N° Doc.
Doc. No.
Mod.
Rev.
M4379
SACE Emax
601933/003
Aparato
Apparatus
Escala
Scale
N° Pag.
Sh. No.
52/100
12. Unidad de protección PR111/LI - LSI - LSIG
12.1 Generalidades
La unidad SACE PR111/P realiza las siguiente funciones de protección:
L
– protección contra sobrecarga a tiempo largo inverso
S
– protección contra cortocircuito a tiempo corto
I
– protección contra cortocircuito instantáneo
G
– protección contra defecto a tierra
Iinst
– protección rápida contra cortocircuito instantáneo
Las unidades SACE PR111 disponibles para el usuario son:
PR111/L+I+Iinst
12. PR111/LI - LSI - LSIG protection unit
12.1 General
The SACE PR111/P unit carries out the following protection functions:
L
– protection against overload with inverse long time-delay
S
– protection against short-time short-circuit
I
– protection against instantaneous short-circuit
G
– protection against earth fault
Iinst
– rapid protection against instantaneous short-circuit
The SACE PR111 units available to the user are:
In=
I
TEST
L
I
1
=
t
1
x
I
n
A
B
C
D
0.4
0.5
0.6
0.7 0.8 0.9 0.95
1
I
3
=
x
I
n
1.5
2
4
6
8
10
12
OFF
I
= 6
I
1
N r. =
15 Vdc
+
I n N = I n / 2
L
I
t
t1
I
I
3
I
1
3s
6s
12s
18s
SACE PR111/P
S
I
TEST
L
I1=
t1
OFF
1
2
3
4
6
8
10
A
B
C
D
x In
A
B
C
D
0.4
0.5
0.6
0.7 0.8 0.9 0.95
1
I2=
x In
I3=
x In
1.5
2
4
6
8
10
12
OFF
I = 6 I 1
I = 8 I n
I > I 2
t2
N r. =
15 Vdc
+
I n N = I n / 2
L
S
I
t
t1
t2
In
I3
I2
I1
In=
0.05s 0.10s 0.25s 0.5s
3s
6s
12s
18s
SACE PR111
S
I
G
TEST
L
I1=
t1
OFF
1
2
3
4
6
8
10
A
B
C
D
x In
A
B
C
D
A
B
C
D
0.4
0.5
0.6
0.7 0.8 0.9 0.95
1
I2=
x In
I3=
x In
I4=
x In
1.5
2
4
6
8
10
12
OFF 0.2 0.3 0.4 0.6 0.8 0.9
1
OFF
I = 6 I 1
I = 8 I n
I > I 2
t2
t4
N r. =
15 Vdc
+
I n N = I n / 2
In=
t
t4
I
I4
SACE PR111
0.1s 0.2s
0.4s 0.8s
0.05s 0.10s 0.25s 0.5s
3s
6s
12s
18s
The protections can be made either in three-phase or three-phase with
neutral mode, depending on the type of circuit-breaker used (three-pole,
four-pole or three-pole with external neutral).
The unit is self-powered and ensures correct operation of the protection
functions when there is a current higher than or equal to 18% of the rated
phase current transformer value (CT).
The protection release assembly consists of the following:
– 3 or 4 current transformers (CT)
– SACE PR111 protection unit
– an opening solenoid (OS) of the overcurrent release which acts directly
on the circuit-breaker operating mechanism.
Las protecciones se pueden efectuar de manera trifásica o trifásica con
neutro en función del tipo de interruptor utilizado (tripolar, tetrapolar o
tripolar con neutro exterior).
La unidad está autoalimentada y garantiza el funcionamiento correcto de
las funciones de protección en presencia de una corriente mayor o igual
al 18% del valor nominal del transformador amperimétrico de fase (TA).
El grupo relé de protección está formado por:
– 3 o 4 transformadores de corriente (TA)
– unidad de protección SACE PR111
– un solenoide de apertura (SA) del relé de sobreintensidad que actúa
directamente en el mando del interruptor.
PR111/L+S+I+G+Iinst
PR111/L+S+I+Iinst
Fig. 47