Secondary system supervision
M16069-1 v11
Table 32. Fuse failure supervision FUFSPVC
Function
Range or value
Accuracy
Operate voltage, zero sequence
(1-100)% of UBase
±0.5% of U
r
Operate current, zero sequence
(1–100)% of IBase
±0.5% of I
r
Operate voltage, negative sequence
(1-100)% of UBase
±0.5% of U
r
Operate current, negative sequence
(1–100)% of IBase
±0.5% of I
r
Operate voltage change level
(1-100)% of UBase
±10.0% of U
r
Operate current change level
(1–100)% of IBase
±10.0% of I
r
Operate phase voltage
(1-100)% of UBase
±0.5% of U
r
Operate phase current
(1–100)% of IBase
±0.5% of I
r
Operate phase dead line voltage
(1-100)% of UBase
±0.5% of U
r
Operate phase dead line current
(1–100)% of IBase
±0.5% of I
r
Operate time, start, 1 ph, at 1 to 0 x U
r
Min. = 10 ms
Max. = 25 ms
-
Reset time, start, 1 ph, at 0 to 1 x U
r
Min. = 15 ms
Max. = 30 ms
-
1MRK 505 362-BEN B
Busbar protection REB650 2.1 IEC
Product version: 2.1
ABB
39