AI895
Section 3 Run-time Operation
96
3BSE027630-600 B
–
Operations in progress
–
Hardware faults
–
Instruments scan faults and status
–
Instruments communication error bits
–
Instruments status bits
See
I/O Module Status area
for more information.
•
Flush completed delayed response
This function will delete the response that is stored in the buffer. If the DTM is
in a lock situation when the I/O module always response busy then this
function can be used to flush the HART response buffer.
•
Read gateway parameters
This function will read gateway parameters for the module. These are:
–
Number of instruments in list
–
Number of instruments scanned
–
Delayed response, primary master
–
Scan enabled
–
Number of retries for busy response
–
Number of retries for error response
•
Enable scan status
This function turns on the scanning.
The scanning function is implemented to monitor the presence of field
instruments. When the scanning is enabled, all instruments of the instrument
lists are scanned with HART command 1. A different channel every 5s. If an
instrument does not reply the DISAPPEARED and SEARCHING bits related
to that instrument are set, else the SCAN_ENABLED will be set.
For the instrument that is not replying the module begins to scan that
instrument with HART command 0. If there is a reply to command 0, the
module verifies if it comes from the original instrument:
Summary of Contents for S800 I/O
Page 1: ...Power and productivity for a better world S800 I O DTM 6 0 System Version 6 0 ...
Page 2: ......
Page 3: ...S800 I O DTM 6 0 ...
Page 20: ...Intended User Section 1 Introduction 20 3BSE027630 600 B ...
Page 28: ...Initial Installation Section 2 Installation 28 3BSE027630 600 B ...
Page 172: ...DP840 Dynamic values Appendix B Dynamic Data 172 3BSE027630 600 B ...
Page 174: ...Updates in Revision Index B 174 3BSE027630 600 B ...
Page 175: ......