Figure 24:
DIO2001 card
5.6
Connecting power supply
The permitted auxiliary voltage range of the protection relay is marked on top of
the protection relay's LHMI.
•
Connect the relay's auxiliary voltage to terminals A1-1 and A1-2.
•
Connect the positive lead to terminal A1-1.
The allowed tightening torque for the wire clamp is 0.40...0.50 Nm
(0.2950...0.3687 ft lb).
2NGA000821 A
Section 5
Connecting
REX610
39
Installation Manual