![ABB RELION REC650 Commissioning Manual Download Page 86](http://html.mh-extra.com/html/abb/relion-rec650/relion-rec650_commissioning-manual_2823086.webp)
1.
Apply voltages U-Line (for example) = 80%
GblBaseSelLine
and U-Bus =
80%
GblBaseSelBusGblBaseSelBus
with the same phase-angle and
frequency.
2.
Check that the AUTOSYOK and MANSYOK outputs are activated.
3.
The test can be repeated with different voltage values to verify that the
function operates within the set
UDiffSC
. Check with both U-Line and U-Bus
respectively lower than the other.
4.
Increase the U-Bus to 110%
GblBaseSelBus
, and the U-Line = 90%
GblBaseSelLine
and also the opposite condition.
5.
Check that the two outputs for manual and auto synchronism are not
activated.
Testing the phase angle difference
M2377-215 v8
The phase angle differences
PhaseDiffM
and
PhaseDiffA
respectively are set to
their final settings and the test should verify that operation is achieved when the
phase angle difference is lower than this value both leading and lagging.
Test with no voltage difference.
1.
Apply voltages U-Line (for example) = 100%
GblBaseSelLine
and U-Bus =
100%
GblBaseSelBus
, with a phase difference equal to 0 degrees and a
frequency difference lower than
FreqDiffA
and
FreqDiffM
.
2.
Check that the AUTOSYOK and MANSYOK outputs are activated.
The test can be repeated with other phase difference values to verify that the
function operates for values lower than the set ones,
PhaseDiffM
and
PhaseDiffA
. By changing the phase angle on the voltage connected to U-Bus,
between ± dφ degrees, the user can check that the two outputs are activated
for a phase difference lower than the set value. It should not operate for other
values. See figure
.
+d
j
-d
j
U-Bus
U-Line operation
U-Bus
No operation
en05000551.vsd
IEC05000551 V1 EN-US
Figure 13:
Test of phase difference
3.
Change the phase angle bdφ and -dφ and verify that the two outputs
are activated for phase differences between these values but not for phase
differences outside, see figure
.
Section 9
1MRK 511 425-UEN A
Testing functionality by secondary injection
80
Bay control REC650 2.2 IEC
Commissioning manual
Summary of Contents for RELION REC650
Page 1: ...RELION 650 SERIES Bay control REC650 Version 2 2 Commissioning manual ...
Page 2: ......
Page 12: ...6 ...
Page 22: ...16 ...
Page 26: ...20 ...
Page 50: ...44 ...
Page 54: ...48 ...
Page 110: ...104 ...
Page 118: ...112 ...
Page 128: ...122 ...
Page 129: ...123 ...