T EC H N I C A L A N D A P P L I C AT I O N G U I D E
21
—
Available frame types
Breaker and auxiliary frames
—
Dimensions
Frame
Width (in)
Height (in)* Depth (in)
2000/3000 A
breaker
36
129.5
86.5 or 93.5
All other frames
36
118
86.5 or 93.5
* Height includes plenum
Options
• Ground CTs
• Surge arrestors
- Distribution
- Intermediate
- Station
• Surge capacitor
• Ground studs
• Space heaters
• Cable supports
Description
The two-high breaker and auxiliary frame consists
of two 38-inch compartments with a 19-inch instru-
ment compartment in between for one breaker and
an auxiliary device in a single frame or one 38-inch
compartment with 19-inch low voltage and two 19-
inch auxiliary compartments for equipment with
short circuit ratings less than 40 kA.
—
Cable termination information
Cable size
# of terms
single pad
per phase
# of terms
bifurcated
pad per
phase*
GCT
option
#2 AWG
4
8
BYZ-S
#4 AWG
4
8
BYZ-S
500 MCM
4
8
BYZ-S
750 MCM
4
8
BYZ-L
1000 MCM (2-hole) 2
4
BYZ-S
1000 MCM (4-hole) 1
2
BYZ-S
* Bifurcated lug pad requires 93.5-inch depth
All ratings (refer to page 29 and 30 for floorplans)
—
01 Breaker below
—
02 Breaker above
—
01
—
02