Not Protected position see Fig 4 2 page 47 Configuration level security is accessed and modified only by the System Administrator User 1 When set to On access to the Setup level is password...

Page 59: ...period after which all passwords expire After this period of time all users must change their passwords Enter the time period after which an inactive user s access privileges are de activated A user is considered inactive if their password has not been used A user is de activated by removal of their access privileges and can be re activated only by the System Administrator User 1 Enter the number ...

Page 60: ...and associated password s to be used to access the Configuration level when Configuration security is set to Password protected see below Enter a name for the selected user Enter an initial password for the selected user Set access privileges for the selected user Enabled The selected user is able to access the Configuration level No access The selected user is unable to access to the Configuratio...

Page 61: ... signature Setup The selected user is able to access the Setup level Configuration No access Disabled The selected user is unable to access the Configuration and Setup levels or enter electronic signatures Config Load The selected user is unable to make any configuration changes but can load configurations from external media Configuration Ltd The selected user is able to Change alarm trip points ...

Page 62: ...The Totalizer log is displayed only if the Totalizer option is enabled The size of the Audit log can be changed only by the System Administrator User 1 Log sizes must be set in the range 10 to 200 The size of the logs has no effect on the amount of memory available for storing channel data Operator messages can be triggered via the Operator Menus or a digital signal Message Tag Enter the message t...

Page 63: ...the process group tag maximum 20 characters that appears in the title bar when any operator views from that group are displayed Note Each process group tag must be unique Select a signal source to enable disable recording of all channels in the current Process Group Refer to Appendix A page 104 for a description of the available sources Note This signal is edge triggered A rising edge inactive to ...

Page 64: ...full details of internal memory and external archive media storage capacity Sample Rate Equivalent Chart Speed On board Storage Time 6 Channels 1 second 720mm h 22 7 hours 3 seconds 240mm h 2 8 days 6 seconds 120mm h 5 7 days 12 seconds 60mm h 11 5 days 36 seconds 20mm h 1 1 months 72 seconds 10mm h 2 3 months Note Sample rates are set using one of the following combinations of units Minutes or mi...

Page 65: ...11 63 4 5 2 Configuring the Chart View Screen Interval Scale Bar Alarm Event Annotation Operator Message Annotation Screen Interval Time Stamp Chart Trace Chart Divisions Horizontal Chart Horizontal Chart Vertical Chart Major Chart Divisions Minor Chart Divisions ...

Page 66: ...re displayed on the chart adjacent to the point at which the alarm occurred see Section 2 3 page 7 This initial setting can be changed by the operator if Chart annotation select enable is enabled in the Chart view menu enables see Menu Enables on page 65 Select the number of major and minor chart divisions to be displayed on the chart and its scale bar Select the number of major vertical divisions...

Page 67: ...fined message Alarm acknowledge enable Enables the Operator to acknowledge any alarms associated with the current group Scale select enable Enables the operator to display the scale for one enabled channel or all channels in turn on the scale bar at the top of the screen Trace select enable Enables individual chart traces to be displayed or hidden Screen interval select enable Enables the Operator...

Page 68: ...ined message Alarm acknowledge enable Enables the Operator to acknowledge any alarms associated with the current group Max min reset enable Enables the operator to reset the maximum and minimum values of one or more channels to the current value Note Menu items that are not enabled are greyed out in the Bargraph menu Alarm Trip Level not shown for slow and fast rate alarms Analog Channels Digital ...

Page 69: ... Operator to acknowledge any alarms associated with the current group Totalizer reset enable Enables the Operator to reset the totalizers on any or all channels Totalizer stop go enable Enables the Operator to stop and start totalizers on any or all channels View select enable Enables the Operator to select the Alarms and Statistics views Note Menu items that are not enabled are greyed out in the ...

Page 70: ...ng the Digital Indicator View Note Displayed only if the Totalizer option is enabled and is enabled for that channel see Section 4 6 5 page 84 and for display see next page Channel Units Totalizer Value Totalizer Units Short Channel Tag Current Value Alarm Status Units See Note below ...

