background image

81

Summary of Contents for RIO600

Page 1: ...Remote I O RIO600 Configuration Manual ...

Page 2: ......

Page 3: ...Document ID 1MRS757489 Issued 2011 12 23 Revision A Product version 1 0 Copyright 2011 ABB All rights reserved ...

Page 4: ...is document is furnished under a license and may be used copied or disclosed only in accordance with the terms of such license Trademarks ABB and Relion are registered trademarks of the ABB Group All other brand or product names mentioned in this document may be trademarks or registered trademarks of their respective holders Warranty Please inquire about the terms of warranty from your nearest ABB...

Page 5: ...product failure would create a risk for harm to property or persons including but not limited to personal injuries or death shall be the sole responsibility of the person or entity applying the equipment and those so responsible are hereby requested to ensure that all measures are taken to exclude or mitigate such risks This document has been carefully checked by ABB but deviations cannot be compl...

Page 6: ...erning electrical equipment for use within specified voltage limits Low voltage directive 2006 95 EC This conformity is the result of tests conducted by ABB in accordance with the product standards EN 50263 and EN 60255 26 for the EMC directive and with the product standards EN 60255 1 and EN 60255 27 for the low voltage directive The product is designed in accordance with the international standa...

Page 7: ... a project 11 Handling connectivity packages 11 Uninstalling connectivity packages 11 Installing connectivity packages 11 Activating connectivity packages 14 Creating a new project 15 Building the plant structure 16 Inserting IEDs 17 Inserting an IED in offline mode 18 Inserting an IED in online mode 24 Setting the technical key 32 Editing object properties 35 Section 4 Using the Parameter Setting...

Page 8: ...ngineering 65 Creating a project 65 Importing an SCL file in IET600 66 Creating GOOSE datasets 68 Defining data attributes 70 Configuring GOOSE control blocks 70 Configuring a GOOSE Subscriber 72 Exporting SCD files in IET600 72 Section 9 Troubleshooting 75 Troubleshooting the technical key in online mode 75 Troubleshooting the reading and writing of parameters 76 Section 10 Glossary 79 Table of c...

Page 9: ... tasks and a description of the basic operations The configuration manual contains information on how to engineer the device using the different tools in PCM600 The manual provides information for IEC 61850 engineering with PCM600 and IET600 For more details on tool usage see the PCM600 documentation The user manual online help contains instructions on how to use the RIO600 Configuration Wizard Th...

Page 10: ...the reader of important facts and conditions The tip icon indicates advice on for example how to design your project or how to use a certain function Although warning hazards are related to personal injury it is necessary to understand that under certain operational conditions operation of damaged equipment may result in degraded process performance leading to personal injury or death Therefore co...

Page 11: ...es are shown in italics The function can be enabled and disabled with the Operation setting Parameter values are indicated with quotation marks The corresponding parameter values are On and Off 1MRS757489 A Section 1 Introduction RIO600 5 Configuration Manual ...

Page 12: ...6 ...

Page 13: ... Automation device COM600 used in power generation plants utility substations and industrial power systems GUID 10936B8E CD69 425B A212 BBACE48211EC V1 EN Figure 1 RIO600 RIO600 is designed to function with ABB IEDs and also with other RIO600 units to exchange binary I O information over Ethernet 1MRS757489 A Section 2 RIO600 overview RIO600 7 Configuration Manual ...

Page 14: ...etails of the IED are available in the respective manuals 2 1 1 Module configuration RIO600 is designed using a modular architecture where the I O control functionality is built on modules The RIO600 modules can be stacked on a standard DIN rail to achieve the required configuration The minimum configuration required for RIO600 is PSM_H LECM DIM8_H or PSM_H LECM DOM RIO600 consists of four module ...

Page 15: ...ed to establish the GOOSE communication between the IEDs configured in PCM600 2 2 1 PCM600 and RIO600 connectivity package version Protection and Control IED Manager PCM600 Ver 2 3 or later RIO600 Connectivity Package Ver 1 0 or later 2 3 Hardware and software requirements Table 1 Requirements Description Requirements Hardware Pentium III 800 MHz or higher 128 RAM or higher 40 MB free disk space S...

Page 16: ...hannels and also creates the datasets comprising all the BI channel status and health information Export the SCD file to the IET600 tool Enter the GoCB parameters for RIO600 and do subscriber mapping Export the SCD file to PCM600 Map the I O using SMT in PCM600 Select the write operation and download the configuration into RIO600 Use the Web client to view parameter settings and other operational ...

Page 17: ...ck Remove GUID A10FAF3F F32A 4E5F 99EC B6EFAC770898 V1 EN Figure 4 Selecting the RIO600 connectivity package 4 In the Add or Remove Programs dialog box click Yes to confirm the uninstallation 3 1 2 Installing connectivity packages Install Microsoft NET Framework 2 0 and PCM600 Version 2 4 Production Build before installing the RIO600 connectivity package 1 Run the ABB RIO600 Connectivity Package V...

Page 18: ...back to the installation or Exit Setup to confirm the cancellation 3 Select I accept the license agreement and click Next GUID A6406B4A C038 4BE8 A6E6 4CB6A23E817A V1 EN Figure 6 Accepting the License Agreement before installation 4 Click Browse select the file destination and click Next Section 3 1MRS757489 A Setting up a project 12 RIO600 Configuration Manual ...

Page 19: ... installation 5 Click Next to start the installation GUID AF3833E9 54FB 41C1 B70B 98CE07D1AA9F V1 EN Figure 8 Installation progress 6 After the installation is complete click Finish to exit the setup program 1MRS757489 A Section 3 Setting up a project RIO600 13 Configuration Manual ...

Page 20: ...e click the Update Manager icon on Windows desktop to activate the appropriate connectivity package The Update Manager shows the connectivity packages that are compatible with the installed PCM600 version 2 Select the ABB RIO600 Connectivity Package Ver n n version number Always use the latest version of the connectivity package Section 3 1MRS757489 A Setting up a project 14 RIO600 Configuration M...

Page 21: ... click File point to Open and click Manage Project The Open Manage Project window is displayed GUID 6A3174B2 48C1 4D34 B01B 2AA21841FE3E V1 EN Figure 11 Managing projects 3 Select Projects on my computer If there are currently any projects or object tools open close them 4 Click New Project The Create New Project dialog box opens 1MRS757489 A Section 3 Setting up a project RIO600 15 Configuration ...

Page 22: ... 482E 9E33 EE2CAB5E5715 V1 EN Figure 13 Naming a project 6 Click Create PCM600 sets up a new project that is listed under Projects on my computer 3 3 Building the plant structure 1 Create a new plant structure in PCM600 1 1 In the Plant Structure view right click and select New General 1 2 Select the element like Substation Voltage level and Bay Section 3 1MRS757489 A Setting up a project 16 RIO60...

Page 23: ...operties view 3 4 Inserting IEDs IEDs can be inserted to the project either in offline or online mode When the physical device is not available or not connected to PCM600 the engineering is done without any synchronization with the device The offline configuration in PCM600 can be synchronized with the physical device later by connecting the device to PCM600 Working in the offline mode has an adva...

Page 24: ...retain the communication parameter s value In Parameter Setting tool the communication parameters are then updated according to the device configuration Otherwise the Parameter Setting tool contains the default data for example the default IP Address 192 168 2 10 3 4 1 Inserting an IED in offline mode 1 In the Plant Structure view right click the bay and select New Remote I O IEDs RIO600 The Confi...

Page 25: ...80F 91E305615A05 V1 EN Figure 17 Selecting IED protocol in offline mode 4 Under PCM600 communication define the communication parameters and click Next 1MRS757489 A Section 3 Setting up a project RIO600 19 Configuration Manual ...

Page 26: ...tion parameters in offline mode 4 1 In the Port list select the port to be used 4 2 In the IP Address box enter the correct IP address 5 In the Communication configuration complete dialog box click Next Section 3 1MRS757489 A Setting up a project 20 RIO600 Configuration Manual ...

Page 27: ...communication parameter configuration in offline mode 6 In the Composition selection page dialog box configure the channels and generate the order code As a default the channels are not configured 1MRS757489 A Section 3 Setting up a project RIO600 21 Configuration Manual ...

Page 28: ...ype and software version choices are enabled 6 2 Click Generate to generate an order code based on the selected composition 7 In the Generating functions dialog box wait until the function generation is ready and click Close 8 In the Composition selection page dialog box click Next 9 In the Setup complete dialog box click Finish Section 3 1MRS757489 A Setting up a project 22 RIO600 Configuration M...

Page 29: ...ck OK to close the configuration setup wizard The plant structure is updated according to the hardware configuration The module types and the related positions are visible under the HW Configuration For example DIM8GGIO1 represents Position 1 and module type DIM8 1MRS757489 A Section 3 Setting up a project RIO600 23 Configuration Manual ...

Page 30: ...lant structure Use Back and Next to navigate between the pages in the setup wizard 3 4 2 Inserting an IED in online mode To set up a device in online mode the device must be connected to PCM600 1 In the Plant Structure view right click the bay and select New Remote I O IEDs RIO600 The Configuration mode selection page dialog box opens 2 Under Configuration mode select Online Configuration and clic...

Page 31: ...4CE4 B436 49FE8E6CA8B1 V1 EN Figure 23 Selecting online configuration mode 3 In the IED protocol list select for example IEC 61850 and click Next 1MRS757489 A Section 3 Setting up a project RIO600 25 Configuration Manual ...

Page 32: ...ocol in online mode 4 Under PCM600 communication define the communication parameters and click Next 4 1 In the Port list select the port to be used 4 2 In the IP Address box enter the correct IP address Section 3 1MRS757489 A Setting up a project 26 RIO600 Configuration Manual ...

Page 33: ...A447 F735D12B9CEB V1 EN Figure 25 Defining communication parameters in online mode 5 In the Communication configuration complete dialog box click Next 1MRS757489 A Section 3 Setting up a project RIO600 27 Configuration Manual ...

Page 34: ...re 26 Completing communication parameter configuration in offline mode 6 In the Composition selection page dialog box click Scan to read the hardware configuration from the device Section 3 1MRS757489 A Setting up a project 28 RIO600 Configuration Manual ...

Page 35: ...In the Generating functions dialog box wait until the function generation is ready and click Close 8 In the Composition selection page dialog box click Next In online mode the composition selection data is read only and cannot be edited 1MRS757489 A Section 3 Setting up a project RIO600 29 Configuration Manual ...

Page 36: ... Figure 28 Viewing device configuration in online mode 9 In the Setup complete dialog box click Finish The plant structure is updated according to the hardware configuration Section 3 1MRS757489 A Setting up a project 30 RIO600 Configuration Manual ...

Page 37: ...page in online mode GUID 500C7771 596F 41B1 BA4B EDEEF7F6AA3A V1 EN Figure 30 Updating the plant structure in online mode In the plant structure the Application configuration does not contain any data 1MRS757489 A Section 3 Setting up a project RIO600 31 Configuration Manual ...

Page 38: ...k mark in front of the node and device name indicates successful communication between PCM600 and the device 3 5 Setting the technical key The technical key is used for the unique identification of each device and can be modified to create a new device 1 In the Plant Structure right click on RIO600 and select Set Technical Key in IED Section 3 1MRS757489 A Setting up a project 32 RIO600 Configurat...

Page 39: ...4B98F17F6 V1 EN Figure 31 Setting technical key 2 In the Technical Key Information dialog box click OK Click Cancel or close the dialog box to cancel the setup 1MRS757489 A Section 3 Setting up a project RIO600 33 Configuration Manual ...

Page 40: ... user defined technical key Select Technical Key in IED to set IED technical key to PCM600 Select Technical Key in PCM600 to set PCM600 technical key to IED Select User defined Technical Key to provide technical key to IED as well as to PCM600 4 Wait until the configuration is complete and click OK The technical key can be modified using the Object Properties Section 3 1MRS757489 A Setting up a pr...

Page 41: ... object properties The Object Properties window is used to view the parameters set during the configuration setup For example the IP Address and Technical Key can be changed directly via the Object Properties of the selected device 1 In the Plant Structure view select a device 2 On the View menu click Object Properties The Object Properties window opens 3 Type in the value like a new IP address to...

Page 42: ...ure 36 Viewing Object properties The changes in the IP Address and Technical Key do not reflect in the device but are used to establish a connection between PCM600 and the device Section 3 1MRS757489 A Setting up a project 36 RIO600 Configuration Manual ...

Page 43: ...t Write to IED In the Plant Structure view right click a device and select the Parameter Setting to view the configured parameters for the selected device GUID 9B08B99B 5367 4007 8D4A FBD71EB8A10B V1 EN Figure 37 Select Parameter Setting The Parameter Setting window shows the parameters of all modules 1MRS757489 A Section 4 Using the Parameter Setting tool RIO600 37 Configuration Manual ...

Page 44: ... 1 Click to read parameters from the device The Read parameters from RIO600 dialog box opens GUID C0262BF3 B922 4FCD B178 267B4964A053 V1 EN Figure 39 Reading parameters 2 Under Parameter range select which parameters are read from the device Section 4 1MRS757489 A Using the Parameter Setting tool 38 RIO600 Configuration Manual ...

Page 45: ...meters from the device 4 3 Setting communication and synchronization parameters 1 In the Plant Structure view go to RIO600 IED Configuration HW Configuration LECM to set the communication parameters GUID 93006CF0 AED8 4CE8 B67F C3019156CA0C V1 EN Figure 40 Selecting LECM to set communication parameters 2 Right click LECM and select Parameter Setting to display the general communication and synchro...

Page 46: ... required configuration 4 4 Writing parameters to the device 1 Click to write parameters to the device The Write parameters to RIO600 dialog box opens 2 Under Parameter range select which parameters are written to the device All parameters of a device like RIO600 A selected group of parameters like General Parameters A selected parameter like IP Address Section 4 1MRS757489 A Using the Parameter S...

Page 47: ...there are no modified or changed parameters and the selected parameter range is All parameters an error message appears GUID FCA4A882 5AFD 4716 939B 157C44E9FA74 V1 EN Figure 43 Detecting modified parameters 5 Wait until the parameters are written to the device and the device reboots The Output window message indicates if the parameters are successfully written to the device If the parameters are ...

Page 48: ...GUID ACC63F51 D685 4A98 A841 7CBAA2DB0688 V1 EN Figure 44 Failing to update parameter value Section 4 1MRS757489 A Using the Parameter Setting tool 42 RIO600 Configuration Manual ...

Page 49: ...er the IEC 61850 communication link In a PCM600 project the other IEDs see the RIO600 binary inputs in the SMT GOOSE page after the system configuration GUID 538E3515 62DA 42BF B653 D4AA7D2251DA V1 EN Figure 45 Signal Matrix tool before GOOSE engineering In the Plant Structure right click a device and select Signal Matrix 1MRS757489 A Section 5 Using the Signal Matrix tool RIO600 43 Configuration ...

Page 50: ...g SCD files After the RIO600 parameters are set export the System Configuration Description from PCM600 for the system configurations tool 1 In the Plant Structure view right click the substation and select Export Section 5 1MRS757489 A Using the Signal Matrix tool 44 RIO600 Configuration Manual ...

Page 51: ...Export dialog box select the file destination and click Save GUID AB744550 5769 47BE 87A5 BDC20B146A5D V1 EN Figure 48 Selecting file destination 4 In the SCL Export Options dialog box click Export to export the private sections to the SCD file 1MRS757489 A Section 5 Using the Signal Matrix tool RIO600 45 Configuration Manual ...

Page 52: ...porting SCD files After GOOSE engineering in the system configuration tool the SCD file can be imported at the substation level 1 In the Plant Structure view right click the substation and select Import Section 5 1MRS757489 A Using the Signal Matrix tool 46 RIO600 Configuration Manual ...

Page 53: ...ox locate an SCD file and click Open 3 In the SCL Import Options dialog box select how to handle the file during the import and click Import GUID CE14F387 5652 478F A010 A3D57FE84ED4 V1 EN Figure 51 Selecting SCD file 1MRS757489 A Section 5 Using the Signal Matrix tool RIO600 47 Configuration Manual ...

Page 54: ...n the SCD file whether or not the IED type s in the SCD file matches the IED object s in PCM600 3 4 Select Ignore Substation Section to not import the SSD file part of the SCD file GUID 5750D3FF C120 40E9 858D 24D7962A2CC7 V1 EN Figure 52 Importing SCD file 4 Make connections from the sending devices publisher to the receiving function blocks subscriber with the Signal Matrix tool The GOOSE connec...

Page 55: ...4 67DE6A12CE54 V1 EN Figure 53 Detecting duplicate connection 5 In the Plant Structure view select the device right click and select Write to IED 1MRS757489 A Section 5 Using the Signal Matrix tool RIO600 49 Configuration Manual ...

Page 56: ...50 ...

Page 57: ... Structure view right click the device and select Write to IED or Read from IED GUID 991A90CE EEE1 48B0 BBD1 85DAA0E59E21 V1 EN Figure 54 Reading configuration from IED The Common Read Write window is added to the tool 2 In the Read Write dialog box click Yes to proceed 1MRS757489 A Section 6 Common Read Write CRW RIO600 51 Configuration Manual ...

Page 58: ... window GUID 47E0208F 4E32 4A8A A8AF 6F636B7FAAD2 V1 EN Figure 57 Switching operation To restart the read or write operation click in the Common Read Write window If the technical key in both PCM600 and the IED matches the writing operation begins The status progress bar and the comment fields show the progress If there is no GOOSE engineering in the IED there may be no configuration in the IED th...

Page 59: ... GOOSE settings 3 The IED reboots after all the required data is written to the IED The procedure is the same when reading data from the IED except that the IED should not be restarted in between operation 1MRS757489 A Section 6 Common Read Write CRW RIO600 53 Configuration Manual ...

Page 60: ...54 ...

Page 61: ...er the composition for an existing IED can be modified with CUT 7 1 Configuring the device offline 1 In the Plant Structure view right click RIO600 and select Composition Update Tool GUID 0A6171A6 5A56 45B4 AEDE 6DEDC09A9318 V1 EN Figure 59 Selecting Composition Update Tool 1MRS757489 A Section 7 Using the Composition Update tool RIO600 55 Configuration Manual ...

Page 62: ... GUID A6041BA0 1ABE 4BF2 B6CE 3758426DBE0E V1 EN Figure 60 Selecting offline update in Composite Update tool The Composition selection page dialog box opens and shows the existing configuration of the selected IED 3 Add or remove a module or update an existing one The Generate option is enabled Section 7 1MRS757489 A Using the Composition Update tool 56 RIO600 Configuration Manual ...

Page 63: ...ed once the composition configuration is updated GUID EC4AB8BC 64EC 4BC1 A473 05566AFE0123 V1 EN Figure 62 Detecting change in composition configuration 5 In the Composition Update Tool dialog box click OK to generate the functions Click No to abort the operation 6 In the Generating functions dialog box wait until the function generation is ready and click Close 1MRS757489 A Section 7 Using the Co...

Page 64: ...ection page dialog box click Next 8 In the Setup complete dialog box click Finish 9 In the Set Technical Key dialog box click OK to close the configuration update wizard The plant structure is updated according to the hardware configuration Section 7 1MRS757489 A Using the Composition Update tool 58 RIO600 Configuration Manual ...

Page 65: ...cture 7 2 Configuring the device online 1 In the Plant Structure view right click RIO600 and select Composition Update Tool The RIO600 Composition update mode selection page dialog box opens 1MRS757489 A Section 7 Using the Composition Update tool RIO600 59 Configuration Manual ...

Page 66: ...update mode selection select Online update to configure the IED in online mode and click Next The Composition selection page dialog box opens 3 In the Composition detection page dialog box click Scan to read the configuration from the IED Section 7 1MRS757489 A Using the Composition Update tool 60 RIO600 Configuration Manual ...

Page 67: ... Tool dialog box click OK to generate the functions Click No to abort the operation 5 In Generating functions dialog box wait until the function generation is ready and click Close 6 In the Composition detection page dialog box click Next 1MRS757489 A Section 7 Using the Composition Update tool RIO600 61 Configuration Manual ...

Page 68: ...C48 AEDC 8C83231B1EE0 V1 EN Figure 67 Viewing the current configuration in online mode 7 In the Setup complete dialog box click Finish Section 7 1MRS757489 A Using the Composition Update tool 62 RIO600 Configuration Manual ...

Page 69: ...e configuration The summary of the configuration wizard selections is displayed Click Finish to close the configuration wizard setup and Plant Structure is updated for the selected IED GUID 3F92EFC9 CCBE 46C6 BFF9 7A57CB81D2C9 V1 EN Figure 69 Viewing updated plant structure 1MRS757489 A Section 7 Using the Composition Update tool RIO600 63 Configuration Manual ...

Page 70: ...64 ...

Page 71: ...C1736397 V1 EN Figure 70 Managing projects 2 In the Projects dialog box click New to create new project GUID 33B167B9 D8D8 4182 BFEB 1F5AF216D89D V1 EN Figure 71 Viewing projects Click Open to open an existing project 3 In the Create New Project dialog box enter a project name and click OK 1MRS757489 A Section 8 GOOSE engineering RIO600 65 Configuration Manual ...

Page 72: ...n SCL file in IET600 1 On the Home menu click Import GUID D07E0914 E729 4EE0 9D3E 4ADFB3E50CFD V1 EN Figure 73 Selecting Import 2 In the Import SCL File dialog box locate the SCD file to be imported in IET600 and click Open Section 8 1MRS757489 A GOOSE engineering 66 RIO600 Configuration Manual ...

Page 73: ...92C 42FC 8961 51EA3DE31B27 V1 EN Figure 74 Importing SCL file GUID AEFF005E 92FB 4451 8C5E 8765E8F01298 V1 EN Figure 75 Viewing imported SCD file 1MRS757489 A Section 8 GOOSE engineering RIO600 67 Configuration Manual ...

Page 74: ...ts in the application If the RIO stack contains more than five binary I O modules there are two default datasets instead of only one dataset 1 Select the IEDs tab in the navigation pane 2 Click the IED node to select a Publisher IED 3 Click the Datasets tab in the editor pane 4 To add a new data set right click on the area containing the data set names and select Insert new row GUID 72438822 9B69 ...

Page 75: ...ID 2CF4FF2E E871 4422 B292 10C5DD25916D V1 EN Figure 78 Creating new row under Datasets tab RIO600 supports only unstructured datasets in GOOSE A single dataset in RIO600 contains at maximum 150 data attributes 1MRS757489 A Section 8 GOOSE engineering RIO600 69 Configuration Manual ...

Page 76: ...SE control blocks 1 Select the IED node on the IEDs tab in the navigation pane 2 Select the GCB Data tab in the editor pane 3 To add a new GOOSE control block right click the area containing the existing GOOSE control blocks and select Insert new row GUID 0BC01B59 FC92 458F A351 779EC6114DAC V1 EN Figure 80 Creating new row under GCB Data tab 4 In the Create New GCB dialog box define a GCB name an...

Page 77: ...reating New GCB 5 In the Attached Dataset drop down list select the previously created data set GUID A86776E0 205A 4DA6 A832 953F2C021D3A V1 EN Figure 82 Attaching GCB to defined dataset Use a unique Multicast MAC address and APP ID 1MRS757489 A Section 8 GOOSE engineering RIO600 71 Configuration Manual ...

Page 78: ...bscribers 3 Connect the publishers and subscribers GUID 36D86174 D9AE 43EF B969 E528B1CF9DF3 V1 EN Figure 83 Making the connection between publisher and subscriber under GCB Clients tab 8 6 Exporting SCD files in IET600 1 On the Home menu click Export GUID 3DE8A07A 85D0 4FCF 97A2 7AFC24A1873A V1 EN Figure 84 Selecting Export 2 In the Export SCL File dialog box select the file destination and click...

Page 79: ...E4555D B78E 4F9B BA1E F1B0304F67C5 V1 EN Figure 85 Exporting SCL file After a successful export PCM600 can be used for further operations 1MRS757489 A Section 8 GOOSE engineering RIO600 73 Configuration Manual ...

Page 80: ...74 ...

Page 81: ...w In online mode the technical key is retrieved from the device and set to the device instance s technical key GUID AB758C3D 2812 4664 913B 81B3A2D29B4B V1 EN Figure 86 Failing to set technical key pop message GUID FCB2751E 5A38 4EB9 BADF 59FFF54968B6 V1 EN Figure 87 Failing to set technical key 2 Define the device type and communication parameters correctly If the device is not responding or is c...

Page 82: ...reading and writing of parameters Common validations while reading and writing parameters Ensure that the device is online Ensure that the device contains a valid configuration Composition of IED and IED object in PCM should match Ensure that the composition selection matches with the device Technical key in IED and PCM should match Ensure that the technical key is correct Validations while writin...

Page 83: ...5776128D7641 V1 EN Figure 90 Detecting conflicting with GOOSE connections Check that both the IRF module number and channel number are either zero or non zero GUID 8D0C19D4 538B 4FB4 B845 F5DB1BC3423D V1 EN Figure 91 Detecting IRF module and channel numbers Check that the physical MAC Address is given in XX XX XX XX XX format where X can be 0 9 a f or A F 1MRS757489 A Section 9 Troubleshooting RIO...

Page 84: ...at Check that the Oscillation Suppression Hysteresis of the Digital input module is lower than the Oscillation Upper limit GUID B68CE3DA 6815 4F60 99B5 FB85F1AD2E9E V1 EN Figure 93 Checking Oscillation Suppression Hysteresis Section 9 1MRS757489 A Troubleshooting 78 RIO600 Configuration Manual ...

Page 85: ...le four channels EMC Electromagnetic compatibility GOOSE Generic Object Oriented Substation Event HMI Human machine interface I O Input output IEC International Electrotechnical Commission IED Intelligent electronic device IET600 Integrated Engineering Toolbox in PCM600 LECM Communication module PCM600 Protection and Control IED Manager PSM_H Power supply module PST Parameter Setting tool in PCM60...

Page 86: ...80 ...

Page 87: ...81 ...

Page 88: ...mation Maneja Vadodara 390013 India Phone 91 265 2604032 Fax 91 265 2638922 ABB Transmission and Distribution Automation Equipment Xiamen Co Ltd ABB Industrial Park Torch Hi tech Development Zone 361006 Xiamen Fujian China Phone 86 592 5702288 Fax 86 592 5718598 www abb com substationautomation 1MRS757489 A Copyright 2011 ABB All rights reserved ...

Reviews: