![ABB RELION REC650 Commissioning Manual Download Page 72](http://html.mh-extra.com/html/abb/relion-rec650/relion-rec650_commissioning-manual_2823072.webp)
1.
Uncheck
Forcing Session
under the menu
IED
.
IEC15000031 V1 EN-US
2.
Click
Yes
in the confirmation dialogue box.
PCM600 will revert all forced signals back to unforced and the real signal
values will immediately take effect again.
This may change both binary input values and output relay states
and will undo any forcing done by using the LHMI.
If the IED is left in test mode, then it is still possible to perform
new forcing operations, both from LHMI and from PCM600
Section 8
1MRK 511 425-UEN A
Testing IED operation
66
Bay control REC650 2.2 IEC
Commissioning manual