Page 71: ...able Enables the Operator to activate one of 24 pre configured messages or a user defined message Alarm acknowledge enable Enables the Operator to acknowledge any alarms associated with the current group Totalizer reset enable Enables the Operator to reset the totalizer value to the preset totalizer value on any or all channels Totalizer stop go enable Enables the Operator to start and stop the to...

Page 72: ...ifferent formats Select the data types that are to be archived to the storage media Channel Data Alarm Event log Totalizer log Audit log Note The totalizer log file can be enabled only if the totalizer option is enabled File Type Contents Extension Channel data files Analog or digital recording channel signals in the current process group D00 Text or B00 Binary Alarm event log files The historical...

Page 73: ...ing to the date format set in Common Configuration see Section 4 4 3 page 54 When set to On archive wrap deletes the oldest archived data file from external archive media automatically when the media approaches its maximum capacity When set to Off archiving stops automatically when external archive media is full No files are deleted Oldest Un archived Data Archive Triggers 1 Day Old Binary or 1 Ho...

Page 74: ...ource to None does not switch off the analog input to which the channel was assigned previously i e the analog input continues to be monitored To switch off an analog input set Analog I P Type for the required channel to Off see Section 4 6 2 page 74 1 If this parameter is changed from any previous setting other than None a new internal data file for this recording channel is created All historica...

Page 75: ...tantaneous A single value based on process conditions at the time of sampling Average The average value of the analog signal since the previous sample Minimum The minimum value of the analog signal since the previous sample Maximum The maximum value of the analog signal since the previous sample Max min Two values are recorded to capture the maximum minimum signal values since the previous sample ...

Page 76: ... digital input is selected the input channel becomes a digital input channel see Section 4 6 3 page 77 Select Off to disable an analog input Warning Ensure that the appropriate electrical connections have been made see Section 5 4 page 100 When Type is set to Volts input signals with voltages greater than 2V standard inputs or 1V high specification inputs must be connected through an external volt...

Page 77: ...D is selected Set the required electrical range Note Applicable only to mA mV V and Resistance input types When an input is connected through an external voltage divider see Warnings on page 74 set the electrical range low and high values to the actual voltage applied to the divider not the voltage after it has been divided down The range of the electrical input signal is determined by the input t...

Page 78: ...m Linearizer 2 Linear Table 4 3 Limits of Engineering Ranges Example for an electrical input range of 4 0 to 20 0mA representing a pressure range of 50 to 250 bar set the Low value to 50 0 and the High value to 250 0 Enter the tag name to be displayed on channel indicators and used to identify the channel in archive files 8 characters max Note Tags with a high percentage of capital letters and wid...

Page 79: ... displayed only if Input type on the Analog I P tab is set to Volt free digital input If this parameter is changed to anything other than Volt free digital input the input channel reverts to an analog input channel see Section 4 6 2 page 74 Enter the tag to be displayed on channel indicators when the digital signal is active 6 characters max Note Tags with a high percentage of capital letters and ...

Page 80: ...p Point Alarm On Alarm Off Alarm On Alarm Off High Process Low Process Hysteresis Hysteresis Process Variable Trip Point Alarm On Alarm Off Alarm Latched Alarm acknowledged by operator Hysteresis Process Variable Trip Point Alarm On Alarm Off Alarm Latched Alarm acknowledged by operator Hysteresis Process Variable High Latch Alarm Action Low Latch Alarm Action ...

Page 81: ...r Deviation exceeded fast rate alarm becomes active slow rate alarm becomes inactive new period starts Deviation below limit at end of time period fast rate alarm becomes inactive slow rate alarm becomes active Deviation below limit at end of time period alarm becomes inactive Alarm On Alarm Off Fast Rate Alarm Period Deviation Deviation Deviation exceeded fast rate alarm becomes active slow rate ...

Page 82: ...goes below trip hysteresis point therefore alarm is de activated Alarm Enable signal is switched On Alarm delay timer is started Process variable goes above trip point but alarm is not activated because alarm delay time has not expired Alarm delay timer expires alarm is now enabled Alarm is activated because process variable is above trip point Process variable goes above trip point alarm is activ...

Page 83: ...Alarm Event views 20 characters max Note Process and Latch alarms only see Figs 4 12 and 4 13 Set the value in engineering units at which the alarm is to activate Set the hysteresis value in engineering units and the time hysteresis in seconds When an alarm trip value is exceeded the alarm does not become active until the time hysteresis value has expired If the signal goes out of the alarm condit...

Page 84: ...for at least one complete Alarm Period Set the minimum or maximum amount of deviation allowed within the Rate Alarm Period before the alarm is activated Set the time period over which the deviation is measured For High Rate alarms the alarm becomes active if the value changes by more than the deviation value within the alarm period For Low Rate alarms the alarm becomes active if the channel value ...

Page 85: ...o None the alarm is always enabled Note For Delayed Process alarm operation see Fig 4 16 page 80 Set to On to record all changes in the alarm state in the Alarm event log see Section 2 7 page 23 Assign the alarm to one or more of 12 groups The alarm states assigned to each group are ORed together to create an internal digital signal that may be assigned to relays digital outputs or internal digita...

Page 86: ...en the Predetermined count value is reached Note A wrap pulse with a duration of 2s occurs if the total reaches the Predetermined count value and Wrap enable is set to On If Wrap enable is set to Off the wrap pulse becomes active when the Predetermined count value is reached and remains active until the totalizer is reset The pulse can be assigned to a relay digital output or digital counter Enter...

Page 87: ... an alarm threshold to indicate when the Predetermined count value is about to be reached Select a Reset source signal see Appendix A page 104 an edge triggered signal to reset the totalizer on a rising edge Select the frequency with which totalizer values are added to the Totalizer log Select a Log update source signal see Appendix A page 104 an edge triggered signal to trigger the addition of th...

Page 88: ...ngineering units at which the totalizer is to stop counting OR Digital Input Sources only see Section 4 6 1 page 72 Set the required totalizer count rate A digital totalizer pulse can be scaled to represent a value of between 0 00001 and 1000 00000 The totalizer is then incremented by this amount each time there is an off on transition Example a count of 5 digital pulses with Count rate set to 100...

Page 89: ...t to be modified Press the key to open the digipad to change the position of that point Press the key to return to the Functions screen Each linearizer has 20 breakpoints Both X and Y values are set as percentages Custom linearizers can be applied to any analog input by selecting them as the linearizer type for that input see Section 4 6 2 page 74 Note X is input to the linearizer expressed as a p...

Page 90: ...the real time alarm on the first day of each month Set the time at which the alarm becomes active If Every hour is set to On the Hours setting cannot be adjusted and the alarm is activated at the same time every hour determined by the Minutes setting or on the hour if Minutes is set to Off Set the duration for the alarm to remain active Set to On to add an entry to the Alarm event log each time th...

Page 91: ...ording in configuration check box is not ticked on entry to the Configuration level see Fig 4 1 page 46 Changes to the Analog Input Type see Section 4 6 2 page 74 must be saved to the current configuration before commencing input adjustment Actual value Desired value 1 Adjust the process or simulated input signal to a known value below 50 of the engineering range 2 If Actual value in engineering u...

Page 92: ...0 For 2 lead resistance thermometers either connect the resistance box at the sensor end of the leads or add the lead resistance to the calibration values Without Adjustment Span Adjust 1 Offset Adjust 0 Engineering Low Engineering High Unadjusted Value Engineering Low Engineering High Adjusted Value With Adjustment typical example Adjusted Value Engineering Low Engineering High Engineering Low En...

Page 93: ...ocol is set to Modbus Set a unique Modbus Address that allows the host system to identify the instrument on a Modbus link Note Maximum 31 slaves per loop Note Displayed only if Protocol is set to Modbus Master Set the poll rate in milliseconds min 0 max 3600000 Note Displayed only if Protocol is set to Modbus Master Set the number of successive polls permitted to fail before the data is marked as ...

