- 94 -
000979AG
5 - Installation
C
onfigurable Relay connection (ALARM and AUX)
The inverter is equipped with 2 multifunction relays
33
with
configurable activation. It can be connected with normally
open contact (being connected between the N.O. terminal
and the common contact C) and with normally closed
contact (being connected between the N.C. terminal and the
common contact C). Different types of devices (light, sound,
etc.) can be connected to the relay, provided they comply
with the following requirements:
Alternating current
Maximum Voltage: 160 V AC Maximum Current: 6 A
Direct current
Maximum Voltage: 30 V DC Maximum Current: 3 A
Cable requirements
External diameter: 6 mm
Conductor cross-section: from 28 to 16 AWG
This contact can be used in different operating configurations that can be selected by
accessing the relevant section in the web user Interface “SETTINGS > Digital Outputs”.
J2
X1
X2
S5
S4
J7
J1
J5
J6
1
2
1
8
7
4
3
2
ZGN.V2Q15.2
N.C
N.O
C
N.C.
N.O.
C
AUX
ALARM
33