![background image](http://html1.mh-extra.com/html/abb/relion-615-series/relion-615-series_manual_3363482034.webp)
Parameter
Values (Range)
Unit
Step
Default
Description
Frame3InUse 1
-1=Not in use
0=User frame
1=Standard frame 1
2=Standard frame 2
3=Standard frame 3
4=Standard frame 4
5=Standard frame 5
6=Private frame 6
7=Private frame 7
-1=Not in use
Active Class2 Frame 3 for instance 1
Frame4InUse 1
-1=Not in use
0=User frame
1=Standard frame 1
2=Standard frame 2
3=Standard frame 3
4=Standard frame 4
5=Standard frame 5
6=Private frame 6
7=Private frame 7
-1=Not in use
Active Class2 Frame 4 for instance 1
Class1OvInd 1
0=No indication
1=Both edges
2=Rising edge
2=Rising edge
Overflow Indication for instance 1
Class1OvFType 1
0...255
10
Function Type for Class 1 overflow
indication for instance 1
Class1OvInfNo 1
0...255
255
Information Number for Class 1
overflow indication for instance 1
Class1OvBackOff 1
0...500
500
Backoff Range for Class1 buffer for
instance 1
GI Optimize 1
0=Standard
behaviour
1=Skip spontaneous
2=Only overflown
3=Combined
0=Standard
behaviour
Optimize GI traffic for instance 1
DR Notification 1
0=Disabled
1=Enabled
0=Disabled
Disturbance Recorder spontaneous
indications enabled/disabled
Serial port 2
0=Not in use
1=COM 1
2=COM 2
0=Not in use
COM port for instance 2
Address 2
1...255
1
Unit address for instance 2
Start delay 2
0...20
char
4
Start frame delay in chars for instance 2
End delay 2
0...20
char
4
End frame delay in chars for instance 2
DevFunType 2
0...255
9
Device Function Type for instance 2
UsrFType 2
0...255
10
Function type for User Class 2 Frame
for instance 2
UsrInfNo 2
0...255
230
Information Number for User Class2
Frame for instance 2
Class1Priority 2
0=Ev High
1=Ev/DR Equal
2=DR High
0=Ev High
Class 1 data sending priority
relationship between Events and
Disturbance Recorder data.
Table continues on next page
Section 4
1MRS756710 C
IEC 60870-5-103 parameters and diagnostics
28
615 series
Communication Protocol Manual
Summary of Contents for Relion 615 series
Page 1: ...Relion Protection and Control 615 series IEC 60870 5 103 Communication Protocol Manual...
Page 2: ......
Page 14: ...8...
Page 32: ...26...
Page 39: ...33...