Section 4
IEC 60870-5-103 parameters and
diagnostics
4.1
Parameter list
The IEC 60870-5-103 parameters can be accessed with PCM600 or via the LHMI
path
Configuration/Communication/IEC 60870-5-103
.
Table 10:
IEC 60870-5-103 settings
Parameter
Values (Range)
Unit
Step
Default
Description
Serial port 1
0=Not in use
1=COM 1
2=COM 2
0=Not in use
COM port for instance 1
Address 1
1...255
1
Unit address for instance 1
Start delay 1
0...20
char
4
Start frame delay in chars for instance 1
End delay 1
0...20
char
4
End frame delay in chars for instance 1
DevFunType 1
0...255
9
Device Function Type for instance 1
UsrFType 1
0...255
10
Function type for User Class 2 Frame
for instance 1
UsrInfNo 1
0...255
230
Information Number for User Class2
Frame for instance 1
Class1Priority 1
0=Ev High
1=Ev/DR Equal
2=DR High
0=Ev High
Class 1 data sending priority
relationship between Events and
Disturbance Recorder data.
Frame1InUse 1
-1=Not in use
0=User frame
1=Standard frame 1
2=Standard frame 2
3=Standard frame 3
4=Standard frame 4
5=Standard frame 5
6=Private frame 6
7=Private frame 7
6=Private frame 6
Active Class2 Frame 1 for instance 1
Frame2InUse 1
-1=Not in use
0=User frame
1=Standard frame 1
2=Standard frame 2
3=Standard frame 3
4=Standard frame 4
5=Standard frame 5
6=Private frame 6
7=Private frame 7
-1=Not in use
Active Class2 Frame 2 for instance 1
Table continues on next page
1MRS756710 C
Section 4
IEC 60870-5-103 parameters and diagnostics
615 series
27
Communication Protocol Manual