6.4
Minimum Distance between Disconnector Poles
Note :
The precise dimensions are contained in the dimension drawing supplied. The dimensions in
Table 6 are standard values.
Table 6 :
Minimum distances P
min
between poles of disconnector in series and parallel arrangement
(standard values)
Rated voltage
kV
123
145
170
245
300
Parallel arrangement
mm
1 970
2 330
2 640
3 570
4 000
+ Series arrangement
mm
2 700
3 150
3 530
4 920
5 700
Table 8 :
Minimum distances Pmin between poles of disconnector in parallel arrangement
Figure 9 :
Minimum distances Pmin between poles of disconnector in series arrangement