![ABB Relion 615 series List Manual Download Page 21](http://html1.mh-extra.com/html/abb/relion-615-series/relion-615-series_list-manual_3383777021.webp)
IEC 61850 name
AFL-Common SA name
Description
DPI value
FUN
INF
In Use
ASDU
GI
Coding
SRGAPC1, flip-flop reset control (all variants)
LD0.SRGAPC1.Rs1.ctlVal
-
Reset SRGAPC1 flip-flop 1
10=Reset
11
101
1
20
0
1
LD0.SRGAPC1.Rs2.ctlVal
-
Reset SRGAPC1 flip-flop 2
10=Reset
11
102
1
20
0
1
LD0.SRGAPC1.Rs3.ctlVal
-
Reset SRGAPC1 flip-flop 3
10=Reset
11
103
1
20
0
1
LD0.SRGAPC1.Rs4.ctlVal
-
Reset SRGAPC1 flip-flop 4
10=Reset
11
104
1
20
0
1
LD0.SRGAPC1.Rs5.ctlVal
-
Reset SRGAPC1 flip-flop 5
10=Reset
11
105
1
20
0
1
LD0.SRGAPC1.Rs6.ctlVal
-
Reset SRGAPC1 flip-flop 6
10=Reset
11
106
1
20
0
1
LD0.SRGAPC1.Rs7.ctlVal
-
Reset SRGAPC1 flip-flop 7
10=Reset
11
107
1
20
0
1
LD0.SRGAPC1.Rs8.ctlVal
-
Reset SRGAPC1 flip-flop 8
10=Reset
11
108
1
20
0
1
Negative sequence overcurrent protection (2 stages), all variants
LD0.NSPTOC1.Str.general
NSPTOC1.START
Stage1 start
10=Stage1 start
21
84
1
2
1
1
LD0.NSPTOC1.Op.general
NSPTOC1.OPERATE
Stage1 operate
10=Stage1 operate
21
90
1
2
0
1
LD0.NSPTOC2.Op.general
NSPTOC2.OPERATE
Stage2 operate
10=Stage2 operate
21
91
1
2
0
1
LD0.NSPTOC2.Str.general
NSPTOC2.START
Stage2 start
10=Stage2 start
21
94
1
2
1
1
Fuse failure protection (1 stage), FE05,06,07
LD0.SEQRFUF1.Str.general
SEQRFUF1.FUSEF_U
General start
10=General Start
22
84
1
2
1
1
LD0.SEQRFUF1.Str3Ph.general
SEQRFUF1.FUSEF_3PH
3 phase start
10=3 phase start
22
94
1
2
1
1
Current circuit failure protection (1 stage), FE05,06,07
CTRL.CCRDIF1.Alm.stVal
CCRDIF1.FAIL
Alarm
10 = Alarm
23
1
1
1
1
1
CTRL.CCRDIF1.Op.general
CCRDIF1.ALARM
Operate
10 = Operate
23
90
1
2
0
1
Admittance based earhtfault protection, 3 stages (FE01,02,05,06,07)
LD0.EFPADM1.Str.general
EFPADM1.START
Stage1 start
10 = Stage 1 start
25
84
1
2
1
1
LD0.EFPADM1.Op.general
EFPADM1.OPERATE
Stage1 operate
10 = Stage 1 operate
25
90
1
2
0
1
LD0.EFPADM2.Op.general
EFPADM2.OPERATE
Stage2 operate
10 = Stage 2 operate
25
91
1
2
0
1
LD0.EFPADM2.Str.general
EFPADM2.START
Stage2 start
10 = Stage 2 start
25
94
1
2
1
1
LD0.EFPADM3.Str.general
EFPADM3.START
Stage3 start
10 = Stage 3 start
25
96
1
2
1
1
LD0.EFPADM3.Op.general
EFPADM3.OPERATE
Stage3 operate
10 = Stage 3 operate
25
98
1
2
0
1
Synchrocheck indications (FE08)
LD0.SECRSYN1.SynPrg.stVal
SECRSYN1.SYNC_INPRO
Synchonization in progress
10 = In progress
26
1
1
1
1
1
LD0.SECRSYN1.FailCmd.stVal
SECRSYN1.CMD_FAIL_AL
CB closing request failed
10 = Request failed
26
2
1
1
0
1
LD0.SECRSYN1.FailSyn.stVal
SECRSYN1.CL_FAIL_AL
CB closing command failed
10 = Command failed
26
3
1
1
0
1
Frequency protection (FRPFRQ1..3), 3 stages (FE08)
LD0.FRPTRC1.Str.general
FRPFRQ1.START
Stage 1 start
1 = Stage1 start
27
11
1
2
1
1
LD0.FRPTOF1.Op.general
FRPFRQ1.OPR_OFRQ
Operate
1
signal
for
overfrequency
1 = Stage1 overfrequency operate
27
12
1
2
0
1
LD0.FRPTUF1.Op.general
FRPFRQ1.OPR_UFRQ
Operate 1 signal for underfrequency
1 = Stage1 underfrequency operate
27
13
1
2
0
1
LD0.FRPFRC1.Op.general
FRPFRQ1.OPR_FRG
Operate 1 signal for frequency gradient
1
=
Stage1
frequency
gradient
operate
27
14
1
2
0
1
LD0.FRPTRC2.Str.general
FRPFRQ2.START
Stage 2 start
1 = Stage2 start
27
21
1
2
1
1
LD0.FRPTOF2.Op.general
FRPFRQ2.OPR_OFRQ
Operate
2
signal
for
overfrequency
1 = Stage2 overfrequency operate
27
22
1
2
0
1
Table continues on next page
1MRS756712 C
Section 2
IEC 60870-5-103 data mappings
REF615
15
Point List Manual
Summary of Contents for Relion 615 series
Page 1: ...Relion 615 series Feeder Protection and Control REF615 IEC 60870 5 103 Point List Manual...
Page 2: ......
Page 16: ...10...
Page 38: ...32...
Page 39: ...33...