T EC H N I C A L A N D A P P L I C AT I O N G U I D E
35
—
Civil engineering details
Typical side views, floor plans, and clearances
SafeGear switchgear two-high frames
Circuit breaker: 1200 A/1200 A
SECTION VIEW
1200A
1200A
FLOOR PLAN
CONTROL CABLE
ENTRY AREA
(4) 1/2"- 13 UNC
ANCHOR BOLTS PER FRAME
POWER CABLE
ENTRANCE
18.5''[469.9 mm]
27''[685.8
mm]
4.5''[114.3 mm]
4.5''[114.3 mm]
36''[914.4
mm]
86.35''[2193.29 mm]
93.35''[2371.09 mm]
0.375''[9.52 mm]
0.375''[9.52 mm]
25.5''[647.7 mm]