Replacing a SPA 300 series relay by a 615 series IED
1.
Make a new panel cut-out to the existing mounting panel according to the
dimensional drawing.
B
A
E
D
C
GUID-F20D587E-5E99-4593-B9EE-A1B125A95524 V1 EN
Figure 36:
New panel cut-out and screw hole dimensions for replacing a
SPA 300 series relay
A Min. 186 mm
B 161.5 ± 1 mm
C 224 mm
D 176 mm
E 7 mm
2.
Drill new screw holes (
∅
4.5 mm) to the panel according to the dimensional
drawing.
3.
Mount the installation plate to the panel cut-out with M5 thread forming screws.