66 Chapter 7
7.5.8 Kick Start
This parameter makes it possible to tune the kick start voltage level which is ap-
plied for a short time duration, before a normal start ramp is performed. Kick Start
provides enough torque during start, but still ensuring a soft start.
It can be set on any of the predefined voltage levels. For each voltage level there is
a fixed time duration relation (t), which is increasing with the different kick voltage
levels. This function can be useful for applications with high initial friction or having
a need of extra power in the first part of the start, as jammed pumps or
conveyor
belts. See table 7.2 and graph in figure 7.19.
Table 7.2 Kick Start settings
Kick start setting
Kick start voltage
Ue
(percent)
Kick start time
t (s)
30
30
0.30
35
35
0.35
40
40
0.40
45
45
0.45
50
50
0.50
55
55
0.55
60
60
0.60
65
65
0.65
70
70
0.70
75
75
0.75
80
80
0.80
85
85
0.85
90
90
0.90
95
95
0.95
100
100
1.00
Note that the
Current Limit function is not working during Kick Start.
Display
Default
value
Setting range
Description
Operational time
Normal ramp
Ramp with Kick Start
t
Ue
Set Initial Voltage
OFF
OFF, 30...100 % Level of Kick Start
Figure 7.18: Kick Start parameter displayed
Figure 7.19: The function of Kick Start
Operational time
Normal ramp
Ramp with Kick Start
t
Ue
Set Initial Voltage