AI815/AI845
Section 3 Run-time Operation
64
3BSE027630-600 B
Mark the Redundancy check box if the unit shall be set for redundant operation.
This check box is only applicable for AI845 when configured via CI840.
Mark the External power supervision check box if supervision of the power
supply to the transducer shall be enabled. If an error occurs the status of the unit is
updated and the channel status bits will be set.
In the Shunt mode drop-down menu you can choose between ‘Internal shunt’ or
‘External shunt’. External shunt shall always be set together with MTU TU844 or
TU845, and at voltage signal together with other MTUs.
Figure 24. AI845 - Configuration - Module Parameters Tab