3.3.5
Basic application functions
⃞ Test mode
⃞ Blocking of monitor direction
⊠ Disturbance data
⃞ Generic services
⊠ Private data
3.3.6
Miscellaneous
Measurands are transmitted as Class2 data using ASDU 3 or ASDU 9. The default
MVAL scalings in 615 series devices is 2.4. User can freely reprogram the MVAL
for each separate measurand.
Measurand
Max. MVAL = rated value times
1.2 or
2.4
Current L
1
⊠
⊠
Current L
2
⊠
⊠
Current L
3
⊠
⊠
Voltage L
1-E
⊠
⊠
Voltage L
2-E
⊠
⊠
Voltage L
3-E
⊠
⊠
Active power P
⊠
⊠
Reactive power Q
⊠
⊠
Frequency f
⊠
⊠
Voltage L
1
- L
2
⊠
⊠
The IED contains additional private Class2 frames, including private measurands.
User can freely select between standard or private Class2 frames.
Section 3
1MRS756712 C
Interoperability profile for 615 series IEC 60870-5-103
30
REF615
Point List Manual