7/16
1 HDU 05004-YN Rev. C
part 2. A “CLOSED” position signal is given after closing near the top dead center (i.e. after closing of
the current path of the disconnector and near top dead center interlocking by the operating linkage) and
is cancelled upon opening even before the top dead center is reached (i.e. before interlocking is
cancelled). The signal for the “OPEN” position is given analogously.
The safety contact (14) interrupts the control circuit for the motor when the manual emergency crank
(18) is inserted, so that the unit can now be operated only with the manual emergency crank.
The optional blocking magnet (19) when de-energised, prevents the motor-operated mechanism from
being operated manually, as it is not possible to insert the hand crank (18) into auxiliary pin (8) for
emergency operation. In the case of AC operation, a rectifier (37) is installed upstream of the blocking
magnet. An additional interlock switch (51), directly attached and actuated by the blocking magnet (19)
allows electrical operation only when the blocking magnet is energised.
Summary of Contents for SGF
Page 112: ...Space for further comments 105 113 1HDB 050016 YN A ...
Page 114: ...1 HDU 05004 YN Rev C Motor Operated Mechanisms Types MT50 and MT100 Instruction Manual ...
Page 128: ...15 16 1 HDU 05004 YN Rev C Note ...
Page 130: ......
Page 131: ......
Page 132: ......
Page 133: ......
Page 134: ......
Page 135: ......
Page 136: ......
Page 137: ......
Page 138: ......
Page 139: ......
Page 140: ......
Page 141: ......
Page 142: ......
Page 143: ......
Page 144: ......
Page 145: ......
Page 146: ......
Page 147: ......
Page 148: ......
Page 149: ......
Page 150: ......
Page 151: ......
Page 152: ......
Page 153: ......
Page 154: ......
Page 155: ......
Page 156: ......