GUID-83B0F607-D898-403A-94FD-7FE8D45C73FF v6
Table 65. Insulation liquid monitoring function SSIML
Function
Range or value
Accuracy
Oil alarm level
1.00-100.00
±10.0% of set value
Oil lockout level
1.00-100.00
±10.0% of set value
Temperature alarm level
-40.00-200.00
±2.5% of set value
Temperature lockout level
-40.00-200.00
±2.5% of set value
Time delay for oil alarm
(0.000-60.000) s
±0.2% or ±250ms whichever is greater
Reset time delay for oil alarm
(0.000-60.000) s
±0.2% or ±250ms whichever is greater
Time delay for oil lockout
(0.000-60.000) s
±0.2% or ±250ms whichever is greater
Time delay for temperature alarm
(0.000-60.000) s
±0.2% or ±250ms whichever is greater
Reset time delay for temperature alarm
(0.000-60.000) s
±0.2% or ±250ms whichever is greater
Time delay for temperature lockout
(0.000-60.000) s
±0.2% or ±250ms whichever is greater
GUID-B6799420-D726-460E-B02F-C7D4F1937432 v7
Table 66. Breaker monitoring SSCBR
Function
Range or value
Accuracy
Alarm level for open and close travel time
(0 – 200) ms
±3 ms
Alarm level for number of operations
(0 – 9999)
-
Independent time delay for spring charging
time alarm
(0.00 – 60.00) s
±0.2% or ±30 ms whichever is greater
Independent time delay for gas pressure alarm (0.00 – 60.00) s
±0.2% or ±30 ms whichever is greater
Independent time delay for gas pressure
lockout
(0.00 – 60.00) s
±0.2% or ±30 ms whichever is greater
CB Contact Travel Time, opening and closing
±3 ms
Remaining Life of CB
±2 operations
Accumulated Energy
±1.0% or ±0.5 whichever is greater
M12700-1 v4
Table 67. Event list
Function
Value
Buffer capacity
Maximum number of events in the list
1000
Resolution
1 ms
Accuracy
Depending on time synchronizing
M13765-1 v4
Table 68. Indications
Function
Value
Buffer capacity
Maximum number of indications presented for single disturbance
96
Maximum number of recorded disturbances
100
1MRK 505 362-BEN B
Busbar protection REB650 2.1 IEC
Product version: 2.1
ABB
47