SafeGear ratings*
Characteristic
Unit
Rated maximum voltage level
5 kV
8.25 kV
15 kV
Rated nominal voltages
kV
2.4, 4.16, 4.8
4.8, 6.9, 7.2
6.9, 7.2, 8.4, 11, 12, 12.47,
13.2, 13.8, 14.4
Main bus continuous current
A
1200, 2000, 3000, 4000**
Short term current (rms)
kA
25, 31.5, 40, 50
Rated frequency
Hz
50, 60
Low frequency withstand (rms)
kV
19
36
36
Impulse level (BIL,crest)
kV
60
95
95
* Ratings given are for service conditions within temperature and altitude limitations as defined by IEEE C37.20.2-2015 metal-clad standard.
** 4000 A is forced-air cooled.
For 5 kV applications, SafeGear switchgear utilizes
ABB VIY-60 potential transformers. For 15 kV appli-
cations, SafeGear uses ABB VIZ-11 and VIZ-75 PTs. All
PTs are available in wye-wye, open delta, line to line
and line to ground connections.
Rating tables and additional details for all instru-
ment transformers can be found in the Switchgear
Components and Accessories Technical and Appli-
cations Guide (1VAL104601-TG)