![ABB Relion 615 series List Manual Download Page 24](http://html1.mh-extra.com/html/abb/relion-615-series/relion-615-series_list-manual_3383777024.webp)
IEC 61850 name
AFL-Common SA name
Description
DPI value
FUN
INF
In Use
ASDU
GI
Coding
LD0.XGGIO130.Ind3.stVal
-
X130-Input 3
10=ON, 01=OFF
50
3
0
1
1
1
LD0.XGGIO130.Ind4.stVal
-
X130-Input 4
10=ON, 01=OFF
50
4
0
1
1
1
LD0.XGGIO130.Ind5.stVal
-
X130-Input 5
10=ON, 01=OFF
50
5
0
1
1
1
LD0.XGGIO130.Ind6.stVal
-
X130-Input 6
10=ON, 01=OFF
50
6
0
1
1
1
LD0.XGGIO130.SPCSO1.stVal
-
X130-Output 1
10=ON, 01=OFF
50
101
0
1
1
1
LD0.XGGIO130.SPCSO2.stVal
-
X130-Output 2
10=ON, 01=OFF
50
102
0
1
1
1
LD0.XGGIO130.SPCSO3.stVal
-
X130-Output 3
10=ON, 01=OFF
50
103
0
1
1
1
LD0.XGGIO120.Ind1.stVal
-
X120-Input 1
10=ON, 01=OFF
51
1
0
1
1
1
LD0.XGGIO120.Ind2.stVal
-
X120-Input 2
10=ON, 01=OFF
51
2
0
1
1
1
LD0.XGGIO120.Ind3.stVal
-
X120-Input 3
10=ON, 01=OFF
51
3
0
1
1
1
LD0.XGGIO120.Ind4.stVal
-
X120-Input 4
10=ON, 01=OFF
51
4
0
1
1
1
LD0.XGGIO110.Ind1.stVal
-
X110-Input 1
10=ON, 01=OFF
52
1
0
1
1
1
LD0.XGGIO110.Ind2.stVal
-
X110-Input 2
10=ON, 01=OFF
52
2
0
1
1
1
LD0.XGGIO110.Ind3.stVal
-
X110-Input 3
10=ON, 01=OFF
52
3
0
1
1
1
LD0.XGGIO110.Ind4.stVal
-
X110-Input 4
10=ON, 01=OFF
52
4
0
1
1
1
LD0.XGGIO110.Ind5.stVal
-
X110-Input 5
10=ON, 01=OFF
52
5
0
1
1
1
LD0.XGGIO110.Ind6.stVal
-
X110-Input 6
10=ON, 01=OFF
52
6
0
1
1
1
LD0.XGGIO110.Ind7.stVal
-
X110-Input 7
10=ON, 01=OFF
52
7
0
1
1
1
LD0.XGGIO110.Ind8.stVal
-
X110-Input 8
10=ON, 01=OFF
52
8
0
1
1
1
LD0.XGGIO110.SPCSO1.stVal
-
X110-Output 1
10=ON, 01=OFF
52
101
0
1
1
1
LD0.XGGIO110.SPCSO2.stVal
-
X110-Output 2
10=ON, 01=OFF
52
102
0
1
1
1
LD0.XGGIO110.SPCSO3.stVal
-
X110-Output 3
10=ON, 01=OFF
52
103
0
1
1
1
LD0.XGGIO110.SPCSO4.stVal
-
X110-Output 4
10=ON, 01=OFF
52
104
0
1
1
1
LD0.XGGIO100.SPCSO1.stVal
-
X100-Output 1
10=ON, 01=OFF
53
101
0
1
1
1
LD0.XGGIO100.SPCSO2.stVal
-
X100-Output 2
10=ON, 01=OFF
53
102
0
1
1
1
LD0.XGGIO100.SPCSO3.stVal
-
X100-Output 3
10=ON, 01=OFF
53
103
0
1
1
1
LD0.XGGIO100.SPCSO4.stVal
-
X100-Output 4
10=ON, 01=OFF
53
104
0
1
1
1
LD0.XGGIO100.SPCSO5.stVal
-
X100-Output 5
10=ON, 01=OFF
53
105
0
1
1
1
LD0.XGGIO100.SPCSO6.stVal
-
X100-Output 6
10=ON, 01=OFF
53
106
0
1
1
1
LD0.XAGGIO130.Ind1.stVal
-
XA130-Input 1
10=ON, 01=OFF
54
1
0
1
1
1
LD0.XAGGIO130.Ind2.stVal
-
XA130-Input 2
10=ON, 01=OFF
54
2
0
1
1
1
LD0.XAGGIO130.Ind3.stVal
-
XA130-Input 3
10=ON, 01=OFF
54
3
0
1
1
1
LD0.XAGGIO130.Ind4.stVal
-
XA130-Input 4
10=ON, 01=OFF
54
4
0
1
1
1
Arc protection (3 stages), optional in all variants
LD0.ARCSARC11.FADet.stVal
ARCSARC1.ARC_FLT_DE T
Stage1 Fault arc detected
10=Stage1 arc detected
156
211
1
1
0
1
LD0.ARCPTRC11.Op.general
ARCSARC1.OPERATE
Stage1 Operate
10=Stage1 operate
156
213
1
2
0
1
LD0.ARCSARC21.FADet.stVal
ARCSARC2.ARC_FLT_DE T
Stage2 Fault arc detected
10=Stage2 arc detected
156
221
1
1
0
1
LD0.ARCPTRC21.Op.general
ARCSARC2.OPERATE
Stage2 Operate
10=Stage2 operate
156
223
1
2
0
1
Table continues on next page
Section 2
1MRS756712 C
IEC 60870-5-103 data mappings
18
REF615
Point List Manual
Summary of Contents for Relion 615 series
Page 1: ...Relion 615 series Feeder Protection and Control REF615 IEC 60870 5 103 Point List Manual...
Page 2: ......
Page 16: ...10...
Page 38: ...32...
Page 39: ...33...