Figure 13:
IED semi-flush mounted inclined
A 25 °
1 M4 screws
B 221 mm 2 Gasket
C 9 mm
4 Case
D 107 mm 3 Angled frame
E 133 mm 5 Plug-in unit
F 230 mm
G 190 mm
4.3.5
Rack mounting the IED
A mounting kit is needed for rack mounting the IED. In addition to the detailed
mounting instructions, the 19" rack mounting kit includes:
•
Mounting panel; the type of the mounting panel depends on the number of
mounted relays
•
Screws
1.
Mount the mounting panel to a 19" rack.
2.
Loosen the four M5 fixing screws in the case to fit the case into the panel cut-
out.
3.
Mount the case to the panel cut-out.
1MRS756375 K
Section 4
Mounting
615 series
27
Installation Manual