outputs TRIP, TRLn and TR1P should be active during first fault. No other
outputs should be active. Functional outputs TRIP, all TRLn and TR3P should
be active during second fault.
7.
Initiate a phase-to-phase fault and switch it off immediately when the trip
signal is issued for the corresponding two phases. Initiate a second phase-to-
phase fault between two other phases within the time interval, shorter
than
tEvolvingFault
(default setting 2.0s).
Check, that the output signals, issued for the first fault, correspond to a two-
trip for included phases. The output signals generated by the second fault
must correspond to the three-phase tripping action.
9.6.1.4
Circuit breaker lockout
SEMOD54375-170 v11
The following tests should be carried out when the built-in lockout function is used
in addition to possible other tests, which depends on the complete configuration of
an IED.
1.
Check that
AutoLock
and
TripLockout
are both set to
Off
.
2.
Activate shortly the set lockout (SETLKOUT) signal in the IED.
3.
Check that the circuit breaker lockout (CLLKOUT) signal is set.
4.
Activate shortly thereafter, the reset lockout (RSTLKOUT) signal in the IED.
5.
Check that the circuit breaker lockout (CLLKOUT) signal is reset.
6.
Initiate a three-phase fault.
A three-phase trip should occur and all trip outputs TRL1, TRL2, TRL3
should be activated. Functional outputs TRIP and TR3P should be active at
each fault. The output CLLKOUT should not be set.
7.
Activate the automatic lockout function, set
AutoLock
=
On
and repeat.
Besides the TRIP outputs, CLLKOUT should be set.
8.
Reset the lockout signal by activating the reset lockout (RSTLKOUT) signal.
9.
Activate the trip signal lockout function, set
TripLockout
=
On
and repeat.
All trip outputs (TRL1, TRL2, TRL3) and functional outputs TRIP and TR3P
must be active and stay active after each fault, CLLKOUT should be set.
10. Reset the lockout.
All functional outputs should reset.
11. Deactivate the trip signal lockout function, set
TripLockout
=
Off
and the
automatic lockout function, set
AutoLock
=
Off
.
9.6.1.5
Completing the test
SEMOD54375-203 v6
Continue to test another function or end the test by changing the
TESTMODE
setting to
Off
. Restore connections and settings to their original values, if they were
changed for testing purposes.
1MRK 511 425-UEN A
Section 9
Testing functionality by secondary injection
Bay control REC650 2.2 IEC
87
Commissioning manual
Summary of Contents for RELION REC650
Page 1: ...RELION 650 SERIES Bay control REC650 Version 2 2 Commissioning manual ...
Page 2: ......
Page 12: ...6 ...
Page 22: ...16 ...
Page 26: ...20 ...
Page 50: ...44 ...
Page 54: ...48 ...
Page 110: ...104 ...
Page 118: ...112 ...
Page 128: ...122 ...
Page 129: ...123 ...