8 - Maintenance
5.
Open the negative fuse board
• Remove the two M5 screws from the negative string fuses plate
20
.
• Tilt the negative string fuses plate
20
.
• Use a screwdriver, to lock the positive string fuses plate
6.
Disconnect the cables from the spring clamps.
During this operation take note of the cables position in order to
connect they in the same way in the new board.
A)
Insert a flat screwdriver in the slot (see the picture); lightly press
the screwdriver from the top to the bottom; insert the screwdriver until
the clamp opens.
B) Insert the cable in the clamp.
C) Remove the screwdriver.
A
B
C
7.
Disconnect the surge arresters monitoring connector
8.
Remove the card through the three screws