![ABB RELION REC650 Commissioning Manual Download Page 57](http://html.mh-extra.com/html/abb/relion-rec650/relion-rec650_commissioning-manual_2823057.webp)
•
The node addresses of the other connected IEDs.
•
The network variable selectors to be used.
This is organized by LNT.
The node address is transferred to LNT via the local HMI by setting the parameter
ServicePinMsg
=
Yes
. The node address is sent to LNT via the LON bus, or LNT
can scan the network for new nodes.
The communication speed of the LON bus is set to the default of 1.25 Mbit/s. This
can be changed by LNT.
M11888-3 v5
The LON communication setting parameters are set via the local HMI. Refer to the
Technical manual for more detailed specifications.
If LON communication from the IED stops because of illegal communication
parameter settings (outside the setting range) or due to other kind of disturbance, it
is possible to reset the IED's LON port.
M11643-1 v4
LON communication setting parameters (Table
parameters (Table
) can only be set via the LON Network Tool (LNT).
Some of these parameters can be viewed on the local HMI under
Main menu/
Configuration/Communication/Station communication/Port
configuration/SLM optical LON port/LONGEN:1
.
Table 11:
LON communication setting parameters
Parameter
Range
Default
Unit
Parameter description
DomainID
0
0
-
Domain identification number
SubnNetAddr*
0 - 255
Step: 1
0
-
Subnet address
NodeAddr*
0 - 127
Step: 1
0
-
Node address
*Can be viewed on the local HMI
Table 12:
LON node information parameters
Parameter
Range
Default
Unit
Parameter description
NeuronID*
0 - 12
Not loaded
-
Neuron hardware identification
number in hexadecimal code
Location
0 - 6
No value
-
Location of the node
*Can be viewed on the local HMI
ADE settings are available on the local HMI under
Main menu/Configuration/
Communication/Station communicaton/LON/ADE:1
1MRK 511 425-UEN A
Section 7
Establishing connection and verifying the LON communication
Bay control REC650 2.2 IEC
51
Commissioning manual
Summary of Contents for RELION REC650
Page 1: ...RELION 650 SERIES Bay control REC650 Version 2 2 Commissioning manual ...
Page 2: ......
Page 12: ...6 ...
Page 22: ...16 ...
Page 26: ...20 ...
Page 50: ...44 ...
Page 54: ...48 ...
Page 110: ...104 ...
Page 118: ...112 ...
Page 128: ...122 ...
Page 129: ...123 ...