Page 94: ...s not set to None Select the register type Holding Register or Input Register Note Displayed only if RTU Address is not set to None Select the format of the data to be read from the slave device Sint16 signed 16 bit integer Sint32 signed 32 bit integer transmitted in high low order rev Sint32 signed 32 bit integer transmitted in low high order IEEE 32 bit floating point number transmitted in high ...

Page 95: ... page 91 Select the comms digital input to hold the data from the nominated slave device Enter the RTU address assigned to the remote unit 1 to 247 Note Displayed only if RTU Address is not set to None Enter the register number to be read or written to in the slave device Note Displayed only if RTU Address is not set to None Select the register type Input Status or Coil Status ...

Page 96: ...to 32 Binary Encoded BCD digital states e g BCD digital I P H0 to BCD digital I P H31 BCD digital inputs can be used as digital sources in the same way as standard digital inputs Inputs H1 H2 H3 H4 and H5 have weightings of 1 2 4 8 and 16 respectively A rising edge on input H6 is used as the update trigger Following an inactive to active transition on input H6 inputs H1 to H5 are evaluated the wei...

Page 97: ...B page 106 for further information on using the Modbus link Select the analog output source Note The analog output source can be any internal or external analog signal Set the required analog output engineering and electrical ranges Note The Engineering low and Engineering high settings are the engineering values corresponding to the Electrical low and Electrical high values below The Electrical l...

Page 98: ...the Directive on Waste Electrical and Electronic Equipment WEEE It must not be disposed of in Municipal Waste Collection Cleaning Clean only the front panel using warm water and a mild detergent Fig 5 1 General Requirements A Close to Sensors B At Eye level Location C Avoid Vibration Sensors Keep distance to a minimum Fig 5 2 Environmental Limits A Within Temperature Limits B Within Humidity Limit...

Page 99: ...0 0 138 5 43 1 0 0 0 0 04 0 0 Dimensions in mm in 34 1 34 3 0 12 29 1 14 7 0 0 27 155 0 6 1 40 1 57 Gasket Gasket AC Power Supply Earth Ground Stud Cut a hole in the panel see Fig 5 3 Insert the instrument Fit the panel clamps Tighten the panel clamp securely by hand See Note 1 2 3 4 AC Power Supply Earth Ground Stud Note This is critical in order to ensure proper compression of the panel seal and...

Page 100: ...ument conforms to Mains Power Input Insulation Category III All other inputs and outputs conform to Category II All connections to secondary circuits must have basic insulation After installation there must be no access to live parts e g terminals Terminals for external circuits are for use only with equipment with no accessible live parts If the instrument is used in a manner not specified by the...

Page 101: ...9 20 NC NO C NC NO C NC NO C NC NO C NC NO C NC NO C Transmit LED Continuity receive LED RJ45 Connector Position C Ethernet 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 24V 45mA 24V 45mA Positions B C and D 24V Tx PSUs Section 5 4 4 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 di1 di2 di3 di4 di5 di6 do1 do2 do3 do4 do5 do6 COM COM COM COM a01 a02 Positions B C and D Hybrid Board Secti...

Page 102: ...ed for current ranges To avoid damage to multi channel instruments high common mode voltages up to 500V r m s max must be present on all channels or not at all For the standard input card the maximum channel to channel voltage between any two channels must not exceed 35V or permanent damage to the instrument s input circuitry may occur For applications requiring higher levels of isolation refer to...

Page 103: ...arate foil screens and integral drain wires Note To prevent false triggering of slaves when the master host computer is inactive pull up and pull down resistors must be fitted to the RS422 485 interface in the host computer Resistors are normally connected to the interface by means of hard wired links or switches refer to the manufacturer s instructions For long transmission lines a 120Ω terminati...

