IEC 61850 name
AFL-Common SA name
Description
DPI value
FUN
INF
In Use
ASDU
GI
Coding
LD0.ARCSARC31.FADet.stVal
ARCSARC3.ARC_FLT_DE T
Stage3 Fault arc detected
10=Stage3 arc detected
156
231
1
1
0
1
LD0.ARCPTRC31.Op.general
ARCSARC3.OPERATE
Stage3 Operate
10=Stage3 operate
156
233
1
2
0
1
Phase discontinuity protection (1 stage), all variants
LD0.PDNSPTOC1.Str.general
PDNSPTOC1.START
Start
10=Stage start
157
84
1
2
1
1
LD0.PDNSPTOC1.Op.general
PDNSPTOC1.OPERATE
Operate
10=Stage operate
157
90
1
2
0
1
Transient/intermittent earth-fault protection (1 stage), FE01,02,05,06
LD0.INTRPTEF1.Str.general
INTRPTEF1.START
Start
10=Stage start
158
84
1
2
1
1
LD0.INTRPTEF1.Op.general
INTRPTEF1.OPERATE
Operate
10=Stage operate
158
90
1
2
0
1
Non-directional earth-fault and sensitive earth-fault protection (4 stages), partly supported in all variants, full support in FE03,04
LD0.EFLPTOC1.Str.general
EFLPTOC1.START
Low(1) stage start
10=Low(1) stage start
159
84
1
2
1
1
LD0.EFLPTOC1.Op.general
EFLPTOC1.OPERATE
Low(1) stage operate
10=Low(1) stage operate
159
90
1
2
0
1
LD0.EFLPTOC2.Op.general
EFLPTOC2.OPERATE
Low(2) stage operate
10=Low(2) stage operate
159
91
1
2
0
1
LD0.EFLPTOC2.Str.general
EFLPTOC2.START
Low(2) stage start
10=Low(2) stage start
159
94
1
2
1
1
LD0.EFHPTOC1.Str.general
EFHPTOC1.START
High stage start
10=High stage start
159
96
1
2
1
1
LD0.EFIPTOC1.Str.general
EFIPTOC1.START
Instanteous stage start
10=Instanteous stage start
159
97
1
2
1
1
LD0.EFHPTOC1.Op.general
EFHPTOC1.OPERATE
High stage operate
10=High stage operate
159
98
1
2
0
1
LD0.EFIPTOC1.Op.general
EFIPTOC1.OPERATE
Instanteous stage operate
10=Instanteous stage operate
159
99
1
2
0
1
Phase overcurrent protection (4 stages), FE01,02,03,04,05
LD0.PHIPTOC1.Str.phsA
-
Instanteous stage Start[.phsA]
10=Inst. stage phsA start
162
34
0
2
1
1
LD0.PHIPTOC1.Str.phsB
-
Instanteous stage Start[.phsB]
10=Inst. stage phsB start
162
35
0
2
1
1
LD0.PHIPTOC1.Str.phsC
-
Instanteous stage Start[.phsC]
10=Inst. stage phsC start
162
36
0
2
1
1
LD0.PHHPTOC2.Str.phsA
-
High(2) stage Start[.phsA]
10=High(2) stage phsA start
162
44
0
2
1
1
LD0.PHHPTOC2.Str.phsB
-
High(2) stage Start[.phsB]
10=High(2) stage phsB start
162
45
0
2
1
1
LD0.PHHPTOC2.Str.phsC
-
High(2) stage Start[.phsC]
10=High(2) stage phsC start
162
46
0
2
1
1
LD0.PHHPTOC1.Str.phsA
-
High(1) stage Start[.phsA]
10=High(1) stage phsA start
162
54
0
2
1
1
LD0.PHHPTOC1.Str.phsB
-
High(1) stage Start[.phsB]
10=High(1) stage phsB start
162
55
0
2
1
1
LD0.PHHPTOC1.Str.phsC
-
High(1) stage Start[.phsC]
10=High(1) stage phsC start
162
56
0
2
1
1
LD0.PHLPTOC1.Str.phsA
-
Low stage Start[.phsA]
10=Low stage phsA start
162
64
0
2
1
1
LD0.PHLPTOC1.Str.phsB
-
Low stage Start[.phsB]
10=Low stage phsB start
162
65
0
2
1
1
LD0.PHLPTOC1.Str.phsC
-
Low stage Start[.phsC]
10=Low stage phsC start
162
66
0
2
1
1
LD0.PHLPTOC1.Str.general
PHLPTOC1.START
Low stage Start[.general]
10=Low stage start
162
84
1
2
1
1
LD0.PHLPTOC1.Op.general
PHLPTOC1.OPERATE
Low stage Operate[.general]
10=Low stage operate
162
90
1
2
0
1
LD0.PHHPTOC1.Op.general
PHHPTOC1.OPERATE
High(1) stage Operate[.general]
10=High(1) stage operate
162
91
1
2
0
1
LD0.PHHPTOC1.Str.general
PHHPTOC1.START
High(1) stage Start[.general]
10=High(1) stage start
162
94
1
2
1
1
LD0.PHHPTOC2.Str.general
PHHPTOC2.START
High(2) stage Start[.general]
10=High(2) stage start
162
96
1
2
1
1
LD0.PHIPTOC1.Str.general
PHIPTOC1.START
Instanteous stage Start[.general]
10=Instanteous stage start
162
97
1
2
1
1
LD0.PHHPTOC2.Op.general
PHHPTOC2.OPERATE
High(2) stage Operate[.general]
10=High(2) stage operate
162
98
1
2
0
1
LD0.PHIPTOC1.Op.general
PHIPTOC1.OPERATE
Instanteous stage Operate[.general]
10=Instanteous stage operate
162
99
1
2
0
1
Table continues on next page
1MRS756712 C
Section 2
IEC 60870-5-103 data mappings
REF615
19
Point List Manual
Summary of Contents for Relion 615 series
Page 1: ...Relion 615 series Feeder Protection and Control REF615 IEC 60870 5 103 Point List Manual...
Page 2: ......
Page 16: ...10...
Page 38: ...32...
Page 39: ...33...