Description
The two-high breaker frame consists of two 38-
inch breaker compartments with a 19-inch instru-
ment compartment in between for two breakers in
a single frame.
—
Cable termination information
Cable size
# of terms
single pad
per phase
GCT option
#2 AWG
4
BYZ-S
#4 AWG
4
BYZ-S
500 MCM
4
BYZ-S
750 MCM
4
BYZ-L
1000 MCM (2-hole)
2
BYZ-S
1000 MCM (4-hole)
1
BYZ-S
—
Available frame types
Two-high frames
—
Dimensions
Frame
Width (in) Height (in)* Depth (in)
2000/3000 A
breaker
36
129.5
86.5 or 93.5
All other frames
36
118
86.5 or 93.5
* Height includes plenum
Options
• Ground CTs
• Surge arrestors
- Distribution
- Intermediate
- Station
• Surge capacitor
• Ground studs
• Space heaters
• Cable supports
All ratings (refer to page 28 for floorplans)