Page 104: ... Yellow Blue Black White Red Black Red Blue Blue Black White Black Case Blue for intrinsically safe circuits Fe Con DIN 43710 DIN 43710 Blue Red Blue Blue Table 5 1 Thermocouple Compensating Cable Fig 5 9 AC Power Supply Warning Use fuse rating 315mA max type T Fig 5 10 DC Power Supply Warning Use fuse rating 3A max type T Terminal Block E L N 85 min to 265V max 50 60Hz 1 2 3 4 5 6 7 8 Line Neutra...

Page 105: ...tput Connections Fig 5 14 Two analog outputs are provided on the Hybrid option board Fig 5 12 Digital Output Connections Note Voltage level 5V Load 450Ω min 15kΩ max Digital Output Common Load 9 10 11 12 13 14 15 16 do1 do2 do3 do4 do5 do6 COM COM Fig 5 13 Digital Input Connections Fig 5 14 Analog Output Connections di1 di2 di3 di4 di5 di6 COM COM Terminal Blocks C or D Input State Dxx active Swit...

Page 106: ...hen the signal detected at the analog input is outside the Fault Detect Level specified in Section 4 6 2 Comms AIN 1 fail to Comms AIN 24 fail Stats 1 1 fail to Stats 2 6 fail Totalizer Input Value Failure Activated when the totalizer fails cleared when the totalizer wraps or is reset Available only for analog channels if the relevant totalizer is enabled in the Configuration level Archive media n...

Page 107: ... 1 to Real time alarm 4 Real Time Alarm States Available only if the relevant alarm is enabled in the Configuration level Run state 1 1 to Run state 2 6 Totalizer Run States Active while totalizer is running Available only if the relevant totalizer is enabled in the Configuration level Wrap pulse 1 1 to Wrap pulse 2 6 Totalizer Wrap Pulse Available only if the relevant totalizer is enabled in the ...

Page 108: ... instrument returns an exception response if the register is not currently writable 06 Preset Single Register sets the value of a single register analog value at the specified address The instrument returns an exception response if the register is not currently writable Limits defined in configuration are applied to the value before storage 08 Loopback Diagnostic Test used to test the integrity of...

Page 109: ...068 0118 19 Alarm 2 4A 0069 0119 20 Alarm 2 4B 0070 0120 21 Alarm 2 5A 0071 0121 22 Alarm 2 5B 0072 0122 23 Alarm 2 6A 0073 0123 24 Alarm 2 6B 0074 0124 Reserved 0075 to 0100 0125 to 0150 Table B 3 Alarm States Coil Number Title Read Always returns 0 Write 1 Activate Operator Message 1 0151 Operator Message 2 0152 Operator Message 3 0153 Operator Message 4 0154 Operator Message 5 0155 Operator Mes...

Page 110: ...sage 0183 Always reads as 0 0 1 No effect Activate Table B 5 Remote Operator Messages Modbus Coil Numbers Read Only 0 Output or Input Inactive 1 Output or Input Active Channel Digital Inputs Digital Outputs Relay Outputs Not Used 0201 to 0212 0251 to 0262 0301 to 0312 C1 0213 0263 0313 C2 0214 0264 0314 C3 0215 0265 0315 C4 0216 0266 0316 C5 0217 0267 0317 C6 0218 0268 0318 D1 0219 0269 0319 D2 02...

Page 111: ...2 0452 0502 0552 3 Totalizer 1 3 0353 0403 0453 0503 0553 4 Totalizer 1 4 0354 0404 0454 0504 0554 5 Totalizer 1 5 0355 0405 0455 0505 0555 6 Totalizer 1 6 0356 0406 0456 0506 0556 7 Totalizer 2 1 0357 0407 0457 0507 0557 8 Totalizer 2 2 0358 0408 0458 0508 0558 9 Totalizer 2 3 0359 0409 0459 0509 0559 10 Totalizer 2 4 0360 0410 0460 0510 0560 11 Totalizer 2 5 0361 0411 0461 0511 0561 12 Totalizer...

Page 112: ... Alarm 0750 Table B 8 Any Alarm Read Only 0 Alarm group inactive 1 Alarm group active Title Coil Number Alarm Group 1 0751 Alarm Group 2 0752 Alarm Group 3 0753 Alarm Group 4 0754 Alarm Group 5 0755 Alarm Group 6 0756 Alarm Group 7 0757 Alarm Group 8 0758 Alarm Group 9 0759 Alarm Group 10 0760 Alarm Group 11 0761 Alarm Group 12 0762 Table B 9 Alarm Groups ...

Page 113: ... Real time alarm active Title Coil Number Real Time Alarm 1 0851 Real Time Alarm 2 0852 Real Time Alarm 3 0853 Real Time Alarm 4 0854 Table B 11 Real Time Alarms Channel Number Process Group 1 Process Group 2 Signal 1 1 1 2 1 3 1 4 1 5 1 6 2 1 2 2 2 3 2 4 2 5 2 6 Channel Fail State R 1001 1021 1041 1061 1081 1101 1121 1141 1161 1181 1201 1221 Alarm A State R 1002 1022 1042 1062 1082 1102 1122 1142...

Page 114: ...t number 999 to 9999 A1 0001 and 0002 A2 0003 and 0004 A3 0005 and 0006 A4 0007 and 0008 A5 0009 and 0010 A6 0011 and 0012 B1 0013 and 0014 B2 0015 and 0016 B3 0017 and 0018 B4 0019 and 0020 B5 0021 and 0022 B6 0023 and 0024 Reserved 0025 to 0100 Table B 13 Analog Inputs Trip Point Registers single precision floating point Read 999 to 9999 Alarm Number and Name Write 999 to 9999 1 Alarm 1 1A 0101 ...

Page 115: ...to 0716 5 Totalizer 1 5 0259 and 0260 0309 and 0310 0359 and 0360 0417 to 0420 0559 and 0560 0609 and 0610 0659 and 0660 0717 to 0720 6 Totalizer 1 6 0261 and 0262 0311 and 0312 0361 and 0362 0421 to 0424 0561 and 0562 0611 and 0612 0661 and 0662 0721 to 0724 7 Totalizer 2 1 0263 and 0264 0313 and 0314 0363 and 0364 0425 to 0428 0563 and 0564 0613 and 0614 0663 and 0664 0725 to 0728 8 Totalizer 2 ...

Page 116: ... 6 0606 0656 0861 and 0862 19 0619 0669 0887 and 0888 7 0607 0657 0863 and 0864 20 0620 0670 0889 and 0880 8 0608 0658 0865 and 0866 21 0621 0671 0891 and 0892 9 0609 0659 0867 and 0868 22 0622 0672 0893 and 0894 10 0610 0660 0869 and 0870 23 0623 0673 0895 and 0896 11 0611 0661 0871 and 0872 24 0624 0674 0897 and 0898 12 0612 0662 0873 and 0874 Reserved 0625 to 0650 0675 to 0700 0899 to 1000 13 0...

Page 117: ...74 116 t 28 40 3C 60 4F 79 O 62 98 b 75 117 u 29 41 3D 61 50 80 P 63 99 c 76 118 v 2A 42 3E 62 51 81 Q 64 100 d 77 119 w 2B 43 3F 63 52 82 R 65 101 e 78 120 x 2C 44 N A 40 64 53 83 S 66 102 f 79 121 y 2D 45 41 65 A 54 84 T 67 103 g 7A 122 z 2E 46 42 66 B 55 85 U 68 104 h 7B 123 2F 47 43 67 C 56 86 V 69 105 i 7C 124 30 48 0 44 68 D 57 87 W 6A 106 j 7D 125 31 49 1 45 69 E 58 88 X 6B 107 k 7E 126 32 ...

Page 118: ... 9 seconds 1 7 days 20 5 hours 13 6 hours 10 2 hours 1 0 second 1 9 days 22 7 hours 15 2 hours 11 4 hours 2 0 seconds 3 8 days 1 9 days 1 3 days 22 7 hours 3 0 seconds 5 7 days 2 8 days 1 9 days 1 4 days 4 0 seconds 7 6 days 3 8 days 2 5 days 1 9 days 5 0 seconds 9 5 days 4 7 days 3 2 days 2 4 days 6 0 seconds 11 4 days 5 7 days 3 8 days 2 8 days 7 0 seconds 13 3 days 6 6 days 4 4 days 3 3 days 8 ...

