![ABB SafeGear Technical And Application Manual Download Page 20](http://html.mh-extra.com/html/abb/safegear/safegear_technical-and-application-manual_2855020.webp)
T EC H N I C A L A N D A P P L I C AT I O N G U I D E
19
Description
The one-high, bottom mounted device frame con-
sists of a 57-inch instrument compartment stacked
over a 38-inch breaker, PT, CPT or draw-out fuse
compartment.
—
Cable termination information
Cable size
# of terms
single pad
per phase
# of terms
bifurcated
pad per
phase*
GCT
option
#2 AWG
4
8
BYZ-S
#4 AWG
4
8
BYZ-S
500 MCM
4
8
BYZ-S
750 MCM
4
8
BYZ-L
1000 MCM (2-hole) 2
4
BYZ-S
1000 MCM (4-hole) 1
2
BYZ-S
* Bifurcated lug pad requires 93.5-inch depth
—
Available frame types
One-high frames
—
Dimensions
Frame
Width (in) Height (in)* Depth (in)
2000/3000/4000
A breaker
36
129.5
86.5 or 93.5
All other frames
36
118
86.5 or 93.5
* Height includes plenum
Options
• Ground CTs
• Surge arrestors
- Distribution
- Intermediate
- Station
• Surge capacitor
• Ground studs
• Space heaters
• Cable supports
All ratings (refer to page 31 for floorplans)