Videographic Recorder
SM1000
4 Configuration
IM/SM1000
Issue 11
87
4.7 Functions
4.7.1 Custom Linearizers
Fig. 4.17 Functions Configuration
Use the
and
keys to highlight the linearizer to be
adjusted.
Press the
key to open the 'Adjust custom linearizer' screen.
Use the
,
,
and
keys to highlight the point to
be modified.
Press the
key to open the digipad to change the position of
that point.
Press the
key to return to the Functions screen.
Each linearizer has 20 breakpoints. Both X and Y values are set
as percentages.
Custom linearizers can be applied to any analog input by
selecting them as the linearizer type for that input – see
Section 4.6.2, page 74.
Note
.
X is input to the linearizer expressed as a percentage of the
electrical range.
Y is output expressed as a percentage of the engineering range.