IEC 61850 name
AFL-Common SA name
Description
DPI value
FUN
INF
In Use
ASDU
GI
Coding
LD0.FRPTUF2.Op.general
FRPFRQ2.OPR_UFRQ
Operate 2 signal for underfrequency
1 = Stage2 underfrequency operate
27
23
1
2
0
1
LD0.FRPFRC2.Op.general
FRPFRQ2.OPR_FRG
Operate 2 signal for frequency gradient
1
=
Stage2
frequency
gradient
operate
27
24
1
2
0
1
LD0.FRPTRC3.Str.general
FRPFRQ3.START
Stage 3 start
1 = Stage3 start
27
31
1
2
1
1
LD0.FRPTOF3.Op.general
FRPFRQ2.OPR_OFRQ
Operate
3
signal
for
overfrequency
1 = Stage3 overfrequency operate
27
32
1
2
0
1
LD0.FRPTUF3.Op.general
FRPFRQ3.OPR_UFRQ
Operate 3 signal for underfrequency
1 = Stage3 underfrequency operate
27
33
1
2
0
1
LD0.FRPFRC3.Op.general
FRPFRQ3.OPR_FRG
Operate 3 signal for frequency gradient
1
=
Stage3
frequency
gradient
operate
27
34
1
2
0
1
Three-phase directional overcurrent protection (3 stages), FE06,07
LD0.DPHHPTOC1.Str.phsA
-
High stage Start[.phsA]
10=High stage phsA start
32
44
0
2
1
1
LD0.DPHHPTOC1.Str.phsB
-
High stage Start[.phsB]
10=High stage phsB start
32
45
0
2
1
1
LD0.DPHHPTOC1.Str.phsC
-
High stage Start[.phsC]
10=High stage phsC start
32
46
0
2
1
1
LD0.DPHLPTOC2.Str.phsA
-
Low(2) stage Start[.phsA]
10=Low(2) stage phsA start
32
54
0
2
1
1
LD0.DPHLPTOC2.Str.phsB
-
Low(2) stage Start[.phsB]
10=Low(2) stage phsB start
32
55
0
2
1
1
LD0.DPHLPTOC2.Str.phsC
-
Low(2) stage Start[.phsC]
10=Low(2) stage phsC start
32
56
0
2
1
1
LD0.DPHLPTOC1.Str.phsA
-
Low(1) stage Start[.phsA]
10=Low(1) stage phsA start
32
64
0
2
1
1
LD0.DPHLPTOC1.Str.phsB
-
Low(1) stage Start[.phsB]
10=Low(1) stage phsB start
32
65
0
2
1
1
LD0.DPHLPTOC1.Str.phsC
-
Low(1) stage Start[.phsC]
10=Low(1) stage phsC start
32
66
0
2
1
1
LD0.DPHLPTOC1.Str.general
DPHLPDOC1.START
Low(1) stage Start[.general]
10=Low(1) stage start
32
84
1
2
1
1
LD0.DPHLPTOC1.Op.general
DPHLPDOC1.OPERATE
Low(1) stage Operate[.general]
10=Low(1) stage operate
32
90
1
2
0
1
LD0.DPHLPTOC2.Op.general
DPHLPDOC2.OPERATE
Low(2) stage Operate[.general]
10=Low(2) stage operate
32
91
1
2
0
1
LD0.DPHLPTOC2.Str.general
DPHLPDOC2.START
Low(2) stage Start[.general]
10=Low(2) stage start
32
94
1
2
1
1
LD0.DPHHPTOC1.Str.general
DPHHPDOC1.START
High stage Start[.general]
10=High stage start
32
96
1
2
1
1
LD0.DPHHPTOC1.Op.general
DPHHPDOC1.OPERATE
High stage Operate[.general]
10=High stage operate
32
98
1
2
0
1
Phase overvoltage protection (3 stages), FE06,07
LD0.PHPTOV3.Str.phsA
-
Stage 3 Start[.phsA]
10=Stage 3 phsA start
40
44
0
2
1
1
LD0.PHPTOV3.Str.phsB
-
Stage 3 Start[.phsB]
10=Stage 3 phsB start
40
45
0
2
1
1
LD0.PHPTOV3.Str.phsC
-
Stage 3 Start[.phsC]
10=Stage 3 phsC start
40
46
0
2
1
1
LD0.PHPTOV2.Str.phsA
-
Stage 2 Start[.phsA]
10=Stage 2 phsA start
40
54
0
2
1
1
LD0.PHPTOV2.Str.phsB
-
Stage 2 Start[.phsB]
10=Stage 2 phsB start
40
55
0
2
1
1
LD0.PHPTOV2.Str.phsC
-
Stage 2 Start[.phsC]
10=Stage 2 phsC start
40
56
0
2
1
1
LD0.PHPTOV1.Str.phsA
-
Stage 1 Start[.phsA]
10=Stage 1 phsA start
40
64
0
2
1
1
LD0.PHPTOV1.Str.phsB
-
Stage 1 Start[.phsB]
10=Stage 1 phsB start
40
65
0
2
1
1
LD0.PHPTOV1.Str.phsC
-
Stage 1 Start[.phsC]
10=Stage 1 phsC start
40
66
0
2
1
1
LD0.PHPTOV1.Str.general
PHPTOV1.START
Stage 1 Start[.general]
10=Stage 1 start
40
84
1
2
1
1
LD0.PHPTOV1.Op.general
PHPTOV1.OPERATE
Stage 1 Operate[.general]
10=Stage 1 operate
40
90
1
2
0
1
LD0.PHPTOV2.Op.general
PHPTOV2.OPERATE
Stage 2 Operate[.general]
10=Stage 2 operate
40
91
1
2
0
1
LD0.PHPTOV2.Str.general
PHPTOV2.START
Stage 2 Start[.general]
10=Stage 2 start
40
94
1
2
1
1
LD0.PHPTOV3.Str.general
PHPTOV3.START
Stage 3 Start[.general]
10=Stage 3 start
40
96
1
2
1
1
Table continues on next page