background image

Relion

®

 Protection and Control

615 series

Installation Manual

Summary of Contents for Relion 615 series

Page 1: ...Relion Protection and Control 615 series Installation Manual ...

Page 2: ......

Page 3: ...Document ID 1MRS756375 Issued 2012 05 11 Revision K Product version 4 0 Copyright 2012 ABB All rights reserved ...

Page 4: ...is document is furnished under a license and may be used copied or disclosed only in accordance with the terms of such license Trademarks ABB and Relion are registered trademarks of the ABB Group All other brand or product names mentioned in this document may be trademarks or registered trademarks of their respective holders Warranty Please inquire about the terms of warranty from your nearest ABB...

Page 5: ...product failure would create a risk for harm to property or persons including but not limited to personal injuries or death shall be the sole responsibility of the person or entity applying the equipment and those so responsible are hereby requested to ensure that all measures are taken to exclude or mitigate such risks This document has been carefully checked by ABB but deviations cannot be compl...

Page 6: ...erning electrical equipment for use within specified voltage limits Low voltage directive 2006 95 EC This conformity is the result of tests conducted by ABB in accordance with the product standards EN 50263 and EN 60255 26 for the EMC directive and with the product standards EN 60255 1 and EN 60255 27 for the low voltage directive The product is designed in accordance with the international standa...

Page 7: ...ety regulations must always be followed The frame of the IED has to be carefully earthed When the plug in unit has been detached from the case do not touch the inside of the case The IED case internals may contain high voltage potential and touching these may cause personal injury The IED contains components which are sensitive to electrostatic discharge Unnecessary touching of electronic componen...

Page 8: ......

Page 9: ...duct 11 Checking delivery items 11 Inspecting the IED 11 Returning an IED damaged in transit 12 Storing 12 Section 4 Mounting 13 Checking environmental conditions and mounting space 13 Detaching and installing the plug in unit 13 Detaching the plug in unit 13 Installing the plug in unit 14 Sealing the plug in unit 16 Securing the handle 17 Mounting the IED 18 Required tools 18 Flush mounting the I...

Page 10: ...s IED 50 Section 5 Connecting 51 Required tools 51 Connecting wires 51 Connecting ring lug type wires 52 Connecting protective earthing 52 Connecting analog signals 53 Connecting current and voltage inputs 53 Connecting RTD and mA inputs 58 Connecting IED with a test switch 58 Connecting binary signals 59 Connecting power supply 60 Connecting communication 61 Energizing the IED 61 Section 6 Removi...

Page 11: ...Section 9 Glossary 73 Table of contents 615 series 3 Installation Manual ...

Page 12: ...4 ...

Page 13: ...ual describes a communication protocol supported by the IED The manual concentrates on vendor specific implementations The engineering guide provides information for IEC 61850 engineering of the 615 series protection IEDs with PCM600 and IET600 This guide concentrates especially on the configuration of GOOSE communication with these tools The guide can be used as a technical reference during the e...

Page 14: ...tput signals setting parameters and technical data sorted per function The manual can be used as a technical reference during the engineering phase installation and commissioning phase and during normal service 1 3 2 Document revision history Document revision date Product series version History A 2007 12 20 1 0 First release B 2008 02 08 1 0 Content updated C 2008 07 02 1 1 Content updated to cor...

Page 15: ...o personal injury it is necessary to understand that under certain operational conditions operation of damaged equipment may result in degraded process performance leading to personal injury or death Therefore comply fully with all warning and caution notices 1 4 2 Document conventions A particular convention may not be used in this manual Abbreviations and acronyms in this manual are spelled out ...

Page 16: ...are indicated with quotation marks The corresponding parameter values are On and Off IED input output messages and monitored data names are shown in Courier font When the function starts the START output is set to TRUE Section 1 1MRS756375 K Introduction 8 615 series Installation Manual ...

Page 17: ...ured with extensive testing during the design and manufacturing processes Moreover long life time is supported by maintenance and repair services as well as by the availability of spare parts Design and manufacturing have been done under a certified environmental system The effectiveness of the environmental system is constantly evaluated by an external auditing body We follow environmental rules ...

Page 18: ...parts and screws Steel Plastic parts PC1 LCP2 Electronics plug in module Various Plug in unit Electronics plug in modules Various Electronics LHMI module Various Plastic parts PC PBT3 LCP PA4 Metallic parts Aluminium Package Box Cardboard Attached material Manuals Paper 1 Polycarbonate 2 Liquid crystal polymer 3 Polybutylene terephthalate 4 Polyamide Section 2 1MRS756375 K Environmental aspects 10...

Page 19: ...ective film from top of the IED The cardboard packaging material is 100 recyclable 3 2 Inspecting the product 3 2 1 Identifying the product 1 Locate the IED s order number from the label on top of the plug in unit 2 Compare the IED s order number with the ordering information to verify that the received product is correct 3 2 2 Checking delivery items Check that all items are included in the deliv...

Page 20: ...e actions must be taken against the latest carrier Please inform the nearest ABB office or representative Notify ABB immediately if there are any discrepancies in relation to the delivery documents 3 3 Storing If the IED is stored before installation it must be done in the original transport packaging in a dry and dust free place Observe the environmental requirements stated in the technical manua...

Page 21: ...ear of the IED to allow access to wires and optical fibres and to enable maintenance and future modifications Ensure that flush mounted IEDs can be added and replaced without excessive dismantling 4 2 Detaching and installing the plug in unit 4 2 1 Detaching the plug in unit Before detaching the plug in unit from the case the auxiliary voltage must be disconnected 1 Turn off the power 2 Open the s...

Page 22: ...rminals inside the case after removing the plug in unit Live terminals can be inside the case The signal connectors are left open when the plug in unit is detached 4 2 2 Installing the plug in unit The IED is built or constructed in a way that a plug in unit with voltage or current measuring inputs can only be plugged into a corresponding case This prevents fitting a non suitable plug in unit into...

Page 23: ... with serial number Forcing a non suitable plug in unit into the case can break both the plug in unit and the case and may cause danger 1 Lift the handle to its fully opened position 90 degrees 2 Push the plug in unit into the case as far as it goes 3 Turn down the handle completely to push plug in unit into it s final position in the case 1MRS756375 K Section 4 Mounting 615 series 15 Installation...

Page 24: ...s an integrated sealing screw By default the screw is screwed all the way in and is not used when installing or detaching the plug in unit 1 Open the sealing screw about nine turns 2 Thread a sealing wire through the holes in the sealing screw and the handle Section 4 1MRS756375 K Mounting 16 615 series Installation Manual ...

Page 25: ...w By default the screw is screwed all the way in and not used when installing or detaching the plug in unit Instead of sealing the plug in unit the sealing screw and the spacer supplied with the IED can be used for securing the handle in place 1 Fully open the sealing screw and remove it 2 Re insert the sealing screw with the spacer 1MRS756375 K Section 4 Mounting 615 series 17 Installation Manual...

Page 26: ...spacer 1 Spacer 2 Sealing screw 4 3 Mounting the IED 4 3 1 Required tools T25 Torx screwdriver for mounting the case T20 Torx screwdriver for connecting the protective earthing Only use adjustable torque screwdrivers Section 4 1MRS756375 K Mounting 18 615 series Installation Manual ...

Page 27: ...nel 153 mm An IED equipped with optical connections requires a minimum depth of 180 mm The allowed minimum bending radius has to be checked from the optical cable manufacturer 1 Loosen the four M5 fixing screws in the case to fit the case into the panel cut out 2 Mount the case to the panel cut out 1MRS756375 K Section 4 Mounting 615 series 19 Installation Manual ...

Page 28: ...nting a case into a panel cut out A 165 5 1 mm 1 M5 fixing screws B 161 5 1 mm 3 Tighten the M5 T25 screws The allowed range for the fixing screws tightening torque is 0 7 1 Nm Section 4 1MRS756375 K Mounting 20 615 series Installation Manual ...

Page 29: ...A070582 V4 EN Figure 7 Flush mounted case tightening the M5 fixing screws 4 Install the plug in unit into the case 1MRS756375 K Section 4 Mounting 615 series 21 Installation Manual ...

Page 30: ... 177 mm C 164 mm D 201 mm E 153 mm F 48 mm G 160 mm 4 3 3 Semi flush mounting the IED A mounting kit is needed for semi flush mounting the IED In addition to the detailed mounting instructions the mounting kit includes Section 4 1MRS756375 K Mounting 22 615 series Installation Manual ...

Page 31: ...e used in the installation 1 Mount the raising frame into the panel cut out with four M4 screws A B E C D 1 2 3 A070589 V4 EN Figure 9 Mounting the raising frame A 173 5 0 3 mm 1 Panel B 165 5 1 mm 2 Raising frame C 161 5 1 mm 3 M4 screw D 133 0 3 mm E 5 5 mm 2 Loosen the four M5 fixing screws in the case to fit the case to the raising frame 3 Mount the case to the raising frame 1MRS756375 K Secti...

Page 32: ... 10 Mounting the case 4 Tighten the M5 screws The allowed range for the fixing screws tightening torque is 0 7 1 Nm 5 Install the plug in unit into the case Section 4 1MRS756375 K Mounting 24 615 series Installation Manual ...

Page 33: ...adius from the optical cable manufacturer 4 3 4 Semi flush mounting the IED inclined A mounting kit is needed for semi flush mounting the IED inclined In addition to the detailed mounting instructions the mounting kit includes Angle frame Gasket Screws Requirements for installation 1MRS756375 K Section 4 Mounting 615 series 25 Installation Manual ...

Page 34: ...igure 12 Mounting the angled frame A 177 0 3 mm B 167 1 mm C 203 1 mm D 40 5 mm E 122 mm F 40 5 mm G 5 5 mm H 190 mm 2 Loosen the four M5 fixing screws in the case to fit the case into the angle frame 3 Mount the case to the angle frame With the angled frame the IED can be mounted inclined downward to a 25 angle 4 Tighten the screws The allowed range for the fixing screws tightening torque is 0 7 ...

Page 35: ...s needed for rack mounting the IED In addition to the detailed mounting instructions the 19 rack mounting kit includes Mounting panel the type of the mounting panel depends on the number of mounted relays Screws 1 Mount the mounting panel to a 19 rack 2 Loosen the four M5 fixing screws in the case to fit the case into the panel cut out 3 Mount the case to the panel cut out 1MRS756375 K Section 4 M...

Page 36: ...A B A070580 V3 EN Figure 14 19 rack mounting panels A 482 6 mm 19 B 177 mm 4U 4 Tighten the screws Section 4 1MRS756375 K Mounting 28 615 series Installation Manual ...

Page 37: ...ailed mounting instructions the wall mounting kit includes Wall mounting frame and rail parts Back plate Screws Dimensions for screw holes 1 Drill screw holes according to the dimensional drawing 2 Mount the wall mounting frame and the rails 3 Install the back plate 4 Loosen the four M5 fixing screws in the case to fit the case into the mounting frame 5 Mount the case between the rails 1MRS756375 ...

Page 38: ...593 V4 EN Figure 16 Wall mounting the IED A 430 mm 6 Tighten the screws The allowed range for the fixing screws tightening torque is 0 7 1 Nm Section 4 1MRS756375 K Mounting 30 615 series Installation Manual ...

Page 39: ...its When connecting the wires a wall mounted IED can be pulled out and turned 45 or 90 degrees downwards or upwards To release the IED for pulling it out push the locks beside the mounting frame To rotate the IED loosen the knurled head screws in the rails 1MRS756375 K Section 4 Mounting 615 series 31 Installation Manual ...

Page 40: ...elow the frame for rotating 4 3 7 Rack mounting the IED and test switch RTXP to a 19 equipment frame A mounting kit is needed for rack mounting the IED in a 19 equipment frame In addition to the detailed mounting instructions the mounting kit includes Section 4 1MRS756375 K Mounting 32 615 series Installation Manual ...

Page 41: ...To rack mount the IED into a 19 equipment frame 1 Mount the mounting panel into the 19 rack 2 Loosen the four M5 fixing screws in the case to fit the case into the panel cut out 3 Mount the case to the panel cut out 4 Install the optional metallic frame to mount the RTXP 18 or 24 test switch to the panel A071312 V3 EN Figure 19 Mounting of the metallic frame for an RTXP 18 test switch 1MRS756375 K...

Page 42: ...or the case and optionally with RTXP test switch 1 Install the mounting bracket into the combiflex equipment frame by using tapping screws ST3 5x13 from rear side The type of mounting bracket to be used depends on whether the IED is installed into the frame on its own or with a test switch 2 Loosen the four M5 fixing screws in the case to fit the case into the mounting bracket 3 Mount the case to ...

Page 43: ...to a 19 combiflex equipment frame 1 RHGT 19 4U equipment frame variant C with support frame 2 Tapping screw ST3 5x13 3 Mounting bracket 6 Install the optional RTXP 18 or 24 test switch 1MRS756375 K Section 4 Mounting 615 series 35 Installation Manual ...

Page 44: ...rotection system Arc protection is used to detect arc situations in air insulated metal clad switchgear The arc protection system determines where in the switchgear cubicle the optional lens sensors are installed See the application examples in the application manual for further information on the alternatives 1 Drill a hole Ø 10 mm in the wall of the supervised space Section 4 1MRS756375 K Mounti...

Page 45: ...ens sensor can be fastened with a cable tie To do this secure the cable tie to a suitable point of attachment on the cubicle wall and wrap the cable tie tightly around the sensor A040182 V1 EN Figure 24 Mounting the lens sensor 3 Make sure that the cable tie lies in the groove of the sensor to prevent it from blocking the light 1MRS756375 K Section 4 Mounting 615 series 37 Installation Manual ...

Page 46: ... C D C B A GUID C7CA77AA 74EA 40D2 B98E 84735BCADDA2 V1 EN Figure 25 Screw hole and existing panel cut out dimensions for replacing a SP_J40 series IED A 442 mm B 183 mm C 150 mm D 152 mm E 194 mm 2 Mount the installation plate to the existing panel cut out with M5 thread forming screws Section 4 1MRS756375 K Mounting 38 615 series Installation Manual ...

Page 47: ...ead screw M5x10 3 Tighten the screws 4 Mount the new IED For ordering numbers see the ordering number table 4 3 11 Replacing two Strömberg SP_J3 series relays by a 615 series IED 1 Make a new panel cut out to the existing mounting panel according to the dimensional drawing 1MRS756375 K Section 4 Mounting 615 series 39 Installation Manual ...

Page 48: ...wo SP_J3 series relays A 155 mm 1 New panel cut out line B 15 mm C 196 mm D Min 165 5 mm E Min 161 5 mm 2 Drill new screw holes 4 5 mm to the panel according to the dimensional drawing 3 Mount the installation plate to the panel cut out with M5 thread forming screws Section 4 1MRS756375 K Mounting 40 615 series Installation Manual ...

Page 49: ...10 4 Tighten the screws 5 Mount the new IED For ordering numbers see the ordering number table 4 3 12 Replacing a Strömberg SP_J3 J6 series relay in 19 rack by a 615 series IED 1 Mount the installation plate to the existing panel cut out with M6 screws and nuts Use the existing screw holes 1MRS756375 K Section 4 Mounting 615 series 41 Installation Manual ...

Page 50: ...419F A795 6FD6E2A4CF95 V1 EN Figure 29 Screw hole and existing panel cut out dimensions for replacing a SP_J3 J6 series relay A 446 mm B 196 mm C 460 mm D 114 5 mm Section 4 1MRS756375 K Mounting 42 615 series Installation Manual ...

Page 51: ... Hexagon nut M6 2 Tighten the screws 3 Mount the new IED with the mounting frame to the installation plate For ordering numbers see the ordering number table 4 3 13 Replacing a Strömberg SP_J6 series relay by a 615 series IED 1 Drill new screw holes 4 5 mm to the panel according to the dimensional drawing 1MRS756375 K Section 4 Mounting 615 series 43 Installation Manual ...

Page 52: ...crew hole and existing panel cut out dimensions for a SP_J6 series relay A 186 1 mm B 186 1 mm C 196 mm D 196 mm 2 Mount the installation plate to the existing panel cut out with M5 thread forming screws Section 4 1MRS756375 K Mounting 44 615 series Installation Manual ...

Page 53: ...orx head screw M5x10 3 Tighten the screws 4 Mount the new IED For ordering numbers see the ordering number table 4 3 14 Replacing three BBC S_ series relays by a 615 series IED 1 Make a new panel cut out to the existing mounting panel according to the dimensional drawing 1MRS756375 K Section 4 Mounting 615 series 45 Installation Manual ...

Page 54: ... 5AB1 4859 91D2 CD8C4556BA7F V1 EN Figure 33 Existing panel cut out and screw hole dimensions for three BBC S_ series relays A 92 mm B 234 mm C 100 mm D 250 mm Section 4 1MRS756375 K Mounting 46 615 series Installation Manual ...

Page 55: ...34 New panel cut out for replacing BBC S_ series relays 1 New panel cut out line 2 Mount the installation plate to the panel cut out with M5 screws nuts and washers Use the existing screw holes 1MRS756375 K Section 4 Mounting 615 series 47 Installation Manual ...

Page 56: ...ion plate for replacing three BBC S_ relays 1 Installation plate 2 Torx head screw M5x16 3 Hexagon nut M5 4 Spring washer 3 Tighten the screws 4 Mount the new IED For ordering numbers see the ordering number table Section 4 1MRS756375 K Mounting 48 615 series Installation Manual ...

Page 57: ...EE A1B125A95524 V1 EN Figure 36 New panel cut out and screw hole dimensions for replacing a SPA 300 series relay A Min 186 mm B 161 5 1 mm C 224 mm D 176 mm E 7 mm 2 Drill new screw holes 4 5 mm to the panel according to the dimensional drawing 3 Mount the installation plate to the panel cut out with M5 thread forming screws 1MRS756375 K Section 4 Mounting 615 series 49 Installation Manual ...

Page 58: ...frame if needed For ordering numbers see the ordering number table 4 3 16 Replacing a SPA 300 series relay in 19 rack by a 615 series IED Mount the IED with the mounting frame to the panel cut out according to the rack mounting instructions No modifications are needed to the panel For replacement kit ordering numbers see the ordering number table Section 4 1MRS756375 K Mounting 50 615 series Insta...

Page 59: ...w compression type A MAX 5 5 mm B MAX 5 mm A A071180 V2 EN Figure 39 Insert bits for CT VT terminals of screw compression type A MIN 15 mm 5 2 Connecting wires All connections are made on the rear of the case No soldering is needed Open the screw compression type terminals before inserting any wires By default the terminals are closed at the time of delivery Use fine wire in door mounting 1MRS7563...

Page 60: ...ngth of the earth lead is long the cross section of the wire must be increased Use fine copper wire as the earth lead To connect a separate earth protection lead 1 Loosen the protective earth screw T20 to connect a separate earth protection lead 7 6 7 8 24 23 22 21 20 19 18 17 16 15 14 13 12 11 10 9 5 4 3 2 1 8 6 23 1 2 3 4 5 9 10 11 12 13 14 15 16 17 18 19 20 21 22 24 A070772 V1 EN Figure 40 The ...

Page 61: ... Connecting analog signals A connection diagram is needed to connect the analog signals When using the ring lug type for CT VT terminals 1 Open the lid that covers the ring lug fixing screw with the tip of a screwdriver Every fixing screw has its own lid 2 Remove the fixing screw 3 Slide the screw through the terminal lug and screw it back on 4 Close the lid 5 4 1 Connecting current and voltage in...

Page 62: ...ure 41 Example of AIM0004 card variant 4 I 3 U with 1 5 A Io channel GUID CAB8DAAA 8A15 4AF6 AFC7 CA232D253F3D V3 EN Figure 42 Example of AIM0005 card variant 7 I with 1 5 A Io channel Section 5 1MRS756375 K Connecting 54 615 series Installation Manual ...

Page 63: ... V3 EN Figure 43 Example of AIM0006 card variant 5 U GUID 7473CEBA AA9C 4F58 8091 F9717AEE7F3A V1 EN Figure 44 Example of AIM0013 card variant 4 I 3 U with 0 2 1 A Io channel 1MRS756375 K Section 5 Connecting 615 series 55 Installation Manual ...

Page 64: ...gure 45 Example of AIM0016 card variant 4 I with 1 5 A Io channel A071232 V4 EN Figure 46 Example of AIM0017 card variant 4 I with 0 2 1 A Io channel Section 5 1MRS756375 K Connecting 56 615 series Installation Manual ...

Page 65: ...e 47 Example of AIM0018 card variant 4 I Uo with 1 5 A Io channel A071234 V4 EN Figure 48 Example of AIM0019 card variant 4 I Uo with 0 2 1 A Io channel 1MRS756375 K Section 5 Connecting 615 series 57 Installation Manual ...

Page 66: ...suppress RF interference connect the RTD earth cable shield straight to the lead that connects to the protective earth screw and not to the protective screw itself The connection must be at least 355 mm from the protective earth screw GUID 965E94AF 4E0F 48D3 A46D 72228BD3A7E6 V1 EN Figure 49 Example of RTD0001 card variant 6 RTD 2 mA channel 5 4 3 Connecting IED with a test switch When the IED is ...

Page 67: ...erminal for binary input and output signal is dimensioned for one 0 5 2 5 mm2 wire or for two 0 5 1 0 mm2 wires See the specific card variant from the application manual GUID 1BE0210A D182 4354 916E EBEAF8F2BD48 V1 EN Figure 50 Example of BIO0005 card variant 8 BI 4 BO 1MRS756375 K Section 5 Connecting 615 series 59 Installation Manual ...

Page 68: ...5 6 Connecting power supply The IED s auxiliary voltage is connected to terminals X100 1 and X100 2 The positive lead is connected to terminal X100 1 The permitted auxiliary voltage range of the IED is marked on top of the IED s LHMI Section 5 1MRS756375 K Connecting 60 615 series Installation Manual ...

Page 69: ...nication check that the HW module has the correct communication interfaces The communication module is located on the left side of the IED when viewing the case from the rear See the technical manual for product specific communication interfaces 5 8 Energizing the IED Before connecting the auxiliary power check that the protective film is removed from top of the IED 1MRS756375 K Section 5 Connecti...

Page 70: ...V1 EN Figure 53 Removing the protective film During the start up all LEDs are lit for a short period Green Ready LED starts to flash LCD lights up and IED start up is displayed The main menu is displayed A steady green Ready LED indicates a successful start up If the IED detects a diagnostic error during start up the green Ready LED flashes and the internal fault code is displayed on the LCD Secti...

Page 71: ...ch as version and serial number The IED information is shown on the display for a few seconds when the device starts up The same information is found also in the IED menu 1 Select Main Menu Information 2 Select a submenu with and 3 Enter the selected submenu with 4 Browse the information with and The Product identifiers submenu contains product related information like product type serial number o...

Page 72: ...BB office or representative for consultation and instructions 6 5 Exchanging the IED To exchange the IED with another identical unit remove the IED and install the new one The exchangeable units can be found from the PartsOnLine system see www abb com partsonline Use of PartsOnLine requires user registration To exchange an IED to a different unit change the case and connect the wires Section 6 1MR...

Page 73: ...Section 7 Technical data 7 1 Case and HMI display variants 7 1 1 Front side of the IED IECA070904 V3 EN Figure 54 Small display 1MRS756375 K Section 7 Technical data 615 series 65 Installation Manual ...

Page 74: ...0 Large variable width 13x14 pixels 4 8 or more 1 Depending on the selected language Table 4 Large display Character size1 Rows in the view Characters per row Small mono spaced 6x12 pixels 10 20 Large variable width 13x14 pixels 8 8 or more 1 Depending on the selected language Section 7 1MRS756375 K Technical data 66 615 series Installation Manual ...

Page 75: ...7 1 2 Rear side of the IED A070596 V1 EN Figure 56 Rear view of an 615 series IED with communication module 1MRS756375 K Section 7 Technical data 615 series 67 Installation Manual ...

Page 76: ...615 series main dimensions A 177 mm B 177 mm 4U C 164 mm D 153 mm E 48 mm F 160 mm Table 5 Dimensions Description Value Width frame 177 mm case 164 mm Height frame 177 mm 4U case 160 mm Table continues on next page Section 7 1MRS756375 K Technical data 68 615 series Installation Manual ...

Page 77: ...lete IED 4 1 kg plug in unit only 2 1 kg 7 3 Enclosure class Table 6 Degree of protection of flush mounted IED Description Value Front side IP 54 Rear side connection terminals IP 20 1MRS756375 K Section 7 Technical data 615 series 69 Installation Manual ...

Page 78: ...70 ...

Page 79: ...8 test switch the test switch is not included in the delivery 2RCA021952A0003 19 rack mounting kit for one IED and one RTXP24 test switch the test switch is not included in the delivery 2RCA022561A0003 Replacement kit for a Strömberg SP_J40 series relay cut out in the center of the installation plate 2RCA027871A0001 Replacement kit for a Strömberg SP_J40 series relay cut out on the left or the rig...

Page 80: ...72 ...

Page 81: ...station communication and modeling IED Intelligent electronic device IET600 Integrated Engineering Toolbox in PCM600 LCD Liquid crystal display LCP Liquid crystal polymer LED Light emitting diode LHMI Local human machine interface PA Polyamide PBT Polybutylene terephthalate PC 1 Personal computer 2 Polycarbonate PCM600 Protection and Control IED Manager RoHS Restriction of the use of certain hazar...

Page 82: ...74 ...

Page 83: ...75 ...

Page 84: ...Contact us ABB Oy Distribution Automation P O Box 699 FI 65101 VAASA Finland Phone 358 10 22 11 Fax 358 10 22 41094 www abb com substationautomation 1MRS756375 K Copyright 2012 ABB All rights reserved ...