9.7.5.1
Measuring the operate limit
M14955-48 v5
1.
Set the test point (|Z| fault impedance and Z
F
impedance phase angle ) for a
condition that meets the requirements in table
.
2.
Subject the IED to healthy normal load conditions for at least two seconds.
3.
Apply a fault condition.
Check that the distance-to-fault value displayed on the HMI complies with
equations
p
Z
x
X1
-------
100
×
=
EQUATION123 V1 EN-US
(Equation 5)
in % for two- and three-phase faults
x
3 Z
p
100
X0 2 X1
×
=
×
+ ×
EQUATION124 V1 EN-US
(Equation 6)
in % for single-phase-to-earth faults
p
3 Z
×
x
X0 2 X1 XM
±
×
+
---------------------------------------------
100
×
=
EQUATION125 V1 EN-US
(Equation 7)
in % for single-phase-to-earth faults with mutual zero sequence current.
Where:
p
= the expected value of a distance to fault in percent
Z
x
= set test point on the test set
X0
= set zero-sequence reactance of a line
X1
= set positive-sequence reactance of a line
XM = set mutual zero-sequence impedance of a line
9.7.5.2
Completing the test
M14955-84 v6
Continue to test another function or end the test by changing the
TESTMODE
setting to
Off
. Restore connections and settings to their original values, if they were
changed for testing purposes.
9.7.6
Limit counter L4UFCNT
GUID-7EBDC372-3407-4577-8B9A-6AB1758A1F34 v2
The Limit counter function L4UFCNT can be tested by connecting a binary input
to the counter and applying pulses to the counter. The speed of the pulses must not
exceed the cycle time of the function. Normally the counter will be tested when
testing the function that the counter is connected to, such as the trip function. When
the function is configured, test it together with the function that operates it. Trigger
Section 9
1MRK 511 425-UEN A
Testing functionality by secondary injection
94
Bay control REC650 2.2 IEC
Commissioning manual
Summary of Contents for RELION REC650
Page 1: ...RELION 650 SERIES Bay control REC650 Version 2 2 Commissioning manual ...
Page 2: ......
Page 12: ...6 ...
Page 22: ...16 ...
Page 26: ...20 ...
Page 50: ...44 ...
Page 54: ...48 ...
Page 110: ...104 ...
Page 118: ...112 ...
Page 128: ...122 ...
Page 129: ...123 ...