Page 119: ...econds 3 1 weeks 1 4 months 2 9 months 5 6 months 0 9 seconds 3 4 weeks 1 6 months 3 2 months 6 3 months 1 0 second 1 0 month 2 0 months 3 6 months 7 0 months 2 0 seconds 2 0 months 3 5 months 7 0 months 14 0 months 3 0 seconds 3 0 months 5 0 months 10 0 months 20 0 months 4 0 seconds 3 5 months 7 0 months 14 0 months 28 0 months 5 0 seconds 4 5 months 9 0 months 18 0 months 35 0 months 6 0 second...

Page 120: ...nds 3 6 months 7 0 months 1 2 years 2 3 years 1 0 second 4 0 months 8 0 months 16 2 months 2 6 years 2 0 seconds 8 0 months 1 3 years 2 7 years 5 2 years 3 0 seconds 12 0 months 2 0 years 4 0 years 7 8 years 4 0 seconds 16 0 months 2 7 years 5 3 years 10 4 years 5 0 seconds 20 0 months 3 3 years 6 7 years 13 0 years 6 0 seconds 2 0 years 4 0 years 8 0 years 15 6 years 7 0 seconds 2 3 years 4 7 yea...

Page 121: ...up 1 Group 2 tag Process Group 2 Recording enable source None Primary sample rate 10 0 sec Secondary sample rate 1 0 sec Sample rate select source None Chart View Chart view enable Vertical Chart annotation None Major chart divisions 5 Minor chart divisions 2 Trace pointers Enabled Screen interval 3 minutes screen Trace width 1 Menu enables Message select False Alarm acknowledge True Scale select ...

Page 122: ...annels Digital on tag On Digital off tag Off Short tag Blank Long tag Blank Process Alarms all channels Alarm type Off Recording channel x x alarm tag Alarm A tag x xA Alarm B tag x xB Trip 0 0 Hysteresis Hysteresis 0 0 Time hysteresis 0 Secs Enable source None Log enable Off Alarm group All None 1 Applicable only if the Totalizer option is enabled Totalizers 1 Count enable Off Wrap enable On Chan...

Page 123: ...lizer reset True 1 Totalizer stop go True 1 View select True Digital Indicator View Digital indicator view enable On Archiving Archive file enables Channel data file True New file interval Hourly 1 Applicable only if the Totalizer option is enabled As D 2 1 QSMilliAmp except Analog Inputs A1 to A6 and B1 to B6 Engineering range Low 0 High 2000 Units l h Totalizers 1 Count enable Count up Count ran...

Page 124: ...nables Message select True Archiving Archive file enables Channel data file True Alarm event log file True Totalizer log file True 1 Audit log file True New file interval Hourly Recording Channel Setup Source indentifiers Channels 1 1 to 1 5 Analog input A1 to A5 Channel 1 6 Alarm State 1 1A Analog Inputs A1 to A5 Input type Type Simulated sine wave Engineering range units Ch1 1 C Ch1 2 bar Ch1 3 ...

Page 125: ...w 10 0 High 90 0 Units C Short tag Tank Long tag Tank Temperature Broken sensor direction Upscale Analog Input A2 Engineering range Low 10 0 High 90 0 Units C Short tag Return Long tag Return Temperature Broken sensor direction Upscale 1 Applicable only if the Totalizer option is enabled Ch1 1 Alarm A Alarm type Delayed high process Trip 10 0 C Hysteresis Delay time Hysteresis 0 5 C Delay time 720...

Page 126: ...oor Keys GR2000 0725 Panel Clamp GR2000 0723 Voltage Divider Board GR2000 0375 inc 250Ω shunt GR2000 0377 Compact Flash Card 512Mb B12156 1Gb B12567 2GB B12568 USB Universal Card Reader B12028 Documentation Pack User Guide this manual IM SM1000 Quick reference guide IM SM1000 Q End User Licence Agreement IM SM2000 L Data Sheet SS SM1000 ...

Page 127: ...e pack GR2000 1700 SmartMedia upgrade pack GR2000 1702 Optional I O Boards Max 4 including factory fitted option boards see Fig 5 5 on page 99 for possible combinations 3 Relay board upgrade pack GR2000 0703 6 Relay board upgrade pack GR2000 0704 Hybrid I O board upgrade pack GR2000 0705 Transmitter PSU board upgrade pack GR2000 0706 6 Channel standard analog I P board upgrade pack GR2000 0708 6 C...

Page 128: ...thought to be formatted correctly press the key to cancel formatting Remove the card and re insert If the error persists press the key to format the card Note this erases all data on the card The storage card folder has been successfully formatted It contains XXMb of usable space Press the key An error occurred while formatting the storage card folder Press the key to clear the message box Remove ...

Page 129: ...arm Delayed Low Process Alarm High Latch Alarm Low Latch Alarm Fast Rate Alarm Slow Rate Alarm High Annunciate Alarm Low Annunicate Alarm Real Time Alarm Daylight Saving Start End Changed Alarm Acknowledged Operator Message Totalizer Started Totalizer Stopped Totalizer Wrapped Totalizer Reset Intermediate Value Reached Timed Event Triggered Event Power Failed Power Restored Batch Total Maximum Val...

Page 130: ...y System Basic BCD Binary Encoded Digital Inputs 94 104 Binary Format Archive Files 41 to 43 C Channel Indicator Tags 76 77 Chart Annotation 11 64 AutoView Scroll 13 16 19 22 Electronic Signature 14 59 Scales 10 13 65 Traces 8 13 65 73 Views Horizontal 7 Vertical 7 Zoning 73 Configuration Access 45 46 Alarms 78 to 83 Analog Input 74 to 77 Electrical Range 75 Engineering Range 76 Input Adjustment 8...

Page 131: ...ctrical Connections 98 to 103 Fitting the Instrument 97 Mounting Dimensions 97 Instrument Status 28 Instrument Tag 52 L Language 52 Linearizer Type 75 Linearizer Units 75 Log Sizes 60 M Mains Power Connections 102 Mains Rejection Frequency 89 Modbus RS485 91 to 93 Baud Rate 91 Character Set for Remote Operator Messages 115 Master Poll Limit 91 Poll Rate 91 Response Timeout 91 RTU Address 92 RTU ad...

Page 132: ...reen Saver 53 Security system Advanced 29 30 Basic 29 56 58 Setup Level Accessing 29 Passwords 31 Menu 32 Recording Control 32 Signal Sources 104 Simulated Inputs 74 Siting 96 Span Adjust 90 Spare Parts and Accessories 124 Storage Capacity External Media 117 Internal Memory 116 System Administrator 30 46 56 57 60 T Text Format Archive Files 37 to 40 Thermocouple Compensating Cable 90 100 102 Total...

Page 133: ... Analytics Instrumentation pH Conductivity and Dissolved Oxygen Transmitters and Sensors Ammonia Nitrate Phosphate Silica Sodium Chloride Fluoride Dissolved Oxygen and Hydrazine Analyzers Zirconia Oxygen Analyzers Katharometers Hydrogen Purity and Purge gas Monitors Thermal Conductivity Customer Support We provide a comprehensive after sales service via a Worldwide Service Organization Contact one...

Page 134: ...ntained herein without notice Printed in UK 04 09 ABB 2009 ABB Limited Howard Road St Neots Cambridgeshire PE19 8EU UK Tel 44 0 1480 475321 Fax 44 0 1480 217948 ABB Inc 125 E County Line Road Warminster PA 18974 USA Tel 1 215 674 6000 Fax 1 215 674 7183 Modbus is a registered trademark of the Modbus IDA organization Microsoft is a registered trademark of Microsoft Corporation in the United States ...

Reviews: