Table 2:
Pre-defined user types
Access rights
Guest
Super User
SPA Guest
System
Operator
Protection
Engineer
Design
Engineer
User
Administrator
Basic setting possibilities (change
setting group, control settings,
limit supervision)
R
R/W
R
R/W
R/W
R/W
R
Advanced setting possibilities (for
example protection settings)
R
R/W
R
R
R/W
R/W
R
Basic control possibilities (process
control, no bypass)
R
R/W
R/W
R/W
R/W
R/W
R
Advanced control possibilities
(process control including interlock
trigg)
R
R/W
R/W
R/W
R/W
R/W
R
Basic command handling (for
example clear LEDs, manual trigg)
R
R/W
R
R/W
R/W
R/W
R
Advanced command handling (for
example clear disturbance record)
R
R/W
R
R
R/W
R/W
R/W
Basic configuration possibilities (I/
O-configuration in SMT)
R
R/W
R
R
R
R/W
R/W
Advanced configuration
possibilities (application
configuration including SMT, GDE
and CMT)
R
R/W
R
R
R
R/W
R/W
File loading (database loading
from XML-file)
-
R/W
-
-
-
R/W
R/W
File dumping (database dumping
to XML-file)
-
R/W
-
-
-
R/W
R/W
File transfer (FTP file transfer)
-
R/W
-
R/W
R/W
R/W
R/W
File transfer (limited) (FTP file
transfer)
R
R/W
R
R/W
R/W
R/W
R/W
File Transfer (SPA File Transfer)
-
R/W
-
-
-
R/W
-
Database access for normal user
R
R/W
R
R/W
R/W
R/W
R/W
User administration (user
management – FTP File Transfer)
R
R/W
R
R
R
R
R/W
User administration (user
management – SPA File Transfer)
-
R/W
-
-
-
-
-
The IED users can be created, deleted and edited only with the User Management
Tool (UMT) within PCM600. The user can only LogOn or LogOff on the local
HMI on the IED, there are no users, groups or functions that can be defined on
local HMI.
Only characters A - Z, a - z and 0 - 9 should be used in user names
and passwords.
Section 14
1MRK 511 188-UEN C
Authorization
98
Operator's manual