M13304-1 v13
Table 30. Two step overvoltage protection OV2PTOV
Function
Range or value
Accuracy
Operate voltage, step 1 and 2
(1.0-200.0)% of
UBase
±0.5% of U
r
at U ≤ U
r
±0.5% of U at U > U
r
Absolute hysteresis
(0.0–50.0)% of
UBase
±0.5% of U
r
at U ≤ U
r
±0.5% of U at U > U
r
Inverse time characteristics for steps 1 and 2, see table
-
See table
Definite time delay, low step (step 1) at 0 to 1.2 x U
set
(0.00 - 6000.00) s
±0.2% or ±45 ms whichever is greater
Definite time delay, high step (step 2) at 0 to 1.2 x U
set
(0.000-60.000) s
±0.2% or ±45 ms whichever is greater
Minimum operate time, Inverse characteristics
(0.000-60.000) s
±0.2% or ±45 ms whichever is greater
Operate time, start at 0 to 2 x U
set
Min. = 15 ms
Max. = 30 ms
-
Reset time, start at 2 to 0 x U
set
Min. = 15 ms
Max. = 30 ms
-
Operate time, start at 0 to 1.2 x U
set
Min. = 20 ms
Max. = 35 ms
-
Reset time, start at 1.2 to 0 x U
set
Min. = 5 ms
Max. = 25 ms
-
Critical impulse time
10 ms typically at 0 to 2 x U
set
-
Impulse margin time
15 ms typically
-
M13317-2 v13
Table 31. Two step residual overvoltage protection ROV2PTOV
Function
Range or value
Accuracy
Operate voltage, step 1 - step 2
(1.0-200.0)% of
UBase
± 0.5% of U
r
at U ≤ U
r
± 0.5% of U at U > U
r
Absolute hysteresis
(0.0–50.0)% of
UBase
± 0.5% of U
r
at U ≤ U
r
± 0.5% of U at U > U
r
Inverse time characteristics for low and high step, see table
-
Definite time delay low step (step 1) at 0 to 1.2 x U
set
(0.00–6000.00) s
± 0.2% or ± 45 ms whichever is
greater
Definite time delay high step (step 2) at 0 to 1.2 x U
set
(0.000–60.000) s
± 0.2% or ± 45 ms whichever is
greater
Minimum operate time
(0.000-60.000) s
± 0.2% or ± 45 ms whichever is
greater
Operate time, start at 0 to 2 x U
set
Min. = 15 ms
Max. = 30 ms
-
Reset time, start at 2 to 0 x U
set
Min. = 15 ms
Max. = 30 ms
-
Operate time, start at 0 to 1.2 x U
set
Min. = 20 ms
Max. = 35 ms
-
Reset time, start at 1.2 to 0 x U
set
Min. = 5 ms
Max. = 25 ms
-
Critical impulse time
10 ms typically at 0 to 2 x U
set
-
Impulse margin time
15 ms typically
-
1MRK 505 362-BEN B
Busbar protection REB650 2.1 IEC
Product version: 2.1
38