ABB Relion 615 series List Manual Download Page 26

IEC 61850 name

AFL-Common SA name

Description

DPI value

FUN

INF

In Use

ASDU

GI

Coding

Directional earth-fault protection (3 stages), FE01,02,05,06, 07

LD0.DEFLPTOC1.Str.general

DEFLPDEF1.START

Low(1) stage start

10=Low(1) stage start

163

84

1

2

1

1

LD0.DEFLPTOC1.Op.general

DEFLPDEF1.OPERATE

Low(1) stage operate

10=Low(1) stage operate

163

90

1

2

0

1

LD0.DEFLPTOC2.Op.general

DEFLPDEF2.OPERATE

Low(2) stage operate

10=Low(2) stage operate

163

91

1

2

0

1

LD0.DEFLPTOC2.Str.general

DEFLPDEF2.START

Low(2) stage start

10=Low(2) stage start

163

94

1

2

1

1

LD0.DEFHPTOC1.Str.general

DEFHPDEF1.START

High stage start

10=High stage start

163

96

1

2

1

1

LD0.DEFHPTOC1.Op.general

DEFHPDEF1.OPERATE

High stage operate

10=High stage operate

163

98

1

2

0

1

Three-phase inrush detection, all variants

LD0.INRPHAR1.Str.phsA

-

Start[.phsA]

10=Start phsA

167

64

0

2

1

1

LD0.INRPHAR1.Str.phsB

-

Start[.phsB]

10=Start phsB

167

65

0

2

1

1

LD0.INRPHAR1.Str.phsC

-

Start[.phsC]

10=Start phsC

167

66

0

2

1

1

LD0.INRPHAR1.Str.general

-

Start[.general]

10=Start general

167

84

1

2

1

1

Thermal overload protection, all variants

LD0.T1PTTR1.Str.general

T1PTTR1.START

Start

10=Start

168

84

1

2

1

1

LD0.T1PTTR1.AlmThm.general

T1PTTR1.ALARM

Thermal alarm

10=Thermal alarm

168

85

1

2

1

1

LD0.T1PTTR1.Op.general

T1PTTR1.OPERATE

Operate

10=Operate

168

90

1

2

0

1

Auto-reclosing, optional in all variants

LD0.DARREC1.RsRec.ctlVal

-

AR reset

10=Reset

169

19

1

20

0

1

LD0.DARREC1.RsCnt.ctlVal

-

AR counters reset

10=Reset

169

20

1

20

0

1

LD0.DARREC1.PrgRec1.stVal

DARREC1.INPRO_1

AR in progress 1st reclose

10=In progress

169

101

1

2

0

1

LD0.DARREC1.PrgRec2.stVal

DARREC1.INPRO_2

AR in progress 2nd reclose

10=In progress

169

102

1

2

0

1

LD0.DARREC1.PrgRec3.stVal

DARREC1.INPRO_3

AR in progress 3rd reclose

10=In progress

169

103

1

2

0

1

LD0.DARREC1.PrgRec4.stVal

DARREC1.INPRO_4

AR in progress 4th reclose

10=In progress

169

104

1

2

0

1

LD0.DARREC1.PrgRec5.stVal

DARREC1.INPRO_5

AR in progress 5th reclose

10=In progress

169

105

1

2

0

1

LD0.DARREC1.PrgRec.stVal

DARREC1.INPRO

AR in progress

10=In progress

169

120

1

2

0

1

LD0.DARREC1.CBManCls.stVal

DARREC1.MAN_CB_CL

CB manually closed

10=CB manually closed

169

159

1

2

0

1

LD0.DARREC1.LO.stVal

DARREC1.LOCKED

Lockout status

10=Lockout

169

164

1

2

0

1

LD0.DARREC1.UnsRec.stVal

DARREC1.UNSUC_RECL

Unsuccessful reclose status

10=Unsuccessful reclose

169

170

1

2

0

1

LD0.DARREC1.InBlkThm.stVal

-

Thermal block (status)

10=Thermal block

169

171

1

2

0

1

LD0.DARREC1.RdyRec.stVal

DARREC1.READY

Ready reclose status

10=Reclose ready

169

172

1

2

0

1

LD0.DARREC1.ActRec.stVal

DARREC1.ACTIVE

Active reclose status

10=Reclose active

169

173

1

2

0

1

LD0.DARREC1.PrgDsr.stVal

DARREC1.DISCR_INPRO

Discrimination time in progress

10=Discrimination time in progress

169

174

1

2

0

1

LD0.DARREC1.PrgCutOut.stVal

DARREC1.CUTOUT_INPR O

Cutout time in progress

10=Cutout time in progress

169

175

1

2

0

1

LD0.DARREC1.FrqOpAlm.stVal

DARREC1.FRQ_OP_ALM

Frequent operation counter alarm

10=Frequent operation alarm

169

176

1

2

0

1

LD0.DARREC1.RclTmStr.stVal

-

Reclaim time started

10=Reclaim time started

169

177

1

2

0

1

LD0.DARREC1.ProCrd.stVal

-

Protection coordination

10=Protection coordination

169

178

1

2

0

1

LD0.DARREC1.Op.general

DARREC1.CLOSE_CB

Operate (close command to XCBR)

10=Close command to CB

169

179

1

2

0

1

Table continues on next page

Section 2

1MRS756712 C

IEC 60870-5-103 data mappings

20

REF615

Point List Manual

Summary of Contents for Relion 615 series

Page 1: ...Relion 615 series Feeder Protection and Control REF615 IEC 60870 5 103 Point List Manual...

Page 2: ......

Page 3: ...Document ID 1MRS756712 Issued 2010 06 11 Revision C Product version 3 0 Copyright 2010 ABB All rights reserved...

Page 4: ...copied or disclosed only in accordance with the terms of such license Trademarks ABB and Relion are registered trademarks of ABB Group All other brand or product names mentioned in this document may...

Page 5: ...roduct failure would create a risk for harm to property or persons including but not limited to personal injuries or death shall be the sole responsibility of the person or entity applying the equipme...

Page 6: ...cerning electrical equipment for use within specified voltage limits Low voltage directive 2006 95 EC This conformity is the result of tests conducted by ABB in accordance with the product standards E...

Page 7: ...n speed 25 Link layer 25 Application layer 26 Transmission mode for application data 26 COMMON ADDRESS of ASDU 26 Selection of standard information numbers in monitor direction 26 System functions in...

Page 8: ...Basic application functions 30 Miscellaneous 30 Section 4 Glossary 31 Table of contents 2 REF615 Point List Manual...

Page 9: ...audience This manual addresses the communication system engineer or system integrator responsible for pre engineering and engineering for communication setup in a substation from an IED perspective T...

Page 10: ...C07000220 V1 EN Figure 1 The intended use of manuals in different lifecycles The engineering manual contains instructions on how to engineer the IEDs using the different tools in PCM600 The manual pro...

Page 11: ...manual can also be used when calculating settings The technical manual contains application and functionality descriptions and lists function blocks logic diagrams input and output signals setting pa...

Page 12: ...n degraded process performance leading to personal injury or death Therefore comply fully with all warning and caution notices 1 4 2 Manual conventions Conventions used in IED manuals A particular con...

Page 13: ...se directional overcurrent protection low stage instance 2 DPHLPDOC2 3I 2 67 1 2 Three phase directional overcurrent protection high stage DPHHPDOC1 3I 67 2 Non directional earth fault protection low...

Page 14: ...ase overvoltage protection instance 2 PHPTOV2 3U 2 59 2 Three phase overvoltage protection instance 3 PHPTOV3 3U 3 59 3 Positive sequence undervoltage protection instance 1 PSPTUV1 U1 1 47U 1 Negative...

Page 15: ...SCBR1 TCS 1 TCM 1 Trip circuit supervision instance 2 TCSSCBR2 TCS 2 TCM 2 Current circuit supervision CCRDIF1 MCS 3I MCS 3I Fuse failure supervision SEQRFUF1 FUSEF 60 Measurement Disturbance recorder...

Page 16: ...10...

Page 17: ...FUN value as default INF Default Information Number definition for the point The user definable Information Number definition is set to the same INF value as default InUse 1 means that the point is ta...

Page 18: ...s if the value is present in Class2 frame 6 Frame No7 Shows if the value is present in Class2 frame 7 Comment Additional information Section 2 1MRS756712 C IEC 60870 5 103 data mappings 12 REF615 Poin...

Page 19: ...2 2 Point list for REF615 Ver 3 0 FE01 08 1MRS756712 C Section 2 IEC 60870 5 103 data mappings REF615 13 Point List Manual...

Page 20: ...signal 10 Input signal ON 10 1 1 2 0 1 LD0 TRPPTRC1 Tr general TRPTRC1 trip output signal 10 Trip output signal ON 10 2 1 2 0 1 LD0 TRPPTRC2 Op general TRPTRC2 input signal 10 Input signal ON 10 3 1...

Page 21: ...2 0 1 Admittance based earhtfault protection 3 stages FE01 02 05 06 07 LD0 EFPADM1 Str general EFPADM1 START Stage1 start 10 Stage 1 start 25 84 1 2 1 1 LD0 EFPADM1 Op general EFPADM1 OPERATE Stage1 o...

Page 22: ...art general 10 Low 1 stage start 32 84 1 2 1 1 LD0 DPHLPTOC1 Op general DPHLPDOC1 OPERATE Low 1 stage Operate general 10 Low 1 stage operate 32 90 1 2 0 1 LD0 DPHLPTOC2 Op general DPHLPDOC2 OPERATE Lo...

Page 23: ...e 3 operate 41 98 1 2 0 1 Positive sequence undervoltage protection 1 stage FE06 07 LD0 PSPTUV1 Str phsA Start phsA 10 phsA start 42 64 0 2 1 1 LD0 PSPTUV1 Str phsB Start phsB 10 phsB start 42 65 0 2...

Page 24: ...XGGIO110 SPCSO1 stVal X110 Output 1 10 ON 01 OFF 52 101 0 1 1 1 LD0 XGGIO110 SPCSO2 stVal X110 Output 2 10 ON 01 OFF 52 102 0 1 1 1 LD0 XGGIO110 SPCSO3 stVal X110 Output 3 10 ON 01 OFF 52 103 0 1 1 1...

Page 25: ...Inst stage phsA start 162 34 0 2 1 1 LD0 PHIPTOC1 Str phsB Instanteous stage Start phsB 10 Inst stage phsB start 162 35 0 2 1 1 LD0 PHIPTOC1 Str phsC Instanteous stage Start phsC 10 Inst stage phsC s...

Page 26: ...Val DARREC1 INPRO_2 AR in progress 2nd reclose 10 In progress 169 102 1 2 0 1 LD0 DARREC1 PrgRec3 stVal DARREC1 INPRO_3 AR in progress 3rd reclose 10 In progress 169 103 1 2 0 1 LD0 DARREC1 PrgRec4 st...

Page 27: ...High alarm 10 High alarm 211 11 0 1 1 1 LD0 RESVMMXU1 HiWrn stVal RESVMMXU1 HIGH_WAR N High warning 10 High warning 211 12 0 1 1 1 Circuit breaker position and failure protection all variants CTRL CB...

Page 28: ...FE02 04 05 06 07 CTRL DCSXSWI1 Pos stVal DCSXSWI1 POSITION Disconnector 1 position 10 Close 01 Open 00 Intermediate 11 Error 253 1 1 1 1 2 CTRL DCSXSWI2 Pos stVal DCSXSWI2 POSITION Disconnector 2 pos...

Page 29: ...LD0 RESVMMXU1 PhV res instCVal mag Residual voltage 2 4 x x n a in FE03 04 6 LD0 CSMSQI1 SeqA c1 instCVal mag Positive sequence current 2 4 x x 7 LD0 CSMSQI1 SeqA c2 instCVal mag Negative sequence cu...

Page 30: ...se to ground voltage phase B 2 4 x x 12 LD0 VMMXU1 phV phsC cVal mag Phase to ground voltage phase C 2 4 x x 13 LD0 VMMXU1 PPV phsAB cVal mag Phase to phase voltage phase AB 2 4 x x 14 LD0 VMMXU1 PPV...

Page 31: ...hat 32 of them can be operated on one line For detailed information refer to clause 3 of EIA RS 485 standard 3 1 2 Optical interface Glass fibre Plastic fibre F SMA type connector BFOC 2 5 type connec...

Page 32: ...System functions in monitor directions INF Semantics 0 End of general interrogation 0 Time synchronization 2 Reset FCB 3 Reset CU 4 Start restart 5 Power on 3 3 3 2 Status indications in monitor direc...

Page 33: ...3 and 38 IED current and voltage measurement supervision signals and alarms are found in private data definitions Semantics of these signals are more complex in 615 series than what is defined by the...

Page 34: ...90 Trip I 91 Trip I 92 Trip IN 93 Trip IN Note Function specific fault signals are as default mapped to private data locations in 615 series IEDs 3 3 3 6 Auto reclosure indications in monitor directi...

Page 35: ...th execution 251 Write entry aborted 3 3 4 Selection of standard information numbers in control direction 3 3 4 1 System functions in control direction INF Semantics 0 Initiation of general interrogat...

Page 36: ...reprogram the MVAL for each separate measurand Measurand Max MVAL rated value times 1 2 or 2 4 Current L1 Current L2 Current L3 Voltage L1 E Voltage L2 E Voltage L3 E Active power P Reactive power Q...

Page 37: ...utput IEC International Electrotechnical Commission IEC 60870 5 103 Communication standard for protective equipment A serial master slave protocol for point to point communication IEC 61850 Internatio...

Page 38: ...32...

Page 39: ...33...

Page 40: ...Contact us ABB Oy Distribution Automation P O Box 699 FI 65101 VAASA Finland Phone 358 10 22 11 Fax 358 10 22 41094 www abb com substationautomation 1MRS756712 C Copyright 2010 ABB All rights reserved...

Reviews: