44
SA FEG E A R®
5/ 1 5 K V, U P TO 5 0 K A A R C- R E S I S TA N T S W I TC H G E A R
To calculate the weight of a frame, identify the cur-
rent rating for each module. Select the weights
from the appropriate column in the adjoining table
for SafeGear components.
A frame consists of one bus and cable module and
the approriate circuit breaker and auxiliary mod-
ules. The weight of the circuit breaker is given sep-
arately and must be added.
Low voltage modules may contain significant
amount of secondary equipment and wiring. De-
pending on the extent of secondary protection and
control equipment, ABB recommends adding 20%
to 50% of the empty weight of the module.
Typical frame weights are listed in the adjoining ta-
ble. Weights include all modules and components
previously listed.
—
Frame weights calculation
All frame styles
Basic frame
configuration
Circuit breaker
(rating)
Weight
lbs
kg
One circuit
breaker
1200
2023
918
2000
2441
1107
3000
3331
1511
4000
3461
1570
Two circuits
breakers
1200/1200
3013
1367
1200/2000
3302
1498
One circuit
breaker, one VT
1200
2440
1107
2000
2858
1396
3000
3748
1700
One circuit
breaker, two VTs
1200
2859
1297
2000
3277
1486
One circuit
breaker, one VT
1200
3210
1456
2000
3628
1646
One circuit
breaker, one CPT
fuse
1200
2590
1175
2000
3008
1364
Note: These weights do not include the circuit break-
ers. Please reference the AMVAC or ADVAC breaker
technical guides for more information