Figure 64 :
Mounting of earthing switch : Earthing contact (18), adjusting measurements
Pole distance
Operated pole : a
Operated pole : b
Operated pole : c
20
0
0
10
10
10
0
0
20
30
0
0
15
15
15
0
0
30
40
0
0
20
20
20
0
0
40
I (recommended presetting on poles a, b, c during mounting)
2 000 ... 2 999 mm
3 000 ... 3 999 mm
4 000 ... 4 999 mm
I (after
mounting)
a
mm
b
mm
c
mm
a
mm
b
mm
c
mm
a
mm
b
mm
c
mm
mm
max. 5
(on one pole
of 3-pole
group)
Rated voltage 36 ... 170 kV,
and rated peak - withstand current < 100 kA
Rated voltage 245 ... 362 kV,
and rated peak - withstand current > 100 kA
I = distance between rear contact finger (20)
and stop (21) of earthing contact (18)
75/113
1HDB 050016-YN-A
Summary of Contents for SGF
Page 112: ...Space for further comments 105 113 1HDB 050016 YN A ...
Page 114: ...1 HDU 05004 YN Rev C Motor Operated Mechanisms Types MT50 and MT100 Instruction Manual ...
Page 128: ...15 16 1 HDU 05004 YN Rev C Note ...
Page 130: ......
Page 131: ......
Page 132: ......
Page 133: ......
Page 134: ......
Page 135: ......
Page 136: ......
Page 137: ......
Page 138: ......
Page 139: ......
Page 140: ......
Page 141: ......
Page 142: ......
Page 143: ......
Page 144: ......
Page 145: ......
Page 146: ......
Page 147: ......
Page 148: ......
Page 149: ......
Page 150: ......
Page 151: ......
Page 152: ......
Page 153: ......
Page 154: ......
Page 155: ......
Page 156: ......