Figure 34:
Viewing technical key properties
Do not set the same technical key for more than one device
through the
Property
window or an error appears in the
Output
window.
A valid technical key can have maximum of 32 characters.
GUID-FAE06F51-DFE2-42A9-ACE5-D4247CCF5D1B V1 EN
Figure 35:
Failing to set technical key
3.6
Editing object properties
The
Object Properties
window is used to view the parameters set during the
configuration setup. For example, the
IP Address
and
Technical Key
can be
changed directly via the
Object Properties
of the selected device.
1.
In the
Plant Structure
view, select a device.
2.
On the
View
menu, click
Object Properties
.
The
Object Properties
window opens.
3.
Type in the value like a new IP address to the
IP Address
row.
Some object properties like
Configuration Version
and
IED Type
are not
editable.
1MRS757489 A
Section 3
Setting up a project
RIO600
35
Configuration